IN-NT-PLUS-1.5 - Reference Guide PDF
IN-NT-PLUS-1.5 - Reference Guide PDF
InteliNano
InteliNano NT Plus
Modular Gen-set Controller with Current
Measurement
Compact Controller for Stand-by Operating Gen-sets
Reference Guide
T ABLE OF CONTENTS
ComAp, a.s..
Kundratka 17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 266 316 647
E-mail: [email protected], www.comap.cz
7.2 Normally Closed Contact ..................................................................................................... 34
8 Outputs settings ............................................................................................................................. 35
NT
8.1 Binary outputs InteliNano Plus - default ............................................................................ 35
8.2 Logical binary outputs .......................................................................................................... 35
9 Inputs settings ................................................................................................................................ 44
NT
9.1 Binary and analog inputs InteliNano Plus - default ........................................................... 44
9.2 Logical binary and analog inputs ......................................................................................... 44
10 Setpoints ................................................................................................................................... 58
10.1 B - Basic settings ................................................................................................................. 61
10.2 E - Engine parameters and protections ............................................................................... 67
10.3 G - Generator protections .................................................................................................... 71
10.4 A – AMF (Auto Mains Failure) settings ................................................................................ 73
11 ECU .......................................................................................................................................... 75
11.1 CAN bus wiring .................................................................................................................... 75
12 Alarms, Events and History Management ................................................................................ 76
12.1 Events .................................................................................................................................. 78
12.2 Warnings .............................................................................................................................. 80
12.3 Shutdowns............................................................................................................................ 82
12.4 ECU Messages .................................................................................................................... 86
13 Technical data .......................................................................................................................... 87
13.1 Power supply ........................................................................................................................ 87
13.2 Operating conditions ............................................................................................................ 87
13.3 Physical dimensions ............................................................................................................. 87
13.4 Binary inputs ........................................................................................................................ 88
13.5 Binary outputs ...................................................................................................................... 88
13.6 Analog inputs ....................................................................................................................... 89
13.7 Generator/Mains measurements ......................................................................................... 89
13.8 Charging alternator preexcitation circuit .............................................................................. 89
13.9 Communication interface ..................................................................................................... 89
13.10 CAN interface ....................................................................................................................... 89
DOCUMENT HISTORY
REVISION NUMBER RELATED SW. VERSION DATE
1.4 11.3.2013
1.5 29.9.2013
CAUTION!
These boxes call special attention to procedures or adjustments, which if done incorrectly can cause
damage or equipment failure.
WARNING!
These boxes call special attention to important procedures or adjustments, which if done incorrectly
could result in personal injury or death.
The following described machine complies with the appropriate basic safety and
health requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
1.3 Important
This manual is intended for use by gen-set control panel builders and parties concerned with
installation, operation, and maintenance of the gen-set.
NT
This manual describes the InteliNano Plus software, which is designed for single set, stand-by and
island applications.
NOTE:
SW and HW must be compatible otherwise some functions will be disabled.
NOTE:
NT
Because of large variety of the InteliNano parameters settings, it is not possible to describe all
NT
combinations. Some of the InteliNano ’s functions are subject of changes depend on SW version.
The data in this manual only describes the product and is not intended as a warranty of performance
or characteristics.
CAUTION!
Dangerous voltage
In no case touch the terminals for voltage measurement!
Always connect grounding terminals!
CAUTION!
All parameters are preset to initial values. But the set points in the “Basic settings” settings group
!!must!! be adjusted before the first startup of the gen-set.
The following instructions are for qualified personnel only. To avoid personal injury do not perform any
action not specified in this User guide!!!
WARNING!
NT
Every time the following InteliNano controller terminals are disconnected:
WARNING!
Remote control
NT
The InteliNano controller can be controlled remotely. When working on the gen-set, ensure that
remote start is disabled.
2.2 Configurability
One of the key features of the controller is high level of adaptability to the needs of every particular
application. This customization is accomplished in the configuration.
NOTE:
Use NanoEdit PC software to the read configuration from the controller or disk, view it, modify it, and
write the configuration to the controller or disk.
The firmware contains large number of binary inputs and outputs for all available. Configuration will
be determined by application and hardware constraints. One of main tasks of the configuration is
mapping of "logical" firmware inputs and outputs to the "physical" hardware input and output terminals.
1. Mapping of logical binary and analog inputs (functions) to physical binary input terminals
2. Mapping of logical binary outputs (functions) to physical binary output terminals
3. Assigning sensor characteristics
4. Selecting of ECU type if an ECU is connected
The controller is delivered with a default configuration, which should fit most standard
applications. The default configuration can be changed from controller’s front panel or by using
NanoEdit PC software. See NanoEdit documentation for details.
