ApplicationNote Harmonics Sep2014
ApplicationNote Harmonics Sep2014
THD
. There are two different
x1
Capacitors are short circuit for high frequencies. Recommendations for new installations:
Power factor correction capacitors are designed Estimate the level of harmonics
for the fundamental harmony. In presence of Install power meters that can measure
harmonics, their impedance is lower which accurately at least 40 harmonics, THD, TDD
result in increasing the amount of harmonics, and K-Factor
capacitor overheating, potentially permanent Specify limits for alerts and configure the
damage to capacitors and resonance between power meters accordingly
the capacitors and transformers. The solution is Consider harmonics filtration solutions (low
installing series reactor to each capacitor that harmonic pollution loads, passive filers,
limit these phenomenon but increase the active filters, retuned power factor etc.)
system losses.
Recommendation for existing installations:
Perform harmonics study for a week and
Directions of Harmonics
compare to international standards. Check
As the rule of thumb above, utilities deliver the levels of at least 40 harmonics, THD,
voltage harmonics to the consumers and TDD and K-Factor. It is possible to use
consumers inject current harmonics toward the temporary handheld meters. However,
power source. However, voltage and current permanent installation is preferred.
harmonics increase each other, particularly in Specify limits for alerts and configure the
situations of resonance. This makes it power meters accordingly
complicated to identify which part has a higher Consider harmonics filtration solutions (low
responsibility for the higher harmonics. harmonic pollution loads, passive filers,
Precise analysis of source of harmonics is based active filters, retuned power factor etc.)
on impedances and network simulation.
However, there are two practices that allow
reasonable evaluation of the direction: