Air-Cooled Rotary Screw Chillers: Product Manual
Air-Cooled Rotary Screw Chillers: Product Manual
Group: Chiller
Date: October 1999
Supersedes: PM ALS-1
Introduction...................................................................................................................4
Customer Benefits..........................................................................................................5
Design Advantages.........................................................................................................8
Controls.......................................................................................................................10
Selection Procedures....................................................................................................13
Application Adjustment Factors....................................................................................15
Performance Data ........................................................................................................17
Part Load Data ............................................................................................................23
Pressure Drop..............................................................................................................24
Sound Data..................................................................................................................26
Electrical Data..............................................................................................................30
Field Wiring Diagram....................................................................................................45
Physical Data...............................................................................................................46
Dimensions, ALS .........................................................................................................51
Installation and Application...........................................................................................55
Electrical Connections ..................................................................................................59
Remote Evaporator......................................................................................................60
Dimensions, Remote Evaporator...................................................................................68
Standard Features........................................................................................................72
Optional Features.........................................................................................................74
Specifications...............................................................................................................76
UNSURPASSED EFFICIENCY
• Single-screw compressor design
• Electronic expansion valve control
• Built-in economizer design
• High efficiency lanced condenser fins
QUIET OPERATION
• Tuned discharge chamber
• Composite gaterotor material
• Liquid refrigerant-cooled motor
• Virtually vibration-free operation
OUTSTANDING RELIABILITY
• Rugged compressor design
• Low thrust loads on bearings
• Advanced composite gaterotor material
• Liquid refrigerant-cooled motors
• Multiple compressors with…
• Independent refrigerant circuits
• Proactive control logic
• Full factory run-testing assures trouble-free operation
• McQuayService start-up
Unsurpassed efficiency
• Zero clearance fit between the two gaterotors and main screw rotor virtually eliminates
leakage between the high and low pressure sides during compression. Special gaterotor
material made from multiple layers of an advanced composite, temperature stable
material makes a zero clearance design possible.
• An internal economizer system enhances the unit's refrigeration effect providing more
BTUs per pound of refrigerant circulated. The result is higher efficiency and lower
operating costs when compared to typical chillers without economizers.
• The ALS screw compressors utilize a liquid refrigerant injection system, meaning only a
fraction of the oil is required when compared to oil injection systems. Oil drag that is
found in oil injected compressors has been eliminated. Less power is required to drive
the compression components (rotors) resulting in a more efficient unit.
• With the liquid injection design, the refrigerant vapor entering the condenser is at a
saturated condition; no desuperheating takes place. This allows the condenser to be fully
utilized for condensing and operate more efficiently.
• The ALS air-cooled chiller is equipped with the most advanced means of refrigerant
flow control available. An electronic expansion valve coupled with MicroTech fuzzy
logic control provides excellent operating efficiencies both at full and part load operation.
Unmatched Serviceability
• Field serviceability has not been sacrificed to meet design objectives for performance on
the ALS screw chiller. Inspection covers allow for an excellent visual inspection of the
main screw and gaterotors.
• Compressors are located on the outside edges of the base allowing them to be easily
removed from within the unit. This inherent unit design allows for quick access to the
compressors if necessary.
• Carefully laid-out refrigerant piping and components allow for excellent serviceability of
the unit.
Economizer Design
The ALS screw compressor
incorporates an integral
economizer where centrifugal
force is utilized to separate the
flash gas from the liquid
refrigerant prior to it entering the
evaporator. A small centrifugal
liquid/vapor separator mounted
on the rear of the compressor
shaft achieves the separation.
The economizer itself is within
the envelope of the standard
motor housing.
Controls
Fouling Factor
Performance tables are based on water with a fouling factor of 0.0001 (0.0176) per ARI
