Amps X 1000 Bus8 (Nom. KV 0.433, Plot Ref. KV 0.433) : T3 FLA - Other 65

The document shows protection curves for two different circuits on buses 8 and 7. It includes protection devices for an incomer circuit and a transformer, along with their current transformer ratios, protection characteristics like inverse time overcurrent settings, and pickup thresholds. Ratings for the transformer and busduct are also provided.

Uploaded by

bjb767
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views

Amps X 1000 Bus8 (Nom. KV 0.433, Plot Ref. KV 0.433) : T3 FLA - Other 65

The document shows protection curves for two different circuits on buses 8 and 7. It includes protection devices for an incomer circuit and a transformer, along with their current transformer ratios, protection characteristics like inverse time overcurrent settings, and pickup thresholds. Ratings for the transformer and busduct are also provided.

Uploaded by

bjb767
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 1000 Bus8 (Nom. kV=0.433, Plot Ref. kV=0.

433)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
T3
FLA - Other 65
500 500

300 300

Incomer-1 PMCC - P
OC1
ALSTOM
100 100
P127
CT Ratio 2500:5
IEC - Extremely Inverse
50 50
Pickup = 0.979 (0.1 - 25 xCT Sec)
Time Dial = 0.359
30 3x = 3.59 s, 5x = 1.2 s, 8x = 0.456 s 30
Inst = 7.03 (0.5 - 40 xCT Sec)
Time Delay = 0.05 s

11kV ICOG - P
10 OC1 10

ABB
REF 601
5 CT Ratio 100:1 5

Seconds
Seconds

Extremely Inverse
3
Pickup = 0.924 (0.2 - 1 xCT Sec) 3
Time Dial = 1.19
3x = 11.9 s, 5x = 3.97 s, 8x = 1.51 s
Inst = 15 (2 - 15 xCT Sec)
Time Delay = 0.15 s
1 T3 1

1600 kVA (Secondary) 6.48 %Z


Delta-Wye Solid Grd
.5 .5

.3 .3 ±
11kV ICOG
I>

T3
Inrush Bus7

Multiplier = 8 xFLA (17067.17 Amps)


.1 Duration = 5 Cycles .1

T3
1600 kVA
.05 .05

.03 .03
BusDuct1

R Incomer-1 PMCC

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 1000 Bus8 (Nom. kV=0.433, Plot Ref. kV=0.433)


ETAP Star 16.0.0C
.01968 .05 .1 .3 .5 1 3 5 10 30 50 100 393.6

Amps X 1000 Bus7 (Nom. kV=11, Plot Ref. kV=11)