Battery Calculation of KGL

This document provides a battery calculation for a fire alarm system located at Kaniz Garments Ltd. in Dhaka, Bangladesh. It calculates the standby and alarm currents for the various fire alarm components, determining the total standby current to be 2.4476 amps and total alarm current to be 64.6782 amps. Based on these values and the required standby and alarm times per NFPA 72, it determines the minimum required battery capacity to be 113.7189 amp-hours. Applying a 120% safety factor results in a recommended battery capacity of 136.462644 or 150 amp-hours.

Uploaded by

faruk hossain
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
237 views

Battery Calculation of KGL

This document provides a battery calculation for a fire alarm system located at Kaniz Garments Ltd. in Dhaka, Bangladesh. It calculates the standby and alarm currents for the various fire alarm components, determining the total standby current to be 2.4476 amps and total alarm current to be 64.6782 amps. Based on these values and the required standby and alarm times per NFPA 72, it determines the minimum required battery capacity to be 113.7189 amp-hours. Applying a 120% safety factor results in a recommended battery capacity of 136.462644 or 150 amp-hours.

Uploaded by

faruk hossain
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Project Name : Kaniz Garments Ltd.

Address: 228/A, Bir Uttam Mir Shawkat Sarak, Dhaka 1208.

Submitted By: Integrated Technologoy & Services Plc.


Address: 146/Ka, Pisciculture Housing Society,Shyamoli,Dhaka-1207.

BATTERY CALCULATION

STANDBY
DESCRIPTION CURRENT PER QTY
UNIT (AMPS)

Central processing Unit (CPU-3030D) 0.340 X 1


Loop Control Module (LCM-320) 0.130 X 3
Loop Expender Module (LCM-320) 0.100 X 3
Repeater Panel (LCD-160) 0.300 X 1
Smoke Detector (FSP-851) 0.0003 X 284
Heat Detector (FST-851) 0.0003 X 103
Multi Detector (FAPT-851) 0.0003 X 310
Remote Indicator (RA100Z) 0.00000 X 0
Fire Alarm Control Panel
Fire Alarm Control Panel Input Module (FMM-1) 0.0004 X 64
Output Module (FRM-1) 0.0003 X 85
NAC Circuit (FCM-1) 0.0005 X 42
Isolator Module (ISO-X) 0.0004 X 33
Manual Call Point (F/MCP/Glass) 0.0004 X 58
Gas Detector(XCD) 0.8 X 1
Horn Cum Strobe(P2RL) 0 X 160
Sounder(HRL) 0 X 11
TOTAL SYSTEM
STANDBY CURRENT (AMPS)

REQUIRED TOTAL SYSTEM


STANDBY TIME STANDBY
(HRS) NFPA 72- CURRENT
2002 4.4.1.5.3.1 (AMPS)
REQUIRED TOTAL SYSTEM
STANDBY TIME STANDBY
Prepared for:
(HRS) NFPA 72- CURRENT
24
2002 4.4.1.5.3.1 X 2.4476
(AMPS)
REQUIRED REQUIRED
STANDBY ALARM
Prepared by:
CAPACITY CAPACITY (AMP-
58.7424
(AMP-HOURS) + 54.9765
HOURS)
Minimum battery capacity 13
Date:28.04.2019

ON

TOTAL ALARM TOTAL


STANDBY CURRENT ALARM
QTY
CURRENT PER UNIT CURRENT
PER ITEM (AMPS) PER ITEM

= 0.340 0.6800 X 1 = 0.68


= 0.390 0.7800 X 3 = 2.34
= 0.3000 0.6000 X 3 = 1.8000
= 0.3000 0.3250 X 1 = 0.3250
= 0.0852 0.0065 X 284 = 1.846
= 0.0309 0.0065 X 103 = 0.6695
= 0.093 0.0065 X 310 = 2.015
= 0.000 0.00000 X 0 = 0
= 0.0256 0.005 X 64 = 0.32
= 0.0255 0.0065 X 85 = 0.5525
= 0.021 0.0065 X 42 0.273
= 0.0132 0.0004 X 33 = 0.0132
= 0.0232 0.005 X 58 = 0.29
0.8 0.8 1 0.8
0 0.326 X 160 52.16
0 0.054 11 0.594
TOTAL SYSTEM
2.4476 64.6782
ALARM CURRENT (AMPS)
REQUIRED
REQUIRED ALARM TOTAL
REQUIRED
STANDBY TIME SYSTEM
ALARM
CAPACITY (HOURS) ALARM
REQUIRED CAPACITY
(AMP- NFPA 72- CURRENT
REQUIRED ALARM TOTAL (AMP-HOURS)
HOURS) 2002 (AMPS) REQUIRED
STANDBY TIME
4.4.1.5.3.1 SYSTEM
ALARM
CAPACITY (HOURS) ALARM
CAPACITY
= (AMP-
58.7424 NFPA
0.8572- X CURRENT
64.6782 = 54.9765
(AMP-HOURS)
HOURS)
TOTAL 2002
TOTAL (AMPS) ADJUSTED
CAPACITY 4.4.1.5.3.1
CAPACITY SAFETY BATTERY
(AMP- (AMP- FACTOR CAPACITY
= 113.7189
HOURS) 113.7189
HOURS) X 120% = 136.462644
(AMP-HOURS)
battery capacity 136.4626AH . Select battery 150AH