550/590-98. As fouling is increased, performance decreases. For performance at other
fouling factors refer to Table 2.
Foreign matter in the chilled water system will adversely affect the heat transfer capability
of the evaporator, and could increase the pressure drop and reduce the water flow. To
insure optimum unit operation, proper water treatment and filtration must be maintained.
Table 3a, Ethylene Glycol Adjustment Table 3b, Propylene Glycol Adjustment
Freeze Freeze
% Point Cap. Power Flow PD % Point Cap. Power Flow PD
E.G. °F (°C) P.G. °F (°C)
10 26 (-3) 0.991 0.996 1.013 1.070 10 26 (-3) 0.987 0.992 1.010 1.068
20 18 (-8) 0.982 0.992 1.040 1.129 20 19 (-7) 0.975 0.985 1.028 1.147
30 7 (-14) 0.972 0.986 1.074 1.181 30 9 (-13) 0.962 0.978 1.050 1.248
40 -8 (-22) 0.961 0.976 1.121 1.263 40 -6 (-21) 0.946 0.971 1.078 1.366
50 -29 (-34) 0.946 0.966 1.178 1.308 50 -28 (-33) 0.929 0.965 1.116 1.481
Units operating with glycol are not included in the ARI Certification Program
5.0 (41.0°F) 434.6 126.9 3.0 416.9 140.8 2.7 399.2 154.8 2.3 381.6 168.8 2.1 363.9 183.0 1.8
6.0 (42.8°F) 445.5 127.9 3.1 427.5 142.0 2.7 409.6 156.2 2.4 391.6 170.4 2.1 373.6 184.5 1.9
125B 7.0 (44.6°F) 456.2 128.9 3.2 438.1 143.3 2.8 419.9 157.6 2.4 401.7 171.9 2.1 383.4 186.0 1.9
8.0 (46.4°F) 467.0 129.8 3.2 448.6 144.4 2.8 430.3 159.0 2.5 411.8 173.6 2.2 393.1 187.5 1.9
9.0 (48.2°F) 477.7 130.8 3.3 459.1 145.5 2.8 440.5 160.4 2.5 421.9 175.2 2.2 402.8 190.0 2.0
10.0 (50.0°F) 488.5 131.7 3.3 469.7 146.8 2.9 450.9 161.8 2.5 432.0 176.9 2.2 412.5 192.3 2.0
5.0 (41.0°F) 487.6 143.7 3.1 467.8 159.5 2.7 447.9 175.4 2.3 428.1 191.1 2.1 408.3 207.3 1.8
6.0 (42.8°F) 499.8 144.8 3.1 479.6 160.9 2.7 459.5 176.9 2.4 439.4 193.0 2.1 419.2 208.9 1.9
140B 7.0 (44.6°F) 511.8 145.9 3.2 491.5 162.2 2.8 471.1 178.5 2.4 450.7 194.7 2.1 430.2 210.7 1.9
8.0 (46.4°F) 523.9 146.9 3.2 503.3 163.6 2.8 482.7 180.0 2.5 462.1 196.5 2.2 441.0 212.3 1.9
9.0 (48.2°F) 536.0 148.1 3.3 515.1 164.8 2.9 494.3 181.6 2.5 473.4 198.5 2.2 451.9 215.2 2.0
10.0 (50.0°F) 548.1 149.2 3.3 526.9 166.2 2.9 505.9 183.3 2.5 484.7 200.3 2.2 462.8 217.7 2.0
5.0 (41.0°F) 544.2 157.9 3.1 522.0 175.2 2.7 499.8 192.6 2.4 477.7 210.0 2.1 455.7 227.7 1.8
6.0 (42.8°F) 557.7 159.1 3.1 535.2 176.7 2.7 512.8 194.3 2.4 490.4 212.0 2.1 467.8 229.5 1.9
155B 7.0 (44.6°F) 571.2 160.3 3.2 548.5 178.2 2.8 525.7 196.1 2.4 503.0 213.9 2.2 480.1 231.4 1.9
8.0 (46.4°F) 584.7 161.4 3.2 561.6 179.7 2.8 538.7 197.8 2.5 515.6 215.9 2.2 492.2 233.3 2.0
9.0 (48.2°F) 598.1 162.7 3.3 574.8 181.0 2.9 551.6 199.5 2.5 528.3 218.0 2.2 504.3 236.4 2.0
10.0 (50.0°F) 611.6 163.9 3.3 588.0 182.6 2.9 564.5 201.3 2.6 540.9 220.0 2.3 516.4 239.2 2.0
5.0 (41.0°F) 593.6 175.8 3.1 569.4 195.1 2.7 545.3 214.5 2.3 521.1 233.8 2.1 497.1 253.5 1.8
6.0 (42.8°F) 608.5 177.1 3.1 583.9 196.8 2.7 559.4 216.4 2.4 534.9 236.1 2.1 510.3 255.6 1.9
170B 7.0 (44.6°F) 623.1 178.5 3.2 598.3 198.5 2.8 573.5 218.4 2.4 548.7 238.2 2.1 523.7 257.7 1.9
8.0 (46.4°F) 637.8 179.8 3.2 612.7 200.1 2.8 587.7 220.2 2.5 562.5 240.4 2.2 536.9 259.7 1.9
9.0 (48.2°F) 652.5 181.2 3.3 627.1 201.6 2.8 601.7 222.2 2.5 576.3 242.8 2.2 550.1 263.2 2.0
10.0 (50.0°F) 667.2 182.5 3.3 641.5 203.3 2.9 615.8 224.2 2.5 590.1 245.0 2.2 563.4 266.3 2.0
5.0 (41.0°F) 604.2 170.4 3.1 579.6 189.2 2.7 555.0 208.0 2.4 530.5 226.7 2.1 506.0 245.8 1.9
6.0 (42.8°F) 619.3 171.7 3.2 594.3 190.8 2.8 569.4 209.8 2.5 544.5 228.9 2.2 519.4 247.8 1.9
175B 7.0 (44.6°F) 634.2 173.1 3.3 609.0 192.4 2.8 583.7 211.7 2.5 558.5 230.9 2.2 533.1 249.9 2.0
8.0 (46.4°F) 649.2 174.3 3.3 623.6 194.0 2.9 598.2 213.5 2.5 572.6 233.1 2.2 546.5 251.8 2.0
9.0 (48.2°F) 664.2 175.6 3.4 638.3 195.4 2.9 612.5 215.4 2.6 586.6 235.4 2.3 559.9 255.2 2.0
10.0 (50.0°F) 679.1 176.9 3.4 652.9 197.1 3.0 626.8 217.3 2.6 600.6 237.5 2.3 573.4 258.2 2.0
5.0 (41.0°F) 643.1 184.8 3.1 616.9 205.1 2.7 590.7 225.5 2.4 564.6 245.8 2.1 538.5 266.5 1.9
6.0 (42.8°F) 659.2 186.2 3.2 632.5 206.8 2.8 606.1 227.5 2.4 579.5 248.1 2.1 552.8 268.6 1.9
185B 7.0 (44.6°F) 675.0 187.6 3.2 648.2 208.6 2.8 621.3 229.5 2.5 594.5 250.4 2.2 567.4 270.9 1.9
8.0 (46.4°F) 691.0 188.9 3.3 663.7 210.3 2.9 636.6 231.5 2.5 609.4 252.7 2.2 581.7 273.0 2.0
9.0 (48.2°F) 706.9 190.4 3.3 679.3 211.9 2.9 651.9 233.5 2.6 624.3 255.2 2.3 595.9 276.7 2.0
10.0 (50.0°F) 722.8 191.8 3.4 694.9 213.7 3.0 667.1 235.6 2.6 639.3 257.5 2.3 610.3 280.0 2.0
5.0 (41.0°F) 664.3 191.5 3.1 637.2 212.5 2.7 610.2 233.7 2.4 583.2 254.7 2.1 556.3 276.2 1.9
6.0 (42.8°F) 680.9 193.0 3.2 653.4 214.4 2.8 626.0 235.7 2.4 598.6 257.2 2.1 571.1 278.4 1.9
195B 7.0 (44.6°F) 697.3 194.5 3.2 669.5 216.2 2.8 641.8 237.9 2.5 614.1 259.5 2.2 586.1 280.7 1.9
8.0 (46.4°F) 713.8 195.8 3.3 685.6 218.0 2.9 657.6 239.9 2.5 629.5 261.9 2.2 600.8 283.0 2.0
9.0 (48.2°F) 730.2 197.4 3.3 701.7 219.6 2.9 673.3 242.1 2.6 644.9 264.5 2.3 615.6 286.7 2.0
10.0 (50.0°F) 746.6 198.8 3.4 717.9 221.5 3.0 689.1 244.2 2.6 660.4 266.9 2.3 630.4 290.2 2.0
5.0 (41.0°F) 713.8 198.6 3.1 684.7 220.5 2.7 655.6 242.4 2.4 626.6 264.2 2.1 597.7 286.5 1.9
6.0 (42.8°F) 731.6 200.1 3.2 702.0 222.3 2.8 672.7 244.5 2.5 643.2 266.7 2.2 613.6 288.8 1.9
204B 7.0 (44.6°F) 749.2 201.7 3.3 719.4 224.2 2.8 689.6 246.7 2.5 659.8 269.1 2.2 629.7 291.2 2.0
8.0 (46.4°F) 766.9 203.1 3.3 736.7 226.1 2.9 706.6 248.8 2.5 676.4 271.7 2.3 645.6 293.5 2.0
9.0 (48.2°F) 784.6 204.7 3.4 754.0 227.7 2.9 723.5 251.1 2.6 692.9 274.3 2.3 661.4 297.4 2.0
10.0 (50.0°F) 802.2 206.2 3.4 771.3 229.7 3.0 740.5 253.3 2.6 709.5 276.8 2.3 677.4 301.0 2.1
NOTES
1. Rated in accordance with ARI Standard 550/590.
2. Units with remote evaporators are not included in the ARI Certification Program.
3. Ratings based on HCFC-22, evaporator fouling factor of 0.0001, 10 degree delta-T, evaporator flow of 2.4 gpm/ton and sea level altitude.
