This document provides a design basis report and structural stability certificate for a proposed steel framed structure to support solar panels in Medchal, Hyderabad. The structure was designed according to IS 800 and IS 875 to withstand wind speeds up to 44 m/s. Section sizes of 150x150x6mm tubular SHS for columns and rafters and 100x100x6mm tubular SHS for purlins were selected. Load calculations and structural analysis using STAAD Pro software found the maximum interaction ratio to be 0.72, confirming the structural stability of the proposed design.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
212 views10 pages

STR Report

This document provides a design basis report and structural stability certificate for a proposed steel framed structure to support solar panels in Medchal, Hyderabad. The structure was designed according to IS 800 and IS 875 to withstand wind speeds up to 44 m/s. Section sizes of 150x150x6mm tubular SHS for columns and rafters and 100x100x6mm tubular SHS for purlins were selected. Load calculations and structural analysis using STAAD Pro software found the maximum interaction ratio to be 0.72, confirming the structural stability of the proposed design.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

JAGMOHAN VIJAY JANDHAYA

BE(CIVIL), MTECH(STRUCTURES), (PHD)

TO WHOM SO EVER IT MIGHT CONCERN


DESIGN BASIS REPORT AND STRUCTURAL STABILITY CERTIFICATE

A steel framed structure to support solar panels has been proposed for erection at Medchal,
Hyderabad, the structure has been designed as per the requirement of design standards of IS
800. IS 875 has been used to calculate all loads including but not limited to winds loads. Staad
pro software has been used for design verification. The structure as per the required section
sizes has been designed and verified for structural stability and integrity. The structure can
withstand wind speed of 44 m/s or 98 miles/hour. I certify that if the frame is erected as per
the sizes given below, the structure would be stable and in confirmation with all check and
balances.

SECTION TYPE (COLUMN, RAFTER, PURLIN) SIZE SIZE SPECIIFICATION


1. COLUMNS TUB (SHS) 150 X 150 X 6 MM
2. RAFTERS TUB (SHS) 150 X 150 X 6 MM
3. PURLINS TUB (SHS) 100 X 100 X 6 MM

DESIGN CALCULATIONS:
DEAD LOAD OF SOLAR PANNEL = 20 kG/m2 = 0.2 kN/m2
WIND LOAD CALCULATIONS
Basic wind speed at Hyderabad, (Medchal) = 44 m/s = Vb

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

Structure max length (dimensions.) = 48 m. (CLASS B.)


Building is in Terrain category 2.
K2 = 0.98.

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

K3 = 1.
Design wind speed = K1 x K2 x K3 x Vb = 0.91 x 0.98 x 1 x 44 = 39.23 m/s.= Vz
(REFER IS :875 PART 3 :1987 SECTION 5.3 & STRSSOLAR 5.3.1,5.3.2)

Design wind pressure = 0.6 x Vz2 = 0.6 x (39.23)2 = 923.40 N/m2 = 0.923 kN/m2

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

Load combination as per IS 800: 1.0 DEAD LOAD + 1.0 WIND LOAD.
DESIGN OUTPUT: MAXIMUM INTERACTION RATIO: 0.72 < 1.00. HENCE SAFE.

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

Force co-efficient on Column Member =2

External Pressure Co-efficient on Panel = 1.2, 1.0 & 0.8 for Suction

= 0.8 & 0.4 for Pressure

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

PRELIMINARY LOADS & LOAD COMBINATIONS: -

The members are checked for all critical loads including the combinations as per
IS :800: 1984

Preliminary load cases for in place Analysis:

1 Dead Load DL

2 Wind load WL Suction

3 Wind load WL Pressure

LOAD COMBINATION AS PER IS:800: 1984.


******************************************

LOAD COMB 101 COMBINATION

1 1.0 2 1.0

LOAD COMB 102 COMBINATION

1 1.0 3 1.0

***************************************

STAAD INPUT:

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]
JAGMOHAN VIJAY JANDHAYA
BE(CIVIL), MTECH(STRUCTURES), (PHD)

Supports are considered as fixed at base.

LOAD INPUT

7-1-29/B/4, PARALLEL RAILWAY TRACK ROAD, LEELA NAGAR, BEGUMPET, TELANGANA 500016,
(M) 9885764695, EMAIL: [email protected]