NOTE:
For connection with PC use integrated USB module. The controller can be powered directly from USB
communication port. In this case the LCD backlight is turned off and all outputs are open
Once the configuration is modified (using PC) it can be stored in a file for reference or use with
another controller. This configuration file is called the archive and has file extension ".ain". If the
archive is saved while the PC is online with the controller, it will contain a full image (setpoints,
measured values, and history log) of the controller at the moment of saving (except firmware).
The archive can then be used for the cloning of controllers, which means preparing controllers with
identical configuration and settings.
MCB 3x GCB
3x 3x G
GCB MCB
MCB GCB
K2 K1
GCB CLOSE/OPEN
MCB CLOSE/OPEN BO InteliNano
BI
MCB
MCB FEEDBACK
GCB
GCB FEEDBACK
Figure 3.1
STAND-BY APPLICATION WITH TWO SEPARATE BREAKERS – GCB AND MCB WITH INTERLOCK
3x 3x G
GCB
K1
GCB CLOSE/OPEN
BO InteliNano
BI
REMOTE START/STOP
ATS BO
GCB
GCB FEEDBACK
Figure 3.2
MRS APPLICATION WITH GCB CONTROL
3x G
1Ph GENERATOR CURRENT
3Ph GENERATOR VOLTAGE
InteliNano
BI
REMOTE START/STOP
ATS BO
Figure 3.3
SIMPLE MRS APPLICATION
Figure 4.1
INTELINANONT‘S CHASSIS MOUNTING
CAN INTERFACE
L
COM
H
USB interface
POWER SUPPLY, D+
T01 = BATT -
T02 = D+
T03 = BATT +
Figure 4.2
INTELINANONT PLUS TERMINALS DESCRIPTION
NOTE:
In case the InteliNano Plus controller is used as MRS controller the terminals T20, T21, T22 and T23
are used for generator voltage measurement.
+ -
+
C
D
+ -
Motor starter
Figure 4.3
RECOMMENDED POWER SUPPLY WIRING
The capacitor size should be 5 000 µF to withstand 150ms voltage dip under following conditions:
Voltage before the drop is 12V, after 150ms the voltage recovers to min. allowed voltage, i.e. 8V.
+ -
+ -
Motor starter
Figure 4.4
INTELINANONT PLUS POWER SUPPLY FUSING
4.5 D+
Charging alternator D+ output is on terminal T02.
D+ current is 100mA and is switched off after 5s when starter is disconnected.
WARNING!
IF THE D+ FEATURE IS NOT USED, CONNECT THIS TERMINAL TO BATTERY POSITIVE!
In case of charging alternator malfunction the warning Low Battery (Charge Fail) will appear in event
log.
There are several voltage measurement connections for two different applications AMF and MRS. For
more details see table below.
L1
G L2
L3
L1 L2 N L1 L2 L3
GENERATOR MAINS
Figure 4.5
AMF APPLICATION 3 PHASE 4 WIRES TERMINALS CONNECTION
Figure 4.6
STAR CONNECTION
L1
G L2
L3
L1 L2 L1 L2 L3
GENERATOR MAINS
Figure 4.7
AMF APPLICATION 3 PHASE 3 WIRES & LINE TO LINE TERMINALS CONNECTION
Figure 4.8
DELTA CONNECTION (LEFT), HIG-LEG DELTA CONNECTION (RIGHT)
L1
G L2
L1 L2 N L1 L2 N
GENERATOR MAINS
Figure 4.9
AMF APPLICATION SPLIT PHASE TERMINALS CONNECTION
Figure 4.10
DOUBLE DELTA CONNECTION (LEFT), ZIG ZAG(DOG LEG) CONNECTION (RIGHT)
G L1
N L1 N L1 N N
GENERATOR MAINS
Figure 4.11
AMF APPLICATION MONO PHASE TERMINALS CONNECTION
Figure 4.12
MONOPHASE CONNECTION
L1
G L2
L3
N L1 L2 L3
Figure 4.13
MRS APPLICATION 3 PHASE 4 WIRES TERMINALS CONNECTION
L1
G L2
L3
L1 L2 L3
Figure 4.14
MRS APPLICATION 3 PHASE 3 WIRES TERMINALS CONNECTION
NOTE:
In case of Voltage Autodetect function and HIGH-LEG DELTA connection, the N (neutral) wire (in the
diagram connected between T6 and T9) has to be connected to terminal T20.
L1
G L2
N L1 L2 N
Figure 4.15
MRS APPLICATION SPLIT PHASE TERMINALS CONNECTION
G L1
N L1 N N
Figure 4.16
MRS APPLICATION MONO PHASE TERMINALS CONNECTION
L1
k l L2
ECU G
L3
Figure 4.17
RECOMMENDED CT CONNECTION
NOTE:
There is no need to connect “I” terminal of CT to the ground.
