ABB EDF GCB Manual PDF
ABB EDF GCB Manual PDF
FUNCTIONAL VALUES
1 H Y B 8 0 0 0 0 1 - 53
2
LUBRICANTS
1HYB800001-28
3
LOCKING LIQUID FOR THREADS
1HYB800001-29
4
GENERAL INSTRUCTIONS FOR
MAINTENANCE, TRANSPORT & STORAGE
1HYB800001-30
5
GOODS MARKING AND TRANSPORT
1HYB800001-31
6
STORAGE PRIOR TO ERECTION
1HYB800001-32
7
INFORMATION
SF6 GAS AND GAS MIXTURES
1HYB800001-33 8
SAFETY REGULATIONS
1HYB800001-35
9
DISPOSAL AND RECYCLING
1HYB800001-36
10
INSTRUCTIONS FOR ERECTION,
OPERATION AND MAINTENANCE
1 H Y B 8 0 0 0 0 1 - 54
11
INSTRUCTIONS FOR OPERATION
AND MAINTENANCE OPERATING
MECHANISM TYPE FSA -
1HYB800001-38
12
1HYB800001-26 Rev. A
Page 1
The circuit-breaker is built up of three separate poles, which consist of three main
parts. At the bottom, the mechanism housing is made of aluminium. The hollow post
insulators, through which operating insulators run and on top, the breaking units.
Each breaking unit consists of a hollow insulator which together with an upper and a
lower flange constitute the casing and a lower and an upper current path with a
contact system. The moving contacts are assembled on the lower current path
whereas the fixed contacts are assembled on the upper one.
The circuit-breaker poles to ED SK are permanently filled with SF6 - gas, normally to
the pressure 0.7 MPa absolute at 200C. For monitoring the pressure the circuit-
breaker is equipped with a density monitor. The poles are mounted on a common
supporting frame, consisting of a front and a rear pole beam. The latter is mounted
on two supports which are anchored to the foundations. The beams and supports are
hot-dip galvanized.
The pressure rise and gas flow which are necessary for extinguishing the arc during
the course of breaking are produced partly by compression of the gas, partly by the
energy given from the arc.
At the opening operation, the moving contact is pulled downwards over the fixed
piston and the confined quantity of gas is compressed and at high speed forced out
through the springs in the upper end of the cylinder. At the same stage the arcing
contacts are separated and an arc occurs. A specially formed nozzle leads the
outflowing gas towards the arc. The gas is allowed to pass both downwards through
the moving arcing contact and upwards past the fixed arcing contact.
For the continuous current there are separate contacts which are not affected by the
arc at breaking.
At closing operation, the moving contact is pushed upwards at which time the con-
tacts engage and the cylinder is filled with gas again.
Functional Values
SF6 BREAKER TYPE ED-SKS 1-1 (72.5 kV) WITH OPERATING DEVICE TYPE FSA 1
Resistance of the main circuit across a breaking unit: Max. 50 at rated current 2000
A/1600 A.
*) ON-OFF time means the time during which the main contacts are closed at a
closing operation when the tripping impulse is connected in simultaneously, via
the auxiliary contact.
1HYB800001-28 Rev. A
Page 1
Grease “G” :
Low temperature grease for all