DG SIZE Ccalculator

This document calculates the sizing requirements for a diesel generator set. It determines that a 30 KVA generator is required to power a lift load of 30 KW at 0.8 power factor. It also provides calculations to determine the generator efficiency of 63%, fuel consumption rate of 23.11 liters/hour for a 115 KVA generator operating at full load, and the unit cost of power output at 4 Rs/KWH.

Uploaded by

KSX
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
268 views

DG SIZE Ccalculator

This document calculates the sizing requirements for a diesel generator set. It determines that a 30 KVA generator is required to power a lift load of 30 KW at 0.8 power factor. It also provides calculations to determine the generator efficiency of 63%, fuel consumption rate of 23.11 liters/hour for a 115 KVA generator operating at full load, and the unit cost of power output at 4 Rs/KWH.

Uploaded by

KSX
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

CALCULATE SIZE OF DIESEL GENERATOR SET Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.

com
System Voltage ( P-P ) 415 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear Load: UPS,Invertor,Ballast,VFD
Future Load Expansion 0% % 1
Average Intermittent Use of
0.8 (0.7 To 1.0) 0.8
Equipment
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load Full Full Full
Sr. Starting Running Diversity Motor Starting Starting Starting
Equipment Load Type Supply Qty Load Load Load
No Load Kw/Hp P.F P.F Factor Starter Amp Kva Kw
Kva Kw Amp RESULTS
0 0 0 0 0 0 Starting Kva 37
0 0 0 0 0 0 Starting Kw 30
0 0 0 0 0 0 Starting Amp 52
Lift Linear 3Ph 1 50 Hp 0.8 0.8 0.8 Dol 52 37 30 37 30 52 Running Kva 37
0 0 0 0 0 0 Running Kw 30
0 0 0 0 0 0 Running Amp 52
0 0 0 0 0 0 Alternator Details
0 0 0 0 0 0 Voltage (P-N) 230
0 0 0 0 0 0 Efficiency 80%
0 0 0 0 0 0 Engine Overload Capacity 130% (Appro 130% To 150%)
0 0 0 0 0 0
0 0 0 0 0 0 Required Generator Rating
0 0 0 0 0 0 Generator KVA 30 (Select D.G near This Value)
0 0 0 0 0 0 Engine KW 31
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0 Calculate D.G Set Efficiency & Unit Calculate Approximate
0 0 0 0 0 0 Rate of Power Fuel Consumption
0 0 0 0 0 0 D.G Size ( Kva ) 1000
0 0 0 0 0 0 D.G P.F 1 D.G Size (Kva) 115
0 0 0 0 0 0 D.G Running Hours 20 D.G P.F 0.8
0 0 0 0 0 0 Diesel Consumption (Liter) 1000 D.G Operation Full Load
0 0 0 0 0 0 KWH Reading of Meter 10000
0 0 0 0 0 0 M.F of KWH Meter 1 Required Diesel
0 0 0 0 0 0 Diesel Rate /Liter (Rs) 40 Liter/Hour 23.11
0 0 0 0 0 0 Efficiency of D.G 63%
0 0 0 0 0 0 KWH/Liter (Unit Per Liter) 10
0 0 0 0 0 0 Unit Rate of Power (Rs) 4.0
0 0 0 0 0 0