NOTE:
Logical binary functions for each binary input have to be assigned during the configuration.
CPU
4K7
5V Out
+ -
Figure 4.18
RECOMMENDED BINARY INPUTS WIRING
WARNING!
Controller outputs switch high side! Never connect any analog sensor to this output to avoid
sensor damage. All outputs are short circuit protected.
CPU
+ -
Figure 4.19
RECOMMENDED BINARY OUTPUT WIRING
CAUTION!
In case of grounded sensors connect the terminal T10 to the engine body as near the sensor as
possible!
CAUTION!
In case of isolated sensors connect the terminal T10 to the negative power supply terminal of the
controller as well as the opposite poles of the sensors!
NOTE:
Value #### is displayed when measured value is out of range or sensor’s wire is broken.
+ -
Figure 4.20
WIRING OF ANALOG INPUTS - GROUNDED SENSORS
+ -
Figure 4.21
WIRING OF ANALOG INPUTS - ISOLATED SENSORS
LOAD
GCB MCB
DIESEL / GASOLINE ENGINE GENERATOR
L1
k l L2
ECU G
L3
N
Fuel Solenoid
Sarter
L COM H
CAN
USB
D+
Emergency Stop
Remote Start And Load
COM
Ready To Load
Alarm
GCB
MCB
Fuel Solenoid
Starter
Battery +
D+
Battery -
PC
Figure 5.1
TYPICAL WIRING DIAGRAM OF AMF APPLICATION
NOTE:
MCB and GCB are recommended to be mechanically interlocked.
LOAD
L1
k l L2
ECU G
L3
N
Fuel Solenoid
Sarter
L COM H
CAN
USB
D+
Emergency Stop
Remote Start And Load
COM
Ready To Load
Alarm
Fuel Solenoid
Starter
Battery +
D+
Battery -
PC
Figure 5.2
TYPICAL WIRING DIAGRAM OF MRS APPLICATION
If you have not configured custom initialization (init) screen then press and hold Stop button, then
briefly press ▲ button then Auto (Figure 6.1).
hold + press
Figure 6.1
ENTRY TO SETUP MODE (WITHOUT CUSTOM SCREEN)
If you have already created your own init screen then press and hold Stop button and then press
briefly press ▲, the custom init screen will appear, keep holding the Stop button. Then press ▼ to
switch LCD to default init screen and then press Auto (Figure 6.2).
hold + press
hold + press
Figure 6.2
ENTRY TO SETUP MODE (WITH CUSTOM SCREEN)
NOTE:
The controller will automatically switch to Setup mode when there is a problem with the CRC or there
is an incompatibility between firmware and archive version. This situation can occur when you
upgrade a firmware. If this occurs, verify that all setpoints are properly configured.
Basic settings
Generator protections
Outputs settings
Inputs settings
ECU setting
Info
Figure 6.4
SETUP MENU ORGANIZATION
To apply all changes return to the main setup menu and restart the controller by pressing the Stop
button.
Each logical binary input and output can be configured as Normally Open (NO) or Normally Close
(NC)
Inputs
Terminal Type Direction Input function assignment
I00, I01, I04, I05, I06, I07, I10, I11, I12, I13, I14, I15, I20, I22,
T07 binary input/output
I24, I29
I00, I01, I02, I03, I04, I05, I06, I07, I10, I11, I12, I13, I14, I15,
T11 binary input
I20, I22, I24, I29
I00, I01, I04, I05, I06, I07, I10, I11, I12, I13, I14, I15, I20, I22,
T12 binary input
I24, I29
I00, I01, I04, I05, I06, I07, I10, I11, I12, I13, I14, I15, I20, I21,
T13 binary/analog input
I22, I23, I24, I25, I29
I00, I01, I04, I05, I06, I07, I10, I11, I12, I13, I14, I15, I20, I21,
T14 binary/analog input
I22, I23, I24, I25, I29
I00, I01, I04, I05, I06, I07, I10, I11, I12, I13, I14, I15, I20, I21,
T15 binary/analog input
I22, I23, I24, I25, I29
Outputs
Terminal Type Direction Input function assignment
O00, O01, O02, O03, O04, O05, O06, O07, O08, O09, O10,
T04 binary output
O11
T05 binary output O00, O02, O03, O04, O05, O06, O07, O08, O09, O10, O11
T06 binary output O00, O02, O03, O04, O05, O06, O07, O08, O09, O10, O11
T07 binary input/output O00, O02, O03, O04, O05, O06, O07, O08, O09, O10, O11
T08 binary output O00, O02, O03, O04, O05, O06, O07, O08, O09, O10, O11
T09 binary output O00, O02, O03, O04, O05, O06, O07, O08, O09, O10, O11
NOTE:
All inputs except for Fuel Level Analog, Coolant Temperature Analog and Oil Pressure Analog
NT
can be configured to the InteliNano controller terminal number T11, T12, T13, T14, T15 and shared
input/output terminal T07. All outputs exceptStarter, can be configured to terminal T04, T05, T06,
T07, T08 and T09. Binary output Starter can be configured only to high current output terminal T04.
