CT Calculation

This document summarizes the calculation of CT parameters for a busbar protection system. It provides the short circuit current, CT ratio, secondary circuit impedances, and device data. It then calculates the required CT kneepoint voltage and saturation time. The calculation shows the selected CT with a 1600:1 ratio and 800V kneepoint voltage meets the requirements for the protection system with an estimated saturation time of 9.97ms.

Uploaded by

Theresia Andina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
477 views

CT Calculation

This document summarizes the calculation of CT parameters for a busbar protection system. It provides the short circuit current, CT ratio, secondary circuit impedances, and device data. It then calculates the required CT kneepoint voltage and saturation time. The calculation shows the selected CT with a 1600:1 ratio and 800V kneepoint voltage meets the requirements for the protection system with an estimated saturation time of 9.97ms.

Uploaded by

Theresia Andina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CT CALCULATION

Busbar Protection
CT Data
Short Circuit Current Isc : 40 kA
ClassAccuracy : PX
Rated Primary Current Ip : 1600 A
Rated Secondary Current Is : 1A
𝐼𝑝
Ratio CT K = 𝐼𝑠 K : 1600
Secondary winding resistance Rct : 6 ohm
Kneepoint Voltage of CT Vk : 800 V
(*) Note : CT Data Kneepoint Voltage and resistance is taken from Mega Project CT Data

Secondary Circuit Data


A Cable Data
2
Cable Size S : 10 mm
Length of cable L : 1000 m
DC Resistance at 20o Rc : 1.83 ohm/km
Lead Resistance 𝑅𝐿 = 2𝑥 𝑅𝐶 𝑥 𝐿 RL : 3.66 ohm
(*) Note : Cable Data is taken from Kabelindo Cable Data Sheet

B Device Data (Multilin B30)


Device Burden Sd : 0.2 VA
Device Resistance Rd : 0.2 ohm

Calculation
A Kneepoint Requirement
The required Kneepoint Voltage of CT is calculated as following
𝑉𝑘𝑟 = 𝐾𝑡𝑓 𝑥𝐼𝑓 𝑥 (𝑅𝑐𝑡 + 𝑅𝐿 + 𝑅𝑑 )
Where :
Ktf is CT overdimensioning factor for UR B30 ver 7.xx : 3
If is fsecondary fault current 𝐼𝑠𝑐 : 25 A
𝐼𝑓 =
𝐾
Vkr : 739.5

The required kneepoint voltage is less than kneepoint voltage of CT


739.5 < 800

B CT Requirement
The Required Saturation Time (Tsat) is calculated as following

Where :
Tsat can be determined using "CT Saturation Time Estimator", shown in Fig. 1
from http://www.gegridsolutions.com/app/ViewFiles.aspx?prod=b90&type=9
Tsat : 9.97 ms

Conclusion
CT Ratio : 1600/1
CT Class : PX
Kneepoint Voltage : 800