4. For units with SpeedTrol option multiply capacity and COP by 0.99.
5. For units operating at 208 volt, multiply capacity by 0.98.
6. Interpolation is allowed, extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.
7. KW input is for compressors only. COP is for the entire unit, including compressors, fan motors and control power. Total power to the unit can be
calculated by: kW = kW(output) / COP.
8. Ratings are valid for operation on 3 phase, 60 Hz, and 208//230/380/460/575 volts.
9. Compressor loading and unloading is adaptively determined by system load, ambient air temperature, and other inputs to the MicroTech control
algorithms.
5.0 (41.0°F) 802.7 213.3 3.4 767.9 238.1 2.9 733.0 263.0 2.5 698.1 287.9 2.2 663.3 312.7 2.0
6.0 (42.8°F) 819.8 214.9 3.4 784.8 240.2 3.0 749.8 265.5 2.6 714.8 290.7 2.3 679.8 315.9 2.0
220B 7.0 (44.6°F) 836.9 216.4 3.5 801.7 242.2 3.0 766.5 267.9 2.6 731.4 293.5 2.3 696.3 319.2 2.0
8.0 (46.4°F) 854.1 218.0 3.5 818.7 244.2 3.0 783.3 270.2 2.7 748.0 296.3 2.3 712.7 322.5 2.1
9.0 (48.2°F) 871.1 219.6 3.6 835.6 246.2 3.1 800.1 272.6 2.7 764.5 299.1 2.4 729.1 325.4 2.1
10.0 (50.0°F) 888.2 221.2 3.6 852.5 248.1 3.1 816.8 275.0 2.7 781.2 301.9 2.4 745.4 329.0 2.1
5.0 (41.0°F) 853.1 230.4 3.3 816.1 257.3 2.9 779.0 284.2 2.5 742.0 311.0 2.2 704.9 337.8 1.9
6.0 (42.8°F) 871.2 232.2 3.4 834.1 259.5 2.9 796.9 286.8 2.5 759.6 314.0 2.2 722.5 341.3 2.0
235B 7.0 (44.6°F) 889.5 233.8 3.4 852.0 261.7 2.9 814.6 289.4 2.6 777.3 317.1 2.3 740.0 344.8 2.0
8.0 (46.4°F) 907.7 235.5 3.4 870.1 263.8 3.0 832.5 291.9 2.6 795.0 320.1 2.3 757.4 348.4 2.0
9.0 (48.2°F) 925.8 237.3 3.5 888.0 266.0 3.0 850.3 294.5 2.6 812.5 323.1 2.3 774.8 351.6 2.0
10.0 (50.0°F) 944.0 239.0 3.5 906.0 268.1 3.1 868.1 297.1 2.7 830.2 326.2 2.3 792.2 355.4 2.1
5.0 (41.0°F) 886.1 247.5 3.2 846.7 276.5 2.8 807.2 305.4 2.4 767.7 334.5 2.1 728.2 363.6 1.9
6.0 (42.8°F) 908.1 249.5 3.3 868.1 278.6 2.8 828.1 307.7 2.5 788.3 336.8 2.2 748.5 365.9 1.9
250B 7.0 (44.6°F) 930.0 251.3 3.3 889.6 280.7 2.9 849.2 310.0 2.5 808.7 339.3 2.2 768.2 368.6 1.9
8.0 (46.4°F) 952.0 253.4 3.4 911.0 282.8 2.9 870.1 312.3 2.6 829.2 341.6 2.2 788.3 370.9 2.0
9.0 (48.2°F) 973.8 255.3 3.4 932.5 284.9 3.0 891.1 314.5 2.6 849.7 344.0 2.3 808.3 373.5 2.0
10.0 (50.0°F) 995.9 257.4 3.5 954.0 287.1 3.0 912.1 316.8 2.6 870.1 346.5 2.3 828.1 376.2 2.0
5.0 (41.0°F) 921.5 267.3 3.1 880.5 298.6 2.7 839.4 329.9 2.3 798.4 361.3 2.1 757.3 392.7 1.8
6.0 (42.8°F) 944.4 269.4 3.2 902.8 300.9 2.7 861.3 332.4 2.4 819.8 363.7 2.1 778.4 395.2 1.8
265B 7.0 (44.6°F) 967.2 271.5 3.2 925.2 303.2 2.8 883.2 334.8 2.4 841.0 366.4 2.1 799.0 398.2 1.9
8.0 (46.4°F) 990.1 273.7 3.3 947.4 305.4 2.8 904.9 337.3 2.5 862.4 369.0 2.2 819.8 400.6 1.9
9.0 (48.2°F) 1012.8 275.8 3.3 969.8 307.8 2.9 926.8 339.7 2.5 883.7 371.6 2.2 840.6 403.4 1.9
10.0 (50.0°F) 1035.7 278.0 3.4 992.1 310.1 2.9 948.6 342.2 2.6 904.9 374.3 2.3 861.2 406.4 2.0
5.0 (41.0°F) 964.0 287.3 3.1 921.2 321.0 2.6 878.2 354.6 2.3 835.2 388.3 2.0 792.3 422.2 1.8
6.0 (42.8°F) 988.0 289.6 3.1 944.5 323.5 2.7 901.0 357.3 2.3 857.6 391.0 2.0 814.4 424.9 1.8
280B 7.0 (44.6°F) 1011.9 291.8 3.2 967.9 325.9 2.7 924.0 359.9 2.4 879.9 393.9 2.1 835.8 428.0 1.8
8.0 (46.4°F) 1035.7 294.2 3.2 991.1 328.3 2.8 946.7 362.6 2.4 902.2 396.7 2.1 857.6 430.7 1.9
9.0 (48.2°F) 1059.5 296.4 3.3 1014.6 330.8 2.8 969.5 365.1 2.5 924.5 399.5 2.2 879.4 433.7 1.9
10.0 (50.0°F) 1083.5 298.8 3.3 1037.9 333.3 2.9 992.4 367.8 2.5 946.7 402.4 2.2 900.9 436.9 1.9
5.0 (41.0°F) 1023.4 277.9 3.2 984.6 309.2 2.8 945.6 340.4 2.5 906.7 371.8 2.2 867.8 403.2 2.0
6.0 (42.8°F) 1053.7 280.4 3.3 1013.6 312.0 2.9 973.6 343.7 2.5 933.6 375.2 2.2 893.6 406.7 2.0
300B 7.0 (44.6°F) 1083.9 283.0 3.3 1042.8 314.9 2.9 1001.6 346.8 2.6 960.4 378.6 2.3 919.2 410.4 2.0
8.0 (46.4°F) 1114.2 285.6 3.4 1071.9 317.8 3.0 1029.5 349.9 2.6 987.2 382.2 2.3 944.9 414.5 2.1
9.0 (48.2°F) 1144.5 288.2 3.5 1101.0 320.7 3.0 1057.6 353.1 2.7 1014.1 385.6 2.4 970.5 418.1 2.1
10.0 (50.0°F) 1174.8 290.8 3.5 1130.1 323.5 3.1 1085.5 356.3 2.7 1040.8 389.0 2.4 996.1 421.7 2.2