In this case 0V on the binary output represents a logical 0 (L) Battery positive voltage on the output
represents a logical 1 (H).
In this case 0V on binary output represents a logical 1 (H). Battery positive voltage on the output
represents a logical 0 (L).
T08 Alarm
For the configuration of outputs use the PC software, NanoEdit, or switch controller to setup mode.
Figure 8.1 is an example of how to configure a binary output via the controller’s screen. First select an
output terminal. Then use ▲ and ▼ buttons to select a function. Then press Start button to confirm
the selection. Lastly press Stop button to return. Then choose a logical function (O00 - O09) and
select contact type (Normally Open contact or Normally Closed contact) and confirm the change.
Output has no function. Use this configuration when output is not connected.
O01 Starter
This output is dedicated for starter motor control. The number of cranking attempts is 6.
Starter Output
6 Cranking Attempts
On
Off
Start Time
Starter Output
Engine run
On
Off
Start Time
The starter output become inactive when one of following conditions is reach or exceeded.
This output is dedicated to control the fuel solenoid (valve). The output is closed in the same time as
Starter output and remains closed while the engine is running.
Starter Output
On Fuel Solenoid is
opened
Off
Start Time
Starter Output
Engine run
On Fuel Solenoid is
opened
Off
This output is dedicated to control the stop solenoid (valve). The output closes when an engine stop
command is received and remains active until the gen-set is stopped.
RPM < 2
and
Generator voltage < 10V
and
Oil pressure < 3 Bar. (43 PSI)
Stop Solenoid
Output Engine run 10 s
Cooling Time
RPM / Frequency
D+
Oil Pressure
Generator voltage
On Fuel Solenoid is
opened
Off
Stop Time 60 s
Gen-set stoped
Stop Time
Stop Solenoid
Output Engine run 10 s
RPM / Frequency
D+
Oil Pressure
Generator voltage
On Fuel Solenoid
is opened
Off
Stop Time
The output is to be used for external alarm indication. The output is active when at least one
unconfirmed and active alarm is present in the event log.
This output is to be used for a contactor control in case a contactor is used in the GCB position.
GCB position is indicated on the mains screen when feedback is configured.
Wrong breaker / contactor position is indicated on mains screen also.
This output is to be used for a contactor control in case a contactor is used in the MCB position.
Output is configured as close-off! When the binary output is inactive (open) the MCB is on-state,
when binary output is active (close) the MCB is open.
Output can also be configured with inverse output logic – (NC).
The output is activated when gen-set is running and all electrical values are in limits and no shutdown
alarms are active - it is possible to close GCB or it is already closed. The output opens during cooling
state or when emergency stop or any shutdown is active.
The output is activated while engine is cranking, but prior to the engine start. It is deactivated when
25% of Nominal RPM speed is reached. This output is typically used for pre-heat or pre-lubrication.
Starter Output
Prestart Output
On On
Off
Start Time
Starter Output
Engine run
Prestart Output
On On
Off
Start Time
This output is to be used for "keyswitch" input to the ECU. If the particular ECU does not have
keyswitch or similar input, it can be used for control of DC power for the ECU.
The output closes together with O08 Prestart and remains closed while the engine is running. It is
opened when a stop command is received. (I.e. together with the O02 Fuel Solenoid ).
NOTE:
The controller does not evaluate the communication failure alarm during the period when this output
is not active.
The output is activated while engine is cranking and between cranking attempts. Choke Time (timer)
will start on engine rune. The Choke output will close when Choke Time elapsed.
Starter Output
On Choke Output
On
Off
Start Time
Starter Output
Engine run
Choke Time
On Choke Output
On
Off
This output is activated before each cranking procedure for Prestart Time but maximally for 8s!
Starter Output
Maximum Maximum
Cranking Time Cranking Time
0 - 60 s 0 - 60 s
On Glow Plugs
Output On
Off
Start Time
Starter Output
Maximum Maximum
Cranking Time Cranking Time
8s 0 - 60 s 0 - 60 s
On Glow Plugs
Output On
Off
Start Time
Starter Output
8s Engine run
Off
Start Time
For the configuration of inputs use the PC software, NanoEdit, or switch the controller to setup mode.
