Getting Started With The Firmware Upgrade Wizard
Getting Started With The Firmware Upgrade Wizard
Requirements
The firmware upgrade wizard for the PanelView Plus and VersaView CE requires
the following software to be properly installed on the computer performing the
firmware upgrade:
? RSView Studio v3.10
? RSLinx Enterprise
? Firmware Upgrade Wizard from Firmware Upgrade Media Kit.
1. Copy the files on the CD to the same drive that RSView Studio is installed on,
such as C:\FUW.
2. Locate the file “Install.bat”, which was copied to the same drive as RSView
Studio (such as C:\FUW), and double click on it.
3. A command prompt window and self extracting ZIP utility will appear. Select
the root directory of the drive that RSView Studio is installed on (such as C:\).
Press “Unzip” to unzip the files.
Important: The files must be unzipped in the root directory (such as C:\) of
the drive that RSView Studio was installed in order for the
Firmware Upgrade Wizard to install properly.
4. The files will unzip into the appropriate directories. When finished, select
“OK” and press “Close”
5. The command prompt window will register the appropriate files and close
automatically.
Running the Firmware Upgrade Wizard
To start the firmware upgrade wizard, Select Start->Rockwell Software->RSView
Enterprise->Tools->Firmware Upgrade Wizard.
1. Select “Create firmware upgrade card”. Next, select the destination for the
compact flash files. This could be in a directory on the hard drive or the physical
location of the compact flash card (such as Drive E:\). Finally, select the existing
terminal type, and select “Next”.
4. Select “Finish” to create the files in the location selected in step #1.
5. If the files were created in a separate directory on a local hard drive, copy the
files to the root directory of the compact flash card.
6. Insert the compact flash card into the external slot of the terminal’s Logic
Module. A dialog box will appear indicating that a firmware upgrade is about to
occur. One can either select OK, or Exit.
7. Press “OK” to begin the firmware upgrade process. DO NOT PULL THE
COMPACT FLASH CARD until instructed to do so.
9. On touch or combo terminals, you will need to recalibrate the touch screen by
selecting the pointers in all four corners of the touch screen, and press the
middle of the screen when prompted.
10. If the error message “Machine edition may be corrupted. Do you want to
download firmware?” with two buttons appears, please disregard this message;
for RSView ME is currently being installed.
11. After the terminal has been upgraded, a dialog box will appear requesting
the removal the compact flash card. Remove the Compact Flash card, and press
F8 or “Exit”. The terminal will reboot.
13. Replace the MER files copied from preparing the terminal or download the
new MER files to the terminal..
15. For VersaView CE, load any other files or viewers from the VersaView CE
Accessories CD.
Upgrading via Ethernet Communications
To upgrade a PanelView Plus or VersaView CE terminal using Ethernet
Communications, follow the steps below:
2. Select “Network connection”, and select “Next”. The Ethernet and Serial
connections are to be used only when the firmware upgrade is not successful.
3. Locate the PanelView Plus / VersaView CE on your Ethernet network via it’s
IP address. Skip to step 5 if you found your terminal. Otherwise if you do not
see your terminal you can right click on the Ethernet driver, and add the device to
the browse tree.
8. Select “Finish” to begin download the files for the firmware upgrade.
9. Press “Yes” if you wish to continue the upgrade process. There should be no
applications running on the terminal if the terminal was properly prepared for the
firmware upgrade.
10. The files start downloading to the terminal. This will take a few minutes
(updwards of 10 to 15 minutes). When the download is complete, select “OK” to
restart the terminal
11. Note – if other PanelView Plus / VersaView CE Terminals exist on the same
Ethernet network, an error message may show up when upgrading stating,
“Error registering name on network (may be duplicate). Change in system
Control Panel and try again.”
Ignore this message, for this error will be corrected automatically during the
upgrade process. Press “OK” or press the Enter key on the keypad to
acknowledge the error and patiently wait until the terminal resets itself.
13. On touch or combo terminals recalibrate the touch screen by selecting the
pointers in all four corners of the touch screen, and press the middle of the
screen when prompted.
14. If the error message “Machine edition may be corrupted. Do you want to
download firmware?” with two buttons appears, please disregard this message;
for RSView ME is currently being installed.
16. Replace the MER files copied from preparing the terminal or download the
new MER files to the terminal.
18. For VersaView CE, load any other files or viewers from the VersaView CE
Accessories CD.