5.0 (41.0°F) 1065.3 287.4 3.2 1024.9 319.9 2.8 984.3 352.2 2.5 943.8 384.7 2.2 903.4 417.1 2.0
6.0 (42.8°F) 1096.9 290.1 3.3 1055.1 322.8 2.9 1013.5 355.5 2.6 971.8 388.2 2.3 930.2 420.7 2.0
315B 7.0 (44.6°F) 1128.3 292.8 3.4 1085.5 325.8 3.0 1042.6 358.7 2.6 999.7 391.7 2.3 956.9 424.5 2.1
8.0 (46.4°F) 1159.8 295.5 3.4 1115.8 328.7 3.0 1071.7 362.0 2.7 1027.6 395.4 2.4 983.6 428.8 2.1
9.0 (48.2°F) 1191.3 298.2 3.5 1146.0 331.8 3.1 1100.9 365.2 2.7 1055.6 398.9 2.4 1010.3 432.5 2.1
10.0 (50.0°F) 1222.9 300.8 3.6 1176.4 334.6 3.1 1129.9 368.6 2.8 1083.5 402.4 2.4 1036.9 436.3 2.2
5.0 (41.0°F) 1114.2 305.7 3.2 1071.9 340.2 2.8 1029.5 374.6 2.5 987.1 409.1 2.2 944.8 443.6 2.0
6.0 (42.8°F) 1147.2 308.6 3.3 1103.5 343.3 2.9 1060.0 378.1 2.5 1016.4 412.8 2.2 972.9 447.5 2.0
330B 7.0 (44.6°F) 1180.1 311.4 3.4 1135.3 346.5 2.9 1090.5 381.5 2.6 1045.6 416.6 2.3 1000.8 451.5 2.0
8.0 (46.4°F) 1213.1 314.3 3.4 1167.0 349.6 3.0 1120.9 385.0 2.6 1074.8 420.5 2.3 1028.7 456.0 2.1
9.0 (48.2°F) 1246.0 317.1 3.5 1198.7 352.8 3.0 1151.4 388.5 2.7 1104.0 424.2 2.4 1056.7 460.0 2.1
10.0 (50.0°F) 1279.0 319.9 3.5 1230.4 355.9 3.1 1181.8 392.0 2.7 1133.2 428.0 2.4 1084.5 464.0 2.1
NOTES
1. Rated in accordance with ARI Standard 550/590.
2. Units with remote evaporators are not included in the ARI Certification Program.
3. Ratings based on HCFC-22, evaporator fouling factor of 0.0001, 10 degree delta-T, evaporator flow of 2.4 gpm/ton and sea level altitude.
4. For units with SpeedTrol option multiply capacity and COP by 0.99.
5. For units operating at 208 volt, multiply capacity by 0.98.
6. Interpolation is allowed, extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.
7. KW input is for compressors only. COP is for the entire unit, including compressors, fan motors and control power. Total power to the unit can be
calculated by: kW = kW(output) / COP.
8. Ratings are valid for operation on 3 phase, 60 Hz, and 208//230/380/460/575 volts.
9. Compressor loading and unloading is adaptively determined by system load, ambient air temperature, and other inputs to the MicroTech control
algorithms.
5.0 (41.0°F) 1145.7 322.6 3.2 1102.2 359.0 2.8 1058.5 395.3 2.4 1015.0 431.7 2.1 971.5 468.1 1.9
6.0 (42.8°F) 1179.6 325.6 3.2 1134.7 362.3 2.8 1089.9 399.0 2.5 1045.1 435.6 2.2 1000.3 472.2 2.0
340B 7.0 (44.6°F) 1213.4 328.6 3.3 1167.3 365.6 2.9 1121.3 402.6 2.5 1075.1 439.6 2.2 1029.0 476.5 2.0
8.0 (46.4°F) 1247.3 331.6 3.3 1200.0 368.9 2.9 1152.5 406.3 2.6 1105.1 443.7 2.3 1057.8 481.2 2.0
9.0 (48.2°F) 1281.2 334.6 3.4 1232.5 372.3 3.0 1183.9 409.9 2.6 1135.2 447.7 2.3 1086.5 485.4 2.1
10.0 (50.0°F) 1315.1 337.6 3.5 1265.1 375.6 3.0 1215.1 413.7 2.7 1165.2 451.6 2.4 1115.1 489.6 2.1
5.0 (41.0°F) 1222.5 320.8 3.3 1176.1 357.1 2.9 1129.5 393.1 2.6 1083.1 429.3 2.3 1036.6 465.6 2.0
6.0 (42.8°F) 1258.7 323.8 3.4 1210.8 360.3 3.0 1163.0 396.8 2.6 1115.2 433.2 2.3 1067.4 469.6 2.1
360B 7.0 (44.6°F) 1294.8 326.8 3.4 1245.6 363.6 3.0 1196.5 400.4 2.7 1147.2 437.2 2.4 1098.1 473.8 2.1
8.0 (46.4°F) 1330.9 329.8 3.5 1280.4 366.9 3.1 1229.8 404.0 2.7 1179.2 441.3 2.4 1128.7 478.6 2.1
9.0 (48.2°F) 1367.1 332.8 3.6 1315.1 370.3 3.1 1263.3 407.7 2.8 1211.3 445.2 2.5 1159.4 482.7 2.2
10.0 (50.0°F) 1403.3 335.7 3.6 1350.0 373.5 3.2 1296.6 411.4 2.8 1243.3 449.1 2.5 1189.9 486.9 2.2
5.0 (41.0°F) 1257.5 338.7 3.2 1209.7 377.0 2.8 1161.8 415.0 2.5 1114.0 453.3 2.2 1066.3 491.5 2.0
6.0 (42.8°F) 1294.7 341.9 3.3 1245.4 380.4 2.9 1196.2 418.9 2.6 1147.1 457.4 2.3 1097.9 495.8 2.0
370B 7.0 (44.6°F) 1331.7 345.0 3.4 1281.2 383.9 3.0 1230.7 422.7 2.6 1180.0 461.5 2.3 1129.4 500.3 2.1
8.0 (46.4°F) 1369.0 348.2 3.4 1317.0 387.4 3.0 1265.0 426.6 2.7 1212.9 465.9 2.4 1161.0 505.2 2.1
9.0 (48.2°F) 1406.2 351.3 3.5 1352.7 390.9 3.1 1299.4 430.4 2.7 1245.9 470.0 2.4 1192.5 509.6 2.1
10.0 (50.0°F) 1443.4 354.4 3.6 1388.5 394.3 3.1 1333.7 434.3 2.8 1278.8 474.2 2.4 1223.9 514.1 2.2
5.0 (41.0°F) 1299.4 355.4 3.2 1250.0 395.6 2.8 1200.5 435.5 2.5 1151.2 475.6 2.2 1101.8 515.8 2.0
6.0 (42.8°F) 1337.8 358.7 3.3 1286.9 399.2 2.9 1236.1 439.6 2.5 1185.3 480.0 2.2 1134.5 520.2 2.0