This is an example of how to configure a binary input via the controller’s screen. First select an input
terminal. Then use ▲ and ▼ buttons to select a function. Then press Start button to confirm the
selection. Lastly press Stop button to return. Then choose a logical function (I00-I20, I22 and I24)
and select contact type (Normally Open contact or Normally Closed contact) and confirm change.
Figure 9.2 is an example of how to configure a binary input as analog.
3x 3x
Input has no function. Use this configuration when binary or analog input is not connected.
Hint:
T07 T07 is input-output terminal. Primarily it is configured as an output. To configure as an input,
assign the function O00 Not Used in the output configuration.
This input will activate the built-in Emergency Stop alarm. It is recommended to use a Normally
Close button for this input.
If this binary input is activated, the left red LED above Stop button will blink, the general shutdown
symbol will be displayed on LCD’s upper right corner, Emergency Stop symbol will be displayed on
event log with running hours stamp and shut down procedure will occur. For more details see
Shutdown procedure in chapter 12 Alarm, Events and History Management.
CAUTION!
This is a software function only.
NOTE:
The Remote Start/stop can be configured only on terminal T11 This is also used for waking the
controller from “Zero Power” mode.
In AMF mode this input starts the engine and transfers the load to the generator after all engine and
generator parameters are within tolerance (open MCB and close GCB). When this input is
deactivated the controller will transfer the load back to mains and stop the engine.
In MRS mode this input starts engine and closes the GCB (only when is configured). When this input
is deactivated the controller will open the breaker (only when is configured) and stop the engine.
NOTE:
The Remote Start And Load can be configured only on terminal T11. This is also used for waking
the controller from “Zero Power” mode.
When this input is closed, the automatic start of the gen-set at Mains failure is blocked. If the gen-set
is running, the GCB is opened, and gen-set stops. This input doesn’t affect the mains circuit breaker.
This input indicates whether MCB is closed or opened. Available only in AMF mode.
This is an input from the generator circuit breaker. If the input is active, the controller will consider the
GCB as closed and vice versa. If the GCB is not in expected position, the alarm GCB Fail will occur.
For more details see Shutdown procedure in chapter 12 Alarm, Events and History Management.
NOTE:
The feedback time limit is 5s.
If this binary input is activated the red LED above Stop button will blink, general warning symbol will
be displayed on LCD’s upper right corner and External Warning 1 symbol will be displayed on event
log with running hours stamp. This alarm is only warning. For more details see Warning procedure in
chapter 12 Alarm, Events and History Management.
If this binary input is activated the red LED above Stop button will blink, general warning symbol will
be displayed on LCD’s upper right corner and External Warning 2 symbol will be displayed on event
log with running hours stamp. This alarm is only warning. For more details see Warning procedure in
chapter 12 Alarm, Events and History Management.
If this binary input is activated left red LED above Stop button will blink, general warning symbol will
be displayed on LCD’s upper right corner and External Warning 3 symbol will be displayed on event
log with running hours stamp. This alarm is only warning. For more details see Warning procedure in
chapter 12 Alarm, Events and History Management.
When this binary input is activated the red LED above Stop button will blink, general shutdown
symbol will be displayed on LCD’s upper right corner, External Shutdown 1 symbol will be displayed
on event log with running hours stamp, and the shutdown procedure will occur. For more details see
Shutdown procedure in chapter 12 Alarm, Events and History Management.
CAUTION!
This is a software function only.
When this binary input is activated the red LED above Stop button will blink, general shutdown
symbol will be displayed on LCD’s upper right corner, External Shutdown 2 symbol will be displayed
on event log with running hours stamp, and the shutdown procedure will occur. For more details see
Shutdown procedure in chapter 12 Alarm, Events and History Management.
CAUTION!
This is a software function only.
When this binary input is activated the red LED above Stop button will blink, general shutdown
symbol will be displayed on LCD’s upper right corner, External Shutdown 3 symbol will be displayed
on event log with running hours stamp, and the shutdown procedure will occur. For more details see
Shutdown procedure in chapter 12 Alarm, Events and History Management.
CAUTION!
This is a software function only.
When this binary input is activated the red LED above Stop button will blink, the general warning
symbol will be displayed on LCD’s upper right corner, and Low Fuel Level symbol will be displayed
on event log with running hours stamp. This alarm is only warning. For more details see Warning
procedure in chapter 12 Alarm, Events and History Management.
NOTE:
Input has 10s delay.
Analog input for fuel level measurement. When measured value exceeds the preset threshold, the left
red LED above Stop button will blink, the general warning symbol will be displayed on LCD’s upper
right corner, and fuel level symbol will be displayed on event log with running hours stamp. This alarm
is only warning. For more details see Warning procedure in chapter 12 Alarm, Events and History
Management.
