* Air flow rate = 160 m3/min = 2.67 kg/s * Air inlet and outlet temperatures: T1 = 15°C, T2 = 45°C * Steam inlet temperature: Ts,i = 225°C * Tube length = 1.5 m * Tube outside diameter = 3 cm * Triangular pitch = 2 * 3 cm = 6 cm * Casing width = 39 cm * Bank dimensions: 6 rows wide, 4 rows deep * Calculate heat transfer rate, tube surface area per bank, number of banks needed Banks needed = Q / (U * A) = 2.67 So 3 banks of tubes are needed.

Uploaded by

Vanjared Ocampo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views

CHE408-Lecture 1 PDF

* Air flow rate = 160 m3/min = 2.67 kg/s * Air inlet and outlet temperatures: T1 = 15°C, T2 = 45°C * Steam inlet temperature: Ts,i = 225°C * Tube length = 1.5 m * Tube outside diameter = 3 cm * Triangular pitch = 2 * 3 cm = 6 cm * Casing width = 39 cm * Bank dimensions: 6 rows wide, 4 rows deep * Calculate heat transfer rate, tube surface area per bank, number of banks needed Banks needed = Q / (U * A) = 2.67 So 3 banks of tubes are needed.

Uploaded by

Vanjared Ocampo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

CHE 408:

HEAT AND MASS TRANSFER

LECTURE 1:
HEAT EXCHANGERS

Lecturer:
Engr. Michael Allan G. Ramos
Chemical Engineering Department
Technological Institute of the Philippines
Summer 2019
Heat Exchanger Applications

Methanol Synthesis from Syngas (source: www.chemsep.org)


Heat Exchanger Applications

An engineer should be able to:

• Define the heat exchanger duty


• Collect necessary fluid properties: physical & chemical
• Decide on type of heat exchanger
• Select the specific configuration of heat exchanger
• Estimate the size of the heat exchanger
• Optimise the over-all design of heat exchanger

PERFORMANCE/EFFECTIVENESS
vs.
ECONOMICS
TYPES OF HEAT EXCHANGER EQUIPMENT
TUBULAR HEAT EXCHANGER: Double-Pipe Heat Exchanger

• Simplest type
• Easy to install and clean
• Can be used at severe fouling
condition
• Can achieve pure concurrent
or countercurrent flow
• Good for high pressure flows

• Bulky and expensive

(source: gireeshheatexchangers.com) (source: sunriseequipments.com)


TYPES OF HEAT EXCHANGER EQUIPMENT
TUBULAR HEAT EXCHANGER: Shell-and-Tube Heat Exchanger

• Larger surface area in a small volume


• Well-established fabrication techniques
• High efficiency
• High operating pressure flows

• Double-space needed for cleaning (source: gireeshheatexchangers.com)

• Difficult to clean shell side

(source: brighthubengineering.com)
TYPES OF HEAT EXCHANGER EQUIPMENT
PLATE HEAT EXCHANGER: Plate-and-Frame Heat Exchanger

• Highest heat transfer coefficients


• Low pressure drop
• Easier to clean than STHE
• Small size
• Expandable capacity
• Closer approach temperature

• Low operating pressure flows


• More prone to fouling

(source: researchgate.net)
TYPES OF HEAT EXCHANGER EQUIPMENT
DIRECT-CONTACT HEAT EXCHANGER: Vertical Quench Tower

• Large flow rates


• Low pressure drop
• High efficiency
• Less fouling

• Large size
• Requires make-up water
• Limited application

(source: monroeenvironmental.com)
RECALL: Principles of Heat Transfer
Rate of Heat Transfer, q
! = # $ %&
Temperature
Over-all heat transfer difference [K or Co]
coefficient [W/m2-K] Heat transfer
Area [m2]

Over-all Heat Transfer Coefficient, U


'
#) = -
' $) +, . Based on the inside area
#$ = ' -) $)
- + +
+, . () /0 1 2 (. $.
' -) '
+ + '
() $) /0 1 2 (. $.
#. = -.
$. +, Based on the outside area
$. -) '
+ +
() $) /0 1 2 (.
Typical Heat-Transfer Coefficients
See Chemical Engineers’ Handbook (Perry et al.): Tables 11-3 to 11-8 (8th ed.)
Typical Heat-Transfer Coefficients
See Chemical Engineers’ Handbook (Perry et al.): Tables 11-3 to 11-8 (8th ed.)
Typical Heat-Transfer Coefficients
See Chemical Engineers’ Handbook (Perry et al.): Tables 11-3 to 11-8 (8th ed.)
Fouling Factor or Fouling Resistance, Rf
$
!" = +
)* +,
$ $ ' $ $
+ + + +
%&' "' %' "' -. / 0 %, ", %&, ",
Additional resistances due to fouling or dirt