380B 7.0 (44.6°F) 1376.1 362.0 3.3 1323.9 402.8 2.9 1271.7 443.6 2.6 1219.3 484.3 2.3 1167.1 525.0 2.0
8.0 (46.4°F) 1414.6 365.4 3.4 1360.9 406.5 3.0 1307.1 447.6 2.6 1253.3 488.9 2.3 1199.7 530.2 2.1
9.0 (48.2°F) 1453.0 368.7 3.5 1397.8 410.2 3.0 1342.7 451.6 2.7 1287.5 493.2 2.4 1232.2 534.8 2.1
10.0 (50.0°F) 1491.5 371.9 3.5 1434.8 413.8 3.1 1378.1 455.8 2.7 1321.5 497.6 2.4 1264.7 539.4 2.1
5.0 (41.0°F) 1400.7 363.3 3.3 1347.5 404.3 2.9 1294.1 445.1 2.6 1240.9 486.1 2.3 1187.7 527.1 2.0
6.0 (42.8°F) 1442.1 366.6 3.4 1387.2 408.0 3.0 1332.5 449.3 2.6 1277.7 490.5 2.3 1223.0 531.7 2.1
425B 7.0 (44.6°F) 1483.4 370.0 3.4 1427.1 411.7 3.0 1370.8 453.3 2.7 1314.4 495.0 2.4 1258.1 536.5 2.1
8.0 (46.4°F) 1524.9 373.4 3.5 1467.0 415.4 3.1 1409.0 457.5 2.7 1351.0 499.6 2.4 1293.2 541.8 2.1
9.0 (48.2°F) 1566.3 376.8 3.6 1506.8 419.2 3.1 1447.4 461.6 2.8 1387.8 504.1 2.5 1328.3 546.6 2.2
10.0 (50.0°F) 1607.8 380.1 3.6 1546.7 422.9 3.2 1485.6 465.8 2.8 1424.5 508.5 2.5 1363.2 551.3 2.2
NOTES:
1. Rated in accordance with ARI Standard 550/590.
2. Units with remote evaporators are not included in the ARI Certification Program.
3. Ratings based on HCFC-22, evaporator fouling factor of 0.0001, 10 degree delta-T, evaporator flow of 2.4 gpm/ton and sea level altitude.
4. For units with SpeedTrol option multiply capacity and COP by 0.99.
5. For units operating at 208 volt, multiply capacity by 0.98.
6. Interpolation is allowed, extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.
7. KW input is for compressors only. COP is for the entire unit, including compressors, fan motors and control power. Total power to the unit can be
calculated by: kW = kW(output) / COP.
8. Ratings are valid for operation on 3 phase, 60 Hz, and 208//230/380/460/575 volts.
9. Compressor loading and unloading is adaptively determined by system load, ambient air temperature, and other inputs to the MicroTech control
algorithms.
ALS Unit Minimum Pressure Maximum Pressure ALS Unit Minimum Pressure Maximum Pressure
Size Flow gpm Drop ft. Flow gpm Drop ft. Size Flow gpm Drop ft. Flow Drop ft.
gpm
125 177 7.0 472 43.2 265 374 3.7 998 33.6
140 199 5.5 530 37.2 280 392 4.1 1044 37.2
155 222 6.8 591 46.1 300 422 3.4 1125 31.0
170 242 8.1 645 54.6 315 439 3.8 1171 33.9
175 246 8.4 657 56.5 330 459 4.2 1225 37.4
185 262 9.4 699 63.8 340 472 4.4 1260 39.8
195 271 6.8 722 45.5 360 504 5.1 1344 46.1
204 291 4.5 776 33.1 370 518 5.5 1382 49.1
220 321 5.3 856 39.2 380 536 5.9 1428 52.8
235 341 6.0 910 44.4 425 577 7.8 1540 67.8
Standards
ARI has established standards to provide uniform methods for the determination of the sound
levels of equipment. For large air-cooled chillers it is ARI Standard 370, Sound Ratings of
Large Outdoor Refrigeration and Air-Conditioning Equipment.
Background Information
Sound is a vibration in an elastic medium and is essentially a pressure and particle
displacement phenomena. A vibrating body produces compression waves and as the waves
are emitted from the vibrating body, molecules are ultimately compressed. These values are
transmitted through gas, liquid, solids-anything which is elastic or viscous.
The sound data provided in this section is presented with both sound pressure and sound
power levels. Sound power is the total sound energy radiated by a source per unit of time
integrated over the surface through which the sound is radiated. Sound power is a
calculated quantity and cannot be measured directly like sound pressure. Sound power is not
dependent on the surrounding environment or distance from the source.
Sound pressure varies with the distance from the source and is dependent on its
surroundings. For example, a brick wall located 10 feet from a unit will affect the sound
pressure measurements differently than a brick wall at 20 feet. Sound pressure is measured
in decibels (dB), which is a dimensionless ratio (on a logarithmic scale) between measured
sound pressure and a reference sound pressure level.
NOTE: Table based on 75°C field wire except (*) which require 90°C field wire.
NOTE: Table based on 75°C field wire except (*) which require 90°C field wire.