Alarm threshold is 20% of measurement range. You can choose one from two preset resistive
sensors (VDO, Datcon) or you can create your own sensor curve.
NOTE:
Input has 10s delay.
VDO Level %
Ohm %
1 0 0
2 10 0
3 96 50
4 180 100
When this binary input is activated the red LED above Stop button will blink, the general shutdown
symbol will be displayed on LCD’s upper right corner, the oil pressure symbol will be displayed on
event log with running hours stamp, and the shutdown procedure will occur. For more details see
Shutdown procedure in chapter 12 Alarm, Events and History Management.
Analog input for oil pressure measurement. When the measured value exceeds the preset threshold
the red LED above Stop button will blink, the general shutdown symbol will be displayed on LCD’s
upper right corner, the oil pressure symbol will be displayed on event log with running hours stamp
and the shutdown procedure will occur. For more details see Shutdown procedure in chapter 12
Alarm, Events and History Management.
Default threshold is 1 Bar of measurement range. You can choice one from five default resistive
sensors (VDO, Datcon) or you can create your own sensor curve.
You can setup shutdown threshold (E04 Oil Pressure Shutdown) in Engine parameters and
protection group.
NOTE:
Input has 3s delay.
VDO 5 Bar
Ohm Bar
1 10 0
2 50 1
3 85 2
4 119 3
5 152 4
6 180 5
Datcon 5 Bar
Ohm Bar
1 33,5 5,5
2 153 1,4
3 240 0
4 350 0
Datcon 10 Bar
Ohm Bar
1 33,5 10,3
2 153 2,6
3 240 0
4 350 0
When this external binary input is activated the red LED above Stop button will blink, the general
shutdown symbol will be displayed on LCD’s upper right corner, the Coolant Temperature symbol will
be displayed on event log with running hours stamp, and the shutdown procedure will occur. For more
details see Shutdown procedure in chapter 12 Alarm, Events and History Management.
Analog input for coolant temperature measurement. When the measured value exceeds the preset
threshold, the red LED above Stop button will blink, the general shutdown symbol will be displayed
on the LCD’s upper right corner, the coolant temperature symbol will be displayed on event log with
running hours stamp, and the shutdown procedure will occur. For more details see Shutdown
procedure in chapter 12 Alarm, Events and History Management.
Default threshold is 90°C. You can choose one from four default resistive sensors (VDO, Datcon) or
you can create your own sensor curve.
You can setup shutdown threshold (E05 Coolant Temperature Shutdown) in Engine parameters
and protection group.
NOTE:
Input has 5s delay.
VDO 40-120 °C
Ohm °C
1 22 120
2 29 110
3 52 90
4 69 80
5 95 70
6 135 60
7 195 50
8 290 40
9 440 30
10 700 20
11 1800 0
12 3200 -16
Datcon High °C
Ohm °C
1 20 161
2 30 139
3 66 111
4 78 105
5 108 94
6 118 91
7 339 50
8 841 25
9 1343 4
10 1845 -12
When this binary input is activated the red LED above Stop button will blink, the general warning
symbol will be displayed on LCD’s upper right corner. Fuel Level SD symbol will be displayed on event
log with running hours stamp and shutdown procedure will occur.
Figure 10.1
NOMINAL FREQUENCY SETUP EXAMPLE
Generator protections
Setpoint
Setpoint name
code
G01 Generator Overvoltage Shutdown
G02 Generator Undervoltage Shutdown
G03 Generator Overfrequency Shutdown
G04 Generator Underfrequency Shutdown
G05 Generator Short Circuit Shutdown
G06 Generator Short Circuit Delay
Nominal system voltage (phase to neutral). This setpoint can be hidden depending on the connection
type (setpoint B04 Connection Type). You can setup this value only if you will choose the connection
type as Mono phase or Split phase - B04 Connection Type (1; 2).
Nominal system voltage (phase to phase). This setpoint can be hidden depending on the connection
type (setpoint B04 Connection Type).You can setup this value only if you will choose the connection
type as 3Ph3Wire or 3Ph4Wire - B04 Connection Type (3; 4).
Autodetect:
High-Leg Delta L1 >=100V; L1 <=140V
L2 >=140V
or L3 >=100V; L3 <=140V
NOTE:
The Autodetect option is available only when B06 AMF Function is disabled!
When you change this setpoint all values will be automatically recalculated including user definable
sensor curve for analog input
When AMF Function is disabled than the system is working as MRS controller and setpoints related
to AMF function are hidden.