(source: manufacturing.net)
(source: tempco.it)

$ $
12 = −
!3'+45 !789:;

• Estimate the percent reduction in the over-all heat


transfer coefficient for Cutback asphalt – water.
(Ans. 15%)
Shell-and-Tube Heat Exchanger

(source: sbs.co.id) (source: Perry et al.)

• Made of casing or shell with tubes arranged inside


• Shell fluid and tube fluid flowing
• Baffles on the shell side to direct flow
Shell-and-Tube Heat Exchanger

• Results to complex flow patterns, which depends on


the configuration (no. of shell & no. of tube passes)

Nomenclature: “no. of shell” - “no. of tube passes” Heat Exchanger

i.e. 1-2 Heat Exchanger à 1 shell – 2 tube pass STHE

2-4 Heat Exchanger à 2 shell – 4 tube pass STHE


Shell-and-Tube Heat Exchanger
Utility Fluid in
t1
T1 ∆"$ t2
Process Fluid in T2
t1
Temperature ∆"#
t2
Process Fluid out T1
T2
Utility Fluid out Length

• Use of correction factor for the LMTD based on counter-current flow


% = ' ( )"*+ ," • FT depends on temperatures in/out and STHE configuration
LMTD Correction Factor, FT
See Chemical Engineers’ Handbook (Perry et al.): Figure 11-4 (8th ed.)
LMTD Correction Factor, FT
See Chemical Engineers’ Handbook (Perry et al.): Figure 11-4 (8th ed.)

#$ − #&
!=
'& − '$
'& − '$
(=
# $ − '$
ILLUSTRATIVE PROBLEM 1
A 1-4 exchanger is used to heat 800 kg/hr of a liquid (Cp = 1600 J/kg-K)
from 30oC to 70oC. The heating medium (Cp = 3200 J/kg-K) enters the
shell at 100oC and leaves at 72oC. Determine:

a) mass rate of heating medium

b) Length per pass if hi = 450 and ho = 2000 W/m2-K and tubes are
1"Sch 40 steel
ILLUSTRATIVE PROBLEM 2
An STHE is to be designed to heat 3.80 kg/s of water from 38oC to 54oC.
Hot water entering at 93oC is to flow (one-pass) thru the shell side at a
rate of 1.90 kg/s. Assume an over-all heat transfer coefficient of 1420
W/m2-oC. Using a tube of 1.90 cm ID, the tube-side average velocity is
0.37 m/s. Due to space constraint, the tube length must not exceed
2.50 m. Determine:

a) Number of tube passes


b) Number of tubes per pass
c) Length of the tube
SEAT WORK (Group of 2 max.)
Water flows through the tubes of a 2-8 exchanger at 20oC and 1 m/s. The
water is heated by nitrogen gas entering the shell at 100oC and leaving at
30oC. The mass rate of the gas is 200 kg/hr. The exchanger is composed
of 1” Sch. 40 steel pipes. Determine the length of the exchanger needed
and the exit temperature of the water.

Assume ho = 4000 and hi = 1000 W/m2-K


Heat Transfer thru Bank of Tubes
Square Pitch Triangular Pitch

(source: thermopedia.com)

(source: Perry et al.)

S = pitch or center-to-center distance between tubes


SL = longitudinal pitch
ST = traverse pitch
ILLUSTRATIVE PROBLEM 3
160 m3/min of air will be heated at 1 atm from 15oC to 45oC by passing it normally
through a bank of vertical tubes that are 1.5 m long. Each bank is 6 rows wide and 4
rows deep and the casing is 39 cm wide. Outside tube diameter is 3 cm and A
triangular pitch of twice the outside diameter is used. Steam at 225oC flows inside
the tubes. Assume no leakage. How many banks of tubes are needed? Assume FT = 1 .
ILLUSTRATIVE PROBLEM 3
- END -