208 329 3 400 1 3.0 400 500 329 3 400 1 3.0 400 500
230 301 3 350 1 2.5 400 500 301 3 350 1 2.5 400 500
125B 380 60 182 3 #3/0 1 2.0 225 300 182 3 #3/0 1 2.0 225 300
460 150 3 #1/0 1 1.5 200 250 150 3 #1/0 1 1.5 200 250
575 122 3 #1 1 1.5 150 200 122 3 #1 1 1.5 150 200
208 329 3 400 1 3.0 400 500 404 6 #4/0 2 2.0 500 700
230 301 3 350 1 2.5 400 500 369 3 500 1 3.0 500 600
140B 380 60 182 3 #3/0 1 2.0 225 300 223 3 #4/0 1 2.0 300 350
460 150 3 #1/0 1 1.5 200 250 184 3 #3/0 1 2.0 250 300
575 122 3 #1 1 1.5 150 200 148 3 #1/0 1 1.5 200 250
208 410 6 #4/0 2 2.0 500 700 410 6 #4/0 2 2.0 500 700
230 375 3 500 1 3.0 500 600 375 3 500 1 3.0 500 600
155B 380 60 226 3 #4/0 1 2.0 300 350 226 3 #4/0 1 2.0 300 350
460 187 3 #3/0 1 2.0 250 300 187 3 #3/0 1 2.0 250 300
575 150 3 #1/0 1 1.5 200 250 150 3 #1/0 1 1.5 200 250
208 410 6 #4/0 2 2.0 500 700 464 6 250 2 2.5 600 800
230 375 3 500 1 3.0 500 600 423 6 #4/0 2 2.0 500 700
170B 380 60 226 3 #4/0 1 2.0 300 350 255 3 300 1 2.5 350 400
460 187 3 #3/0 1 2.0 250 300 211 3 #4/0 1 2.0 250 350
575 150 3 #1/0 1 1.5 200 250 169 3 #2/0 1 1.5 225 250
208 416 6 #4/0 2 2.0 500 700 470 6 250 2 2.5 600 800
230 381 6 #3/0 2 2.0 500 600 429 6 #4/0 2 2.0 500 700
175B 380 60 230 3 #4/0 1 2.0 300 350 259 3 300 1 2.5 350 400
460 190 3 #3/0 1 2.0 250 300 214 3 #4/0 1 2.0 250 350
575 152 3 #2/0 1 1.5 200 250 171 3 #2/0 1 1.5 225 250
208 470 6 250 2 2.5 600 800 470 6 250 2 2.5 600 800
230 429 6 #4/0 2 2.0 500 700 429 6 #4/0 2 2.0 500 700
185B 380 60 259 3 300 1 2.5 350 400 259 3 300 1 2.5 350 400
460 214 3 #4/0 1 2.0 250 350 214 3 #4/0 1 2.0 250 350
575 171 3 #2/0 1 1.5 225 250 171 3 #2/0 1 1.5 225 250
208 470 6 250 2 2.5 600 800 470 6 250 2 2.5 600 800
230 429 6 #4/0 2 2.0 500 700 429 6 #4/0 2 2.0 500 700
195B 380 60 259 3 300 1 2.5 350 400 259 3 300 1 2.5 350 400
460 214 3 #4/0 1 2.0 250 350 214 3 #4/0 1 2.0 250 350
575 171 3 #2/0 1 1.5 225 250 171 3 #2/0 1 1.5 225 250
208 484 6 250 2 2.5 700 800 484 6 250 2 2.5 700 800
230 439 6 #4/0 2 2.0 600 700 439 6 #4/0 2 2.0 600 700
204B 380 60 284 3 300 1 2.5 400 450 264 3 300 1 2.5 400 450
460 219 3 #4/0 1 2.0 300 350 219 3 #4/0 1 2.0 300 350
575 176 3 #3/0 1 2.0 250 300 176 3 #3/0 1 2.0 250 300
208 329 3 400 1 2.5 400 500 410 6 300 1 3 600 700
230 302 3 350 1 2.5 400 500 375 6 250 1 3 500 600
220B 380 60 182 3 #3/0 1 1.5 250 300 223 3 #4/0 1 2 300 350
460 150 3 #1/0 1 1.25 200 250 187 3 #3/0 1 1.5 250 300
575 122 3 #1/0 1 1.25 175 200 150 3 #1/0 1 1.25 200 250
208 416 6 300 1 3 600 700 464 6 350 1 3.5 700 800
230 375 6 250 1 3 500 600 423 6 300 1 3 600 700
265B 380 60 2270 3 #4/0 1 2 300 350 259 3 250 1 2 350 400
460 187 3 #3/0 1 1.5 250 300 211 3 #4/0 1 2 300 350
575 150 3 #1/0 1 1.25 200 250 170 3 #2/0 1 1.5 250 250
208 464 6 350 1 3.5 700 800 464 6 350 1 3.5 700 800
230 423 6 300 1 3 600 700 423 6 300 1 3 600 700
280B 380 60 256 3 250 1 2 350 400 256 3 250 1 2 350 400
460 211 3 #4/0 1 2 300 350 211 3 #4/0 1 2 300 350
575 170 3 #2/0 1 1.5 250 250 170 3 #2/0 1 1.5 250 250
230 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
380 60 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
220B
460 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
575 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
208 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
230 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
380 60 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
235B
460 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
575 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
208 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
230 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
380 60 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
250B
460 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
575 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
208 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
230 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
380 60 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
265B
460 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
575 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
208 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
230 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
380 60 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
280B
460 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
575 840 840 840 (2) #2 to 600 MCM (2) #2 to 600 MCM (2) #2 to 600 MCM
Rigging
Care should be taken to avoid dropping the unit during unloading or moving as this may result
in serious damage. Do not push or pull the unit from anything other than the base, and block
the fork lift away from the unit to prevent damage to the sheet metal cabinet and end frame.
Do not lift the unit with a fork lift truck. To lift the unit, two 2 1/2 inch (65mm) diameter
lifting holes are provided in the base of the unit. Spreader bars must be used between
rigging lines to prevent damage to the condenser coils or unit cabinet.
Unit Placement
For roof mounted applications, the unit should be installed on a steel channel or I-beam frame
to support the unit above the roof. For ground level applications, the unit should be installed
on a substantial base that will not settle. A one piece concrete slab with footings extended
below the frost line is recommended. The foundation must be level within 1/2 inch (13mm)
over its length and width and strong enough to support the unit's operating weight as listed in
the Physical Data tables.
On ground level applications fin protection against vandalism is recommended, either by the
optional factory installed condenser coil guard or a field installed screen fence. Note that the
fence must allow free flow of air to the condenser coil for proper unit operation.