Figure 10.2
AMF SCREENS
Figure 10.3
MRS SCREENS
The controller is switched to Zero Power Mode when there is no user interaction with the controller for
the preset time. Zero Power Mode is disabled in AMF mode. Value 0 also disables this function. For
the controller wake up press button Start or activate input T11. The controller will not switch to Zero
Power Mode if any alarm is active.
This setpoint is available only when B06 AMF Function is disabled. When this setpoint is enabled,
the controller is switched to special operation mode. First screen was changed and generator voltage
measurement is hides in this operation mode.
First main screen shows battery voltage, running hours and engine status (stop,
starting/stopping, run) via symbol in light tower reflector (upper left corner).
Second screen shows all analog values which are available. (Oil Pressure, Coolant
Temperature; Fuel Level and Battery Voltage)
Last screen is event log.
Figure 10.4
LIGHTTOWER SCREENS
It is nominal generator current. This value is used as a base for Generator Short Circuit alarm
(shutdown). For overcurrent limit set the setpoint Generator Short Circuit Shutdown.
Nominal Current can be different from generator rated current value.
B10 CT Ratio
Units: Ampere [A]
Step: A/5A
Range: 1 – 5000 A
Default value: 50 A
For CT Ratio < 50 the values of power and current are displayed in a controller with one decimal.
For CT Ratio ≥ 50 the values of power and current are displayed in a controller with integral numbers.
Time of closing of the O08 Prestart output prior to the engine start.
Set to zero if you want to leave the output O08 Prestart open.
When this protection is activated the red LED above Stop button will blink, the general shutdown
symbol will be displayed on LCD’s upper right corner. Fuel Level SD symbol will be displayed on event
log with running hours stamp and the shutdown procedure will occur.
Counts down when the engine is running. When the counter reaches zero, an alarm will appear.
When the value 10000 is set, than the Maintenance function is disabled and counter will not count.
Counter value will not appear in the controller’s statistics. Maximum value for running countdown is
9999. Warning Maintenance will appear when counter time has elapsed.
When this setpoint is enabled, the controller will use Low Oil Pressure or Oil Pressure Analog
signal for starter disengagement. Starter will disengaged when oil pressure reach starting oil pressure
or binary input Low Oil Pressure will be opened (Normally Open contact) or closed (Normally
Close contact).
When is disabled then only RPM (frequency), generator voltage or D+ will be used for starter
disengagement.
Starter Output
On Choke Output
On
Off
Start Time
Starter Output
Engine run
Choke Time
On Choke Output
On
Off
Minimum time after reaching of defined level of RPM to the closing GCB.
Starter Output
Engine run
Start Time
Threshold for generator overvoltage. All three phases are evaluated. Maximum value is used.
Generator Overvoltage alarm will appear when output voltage exceed preset threshold and
shutdown procedure will start.
Threshold for generator undervolatge. All three phases are evaluated. Minimum value is used.
Generator Undervoltage alarm will appear when output voltage exceed preset threshold and
shutdown procedure will start.
Threshold for Generator Overfrequency alarm, relative to the nominal frequency (setpoint B03
Nominal Frequency).
Threshold for Generator Underfrequency alarm, relative to the nominal frequency (setpoint B03
Nominal Frequency).
Generator Short Circuit shutdown occurs when generator current exceed preset current limit longer
than Generator Short Circuit Delay.
Delay for the Generator Short Circuit alarm. The limit for this alarm is adjustable by setpoint
Generator Short Circuit Shutdown.
Delay between the mains failure and the automatic start of the gen-set to an AMF operation.
This is a "mains stabilization" time. Timer begins when mains returns. If the mains are continuously
healthy for this period, the controller will finish the AMF operation.
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint B01 Nominal Voltage Ph-N or B02 Nominal Voltage Ph-Ph
depending on B04 Connection Type setting).
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint B01 Nominal Voltage Ph-N or B02 Nominal Voltage Ph-Ph
depending on B04 Connection Type setting).
Threshold for detection of mains failure due to overfrequency. The setpoint is adjusted relative to the
system nominal frequency (setpoint B03 Nominal Frequency).
Threshold for detection of mains failure due to underfrequency. The setpoint is adjusted relative to the
system nominal frequency (setpoint B03 Nominal Frequency).
If ECU is configured simultaneously with analog inputs (Fuel Level Analog, Oil Pressure Analog,
Coolant Temperature Analog) value from analog measurement will be displayed and used for
protection.
If ECU is configured simultaneously with binary inputs (Low Fuel Level, Low Oil Pressure, High
Coolant Temperature) value from ECU will be displayed. For protections is used value from ECU and
binary input signal. For more detail see example.