Clearances
Since these units are air cooled, the flow of air to and from the condenser coil must not be
impeded. Restricting unit airflow and air recirculation will result in a decrease in unit
performance and efficiency due to an increase in operating discharge pressures. Although
the MicroTech chiller control system will cycle fans or may unload compressors to maintain
the optimum system head, adequate clearances must be obtained. Warm air recirculation
and condenser coil air starvation can be prevented with proper design.
There must be no obstruction above the unit that would tend to deflect discharge air
downward where it could be recirculated back to the inlet of the condenser coil. The
condenser fans are propeller type and ductwork should not be applied to the fan outlet.
Further information on air restriction can be found in Application Manual AM ALSWHS.
For lateral clearance considerations, the unit must be installed with sufficient clearance for
air entrance to the coil and for servicing. Service access to the evaporator, compressors,
electrical control panel and piping components must be provided as per the limitations in
Figure 11 through Figure 13. Do not block access to sides or ends of unit with piping or
conduit.
Debris should not be allowed to accumulate in the vicinity of the unit. Air movement may
draw debris into the condenser coil causing coil starvation. Special consideration should be
given to units installed in cold climates where snow accumulation is common. Condenser
coils and fan discharge must be kept free of snow or other obstructions to permit adequate
airflow for proper unit operation. Units mounted next to a building with a sloping roof must
be protected from falling ice and snow.
Sound isolation
The ultra-low sound level for the ALS screw chiller satisfies most customer requirements.
However, there may be applications where extremely low sound levels may be required.
The most effective isolation method is to locate the unit away from sound sensitive areas.
Avoid locations beneath windows or between structures where normal operating sounds may
be objectionable. Isolating water lines, electrical conduit and the unit itself can reduce
structurally transmitted sound. Wall sleeves and rubber isolated piping hangers can be used
to reduce transmission of water or pump noise into occupied spaces, and flexible electrical
conduit can be used to isolate sound through electrical conduit. Spring isolators are effective
in reducing the low amplitude sound generated by screw compressors and can be used for
unit isolation in sound sensitive areas.
Notes:
1. Minimum side clearance between two units is 12 feet (3.7 meters).
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of
the unit unless extra clearance is provided per note 4.
3. Minimum clearance on each side is 8 feet (2.4 meters) when installed in a pit no deeper
than the unit height.
4. Minimum side clearance to a side wall or building taller than the unit height is 8 feet (2.4
meters) provided no solid wall above 6 feet (1.8 meters) is closer than 12 feet (3.7
meters) to the opposite side of the unit.
5. The removable post for compressor service access must not be blocked at either side of
the unit.
6. Do not mount electrical conduits, etc, above the side rail on either side of the unit.
7. There must be no obstruction of the fan discharge.
Electrical Connections
All wiring must be done in accordance with applicable local and national codes.
ALS units may be ordered with internal power wiring for either single or multiple point
power connections. If single point power connection is ordered, a single power terminal
block is provided and wiring within the unit is sized in accordance with the U.S.A. National
Electrical Code. A single field supplied disconnect is required. If multiple point power wiring
is ordered, two power connections are required for ALS 125B - ALS 204B and ALS 300B -
ALS 425B. Three power connections are required for ALS 220B - ALS 280B. Wiring
within the unit is sized in accordance with the U.S.A. National Electrical Code. Separate
field supplied disconnects are required for each circuit.
Remote Evaporator
General
The multiple compressor ALS air-cooled chillers are available with remote evaporator. This
allows the main unit to be installed outdoors to save interior room and eliminates the need for
anti-freeze solutions and heat tracing of chilled water lines since the chilled water system is
indoors. There are some general guidelines to review before proceeding:
1. R-22 only.
2. Maximum line length of 50 ft (15 m) and Total Equivalent Length (TEL) of 120 ft
(37 m).
3. Evaporator not more than 6 ft (1.8 m) above the compressor or 16 ft (5 m) below
compressor.
4. No underground piping.
5. No hot gas bypass.
6. Units with remote evaporator are not included in the ARI Certification Program.
The remote evaporator is shipped separately, ready for quick and easy installation at the job
site. All refrigerant accessories such as liquid-vapor line shut-off valves, replaceable core
filter-driers, liquid line solenoid valves, electronic expansion valves, and sightglasses are
already included on the ALS condensing unit. The evaporator is equipped with entering and
leaving chilled water temperature sensor wells. The sensors are pre-wired to the ALS unit
with 75 feet long sensor leads that must be field connected to the evaporator thermowells.
Suction pressure transducers and temperature sensors must also be relocated to the
evaporator. ALS units are shipped with a holding charge of refrigerant. Field piping must be
leak tested, evacuated and the entire unit charged during installation. Do not exceed 150
psig test pressure unless the unit is blanked off from the piping.
Suction Lines
General
Careful design of the refrigerant piping is necessary for efficient system operation. The
refrigerant piping should be designed for a low pressure drop to obtain maximum capacity
and efficiency while maintaining adequate velocity. Lines should slope in the direction of
flow to assure good oil return to the compressors. Cost considerations favor keeping line
sizes as small as possible while not exceeding acceptable pressure drops in order to maintain
unit performance.
NOTE
All refrigerant piping must be reviewed by McQuay Application Engineers
prior to order entry and will be verified by McQuay startup technicians.
Liquid-Vapor Lines
The liquid-vapor line from the ALS condensing unit to the evaporator liquid connection is not
a conventional liquid line since it carries both liquid and vapor. The compressors on the ALS
units utilize a liquid cooled motor and an economizer. Therefore the expansion valve which
feeds the full flow of liquid refrigerant into the compressor for motor cooling is mounted in
the liquid line between the condenser sub-cooling coil and the compressor inlet; not at the
evaporator inlet. The liquid-vapor line to the evaporator is a low pressure line downstream
of the expansion valve and the size is slightly larger than a normal liquid line. For liquid line
sizing see Table 36 and Table 37.
Insulation
All piping joints and fittings must be thoroughly leak tested before insulation is applied.
Suction lines must be insulated and should not be installed underground. Suction line
insulation must be selected to prevent condensation under local ambient conditions with the
lines at 40°F to 50°F (4.4°C to 10°C) operating temperatures. The liquid-vapor lines will
operate at 40°F to 60°F (4.4°C to 15.6°C) and must also be insulated to prevent sweating
and heat gain.
NOTE: Keep the trap width at a minimum to avoid trapping excessive oil.
Startup Procedures
NOTE: McQuayService or an authorized McQuay service agent must do initial start-up and
commissioning.
Filter Driers
Following an initial 24 hour operation the pressure drop across the replaceable core, filter
drier should be checked. If this pressure drop exceeds the values given in Table 39 at the
various load conditions the filter drier cores must be replaced. Also if the moisture indicating
sight glass shows a wet system condition after 24 hours of operation the filter cores must be
changed. This should remove any contaminants introduced during field piping. The filter
drier cores must also be changed anytime the system is opened for servicing.
Dimensions
Use the ALS dimension drawings Figure 7 to Figure 10 for the ALS with remote evaporator.
The refrigerant connections are located approximately where the refrigerant connections to
ALS Evaporator Water Volume Refrig Volume Weights lb. (kg) R-22 Operating Charge lb. (kg)
Model Model gal. (l) lb. (kg) Operating Shipping Circuit 1 Circuit 2
125 1207-C 30 (113) 170 (77) 1534 (697) 1342 (608) 4.04 (1.8) 4.04 (1.8)
140-185 1407-A 31 (119) 222 (100) 1743 (792) 1536 (696) 5.27 (2.4) 5.27 (2.4)
ALS Evaporator Water Volume Refrig Volume Weights lb. (kg) R-22 Operating Charge lb. (kg)
Model Model gal. (l) lb. (kg) Operating Shipping Circuit 1 Circuit 2
195 1608-2 55 (208) 175 (79) 1404 (638) 959 (436) 26 (12) 26 (12)
204 2008-2 98 (373) 210 (95) 1956 (889) 1137 (517) 32 (14) 32 (14)
ALS Evaporator Water Volume Refrig Volume Weights lb. (kg) R-22 Operating Charge lb. (kg)
Model Model gal. (l) lb. (kg) Operating Shipping Circuit 1 Circuit 2 Circuit 3
220-235 2008-2 98 (371) 215 (97) 1961 (888) 1146 (519) 22 (10) 22 (10) 22 (10)
250-280 2008-3 94 (357) 243 (110) 1984 (899) 1190 (539) 24 (11) 24 (11) 24 (11)
ALS Evaporator Water Vol. Refrig Vol. Weights lb. (kg) R-22 Operating Charge lb. (kg)
Model Model gal. (l) lb. (kg) Operating Shipping Circuit 1 Circuit 2 Circuit 3 Circuit 4
300-380 2208-1 115 (435) 306 (139) 2424 (1102) 1439 (654) 23 (10) 23 (10) 23 (10) 23 (10)
425 2208-2 110 (416) 345 (156) 2457 (1117) 1500 (682) 26 (12) 26 (12) 26 (12) 26 (12)
Rigging
Designed for easy handling and low installation costs, the ALS air-cooled screw chillers are
assembled on a rugged galvanized steel channel base. The channel base distributes the unit
weight for uniform low roof loading. Lifting holes are provided in the base of the unit to
simplify installation.
Cabinet Construction
The unit casing and all structural members and rails are fabricated of continuous G90
galvanized steel and galvanized steel channel. The galvanized coating is applied to the base
metal by the hot dip process and conforms to standard ASTM A525. The exterior casing is
phosphatized and painted with a beige urethane finish.
Compressors
All units feature multiple compressors with independent refrigerant circuits. The compressor
is a direct drive, 3600 rpm, single-screw type with one main screw rotor that meshes with
two diametrically opposed gaterotors. The two exactly opposed gaterotors create two
exactly opposed compression cycles resulting in a well balanced compression cycle.
The compressor utilizes an internal economizer to enhance the unit's refrigeration effect and
to allow the compressor to run at a more efficient operating point. During the economizer
cycle vapor produced at the electronic expansion valve and motor cooling process is
redirected to the rotor inlet, while the remaining liquid refrigerant flows to the evaporator.
Unlike twin-screw designs, the ALS single-screw compressor uses liquid refrigerant instead
of oil to seal the rotors. The oil management concerns associated with oil injection systems
are a thing of the past.
The electric motor is semi-hermetic, squirrel cage induction type and cooled by liquid
refrigerant. This allows the motor to operate at lower temperatures enhancing system
reliability and motor life when compared to suction gas cooled motors found on reciprocating
and twin-screw compressors.
Each compressor is equipped with suction and discharge shutoff valves to facilitate service
work.
Evaporator
The evaporator is a direct expansion, shell-and-tube type with water flowing in the baffled
shell and refrigerant flowing through the tubes. Independent refrigerant circuits within the
evaporator serve each compressor.
Condenser Coils
The condenser coils are constructed with internally enhanced seamless copper tubes
arranged in a staggered row pattern and mechanically expanded into McQuay lanced and
rippled aluminum fins with full fin collars. The fins have full drawn collars to completely
cover the copper tube for protection against atmospheric corrosion and provide excellent
heat transfer. An integral subcooler with a liquid sightglass on the inlet provides sufficient
subcooling to effectively eliminate the possibility of liquid flashing and increase unit
efficiency.
Control Center
The ALS screw chiller is shipped with all operating and safety controls and motor starting
equipment factory wired, operationally tested, and ready for service. All controls are
centrally located in a NEMA type 3R weatherproof, hinged control center, with key locked
doors to prevent unauthorized entry. Panel access doors include steel rod door retainers to
prevent flapping while open. Dead front panels protect service personnel from accidental
contact with line voltage components.
Disconnect switch
A factory installed nonfused disconnect switch is available on all units. The disconnect
switch is properly sized for model and voltage required.
Phone modem
An optional 9600 baud modem interface is available which allows the operator to control (or
monitor) all chiller operations from a remote location through standard phone lines.
Ice storage
The unit can be equipped with control logic to handle the low temperatures associated with
thermal storage applications. In addition to the change within the controller, the unit is
supplied with additional evaporator insulation to prevent any loss of efficiency through
condensation.
Hail guards
Hail can have a damaging effect on the performance of an air-cooled condenser. As the
finned area is flattened against the coil, restricting airflow, the efficiency of the coil is
reduced. Hail guards are available for field installation to completely cover the coil finned
area. The hail guards will also protect the coil from wind.
Vibration isolators
Spring vibration isolators are available for field installation under the unit base frame on
sound sensitive applications.
1.01 SUMMARY
PART 2--PRODUCTS
A. McQuay International
B. (Approved Equal)
2.02 UNIT DESCRIPTION
Provide and install as shown on the plans factory assembled, factory charged, and
factory run tested air-cooled rotary screw compressor packaged chillers in the
quantity specified. Each chiller shall consist of multiple semi-hermetic rotary screw
compressors, direct expansion evaporator, air-cooled condenser section, control
system and all components necessary for safe and controlled unit operation.
2.03 DESIGN REQUIREMENTS
3.01 INSTALLATION
3.02 START-UP