ECU configured Analog input Binary input Protections from Displayed value from
yes no no ECU ECU
yes yes no analog input analog input
yes no yes ECU or binary input ECU
yes yes yes analog or binary input analog input
no no yes binary input binary input status
Maximal length of the CAN bus depends on the communication speed. For the speed of
250kbps, which is used on the CAN for communication with ECU the maximal length is 200m.
The bus must be wired in linear form with termination resistors at both ends. No nodes except
on the controller terminals are allowed.
Use cable with following parameters:
Event
Warnings
Shutdowns
ECU Messages
Four records can be displayed simultaneously on the LCD screen. Total capacity is 10 records. The
Figure 12.1 is an example of how the history is organized. The last screen in this example is showing
the four latest events.
To view further history records press ▼ button see Figure 12.1.For alarm (shutdown) confirmation press
Stop button.
Figure 12.1
Figure 12.3
EVENT – POWER ON
Possible Events
Mains Return
Mains has returned. All mains parameters are within the preset range.
Mains Fail
Mains failure detection depends on Auto mains failure setpoints.
Manual Start
Engine was manually started by pressing button Start in Manual mode.
Remote Start
Engine was remotely started via input terminal’s function I02 Remote Start/Stop or
I03 Remote Start And Load. The controller is in Auto mode.
AMF Start
Engine was automatically started because of mains failure. The controller is in Auto
mode.
Manual Stop
Engine was manually stopped by pressing button Stop in Manual mode.
Remote Stop
Engine was remotely stopped via input terminal’s function I02 Remote Start/Stop or
I03 Remote Start And Load. The controller is in Auto mode.
Auto On
Auto mode is active.
Auto Off
Auto mode is inactive
Power On
The controller is turned on.
Island Operation
Load is powered from generator.
Figure 12.4
ACTIVE WARNING – LOW BATTERY
Figure 12.5
INACTIVE WARNING – LOW BATTERY
Warning Maintenance
The service interval is determined by the setpoint E07 Maintenance. The protection
becomes active when the engine running hours reach this value.
External Warning 1
This warning occurs when external warning 1 input is activated.
External Warning 3
This warning occurs when external warning 3 input is activated.
MCB Fail
Failure of mains circuit breaker.
Figure 12.6
ACTIVE UNCONFIRMED SHUTDOWN – EMERGENCY STOP
Figure 12.7
ACTIVE CONFIRMED SHUTDOWN – EMERGENCY STOP
Figure 12.8
INACTIVE UNCONFIRMED SHUTDOWN – EMERGENCY STOP
Figure 12.9
INACTIVE CONFIRMED SHUTDOWN – EMERGENCY STOP
Emergency Stop
The binary input Emergency Stop was activated.
Overspeed
The protection comes active if the speed is greater than 115% of nominal engine
RPM, which is derived from generator frequency.
Underspeed
Low engine RPM. This alarm will be issued when the gen-set is running and then
stops by itself, i.e. the RPM drops under the nominal engine RPM.
The underspeed alarm starts to be evaluated 5 sec after successful gen-set start and
is being evaluated all the time the Fuel Solenoid is on.
External Shutdown 1
External Shutdown 2
GCB Fail
Failure of generator circuit breaker.
Generator Overvoltage
Generator will stop when output voltage exceeds the preset threshold G01 Generator
Overvoltage Shutdown.
Generator Undervoltage
Generator will stop when output voltage drops below the preset threshold G02
Generator Undervoltage Shutdown.
Generator Overfrequency
The generator frequency is out of limits given by setpointsG03 Generator
Overfrequency Shutdown and G04 Generator Underfrequency Shutdown .
Generator Underfrequency
The generator frequency is out of limits given by setpointsG03 Generator
Overfrequency Shutdown and G04 Generator Underfrequency Shutdown .
Start Fail
Gen-set start failed.
Stop Fail
Gen-set stop failed.
Battery Flat
If the controller loses power during starting sequence due to bad battery condition, it
will not try to start again and will activate this protection.
Fuel Level SD
This shutdown occurs when analog input Fuel Level is below shutdown level or binary
input Fuel Level SD is closed longer than 10s.
Figure 12.10
ECU MESAAGE
ECU Message
Diagnostic messages are read and displayed in the history behind the ECU Warning
symbol. For Standard J1939 SPN (Suspect Parameter Number) and FMI (Failure
Mode Identifier) are shown.
Detail SPN/FMI code specification see in:
• SAE Truck and Bus Control and Communications Network Standards Manual,
SAE HS-1939 Publication
• Or refer to corresponding engine manufacturer’s ECU error codes list.
Complete list of text diagnostic messages for each ECU can be found in ComAp
Electronic Engines Support manual.
NOTE:
One low current (500mA) binary output – T07 can be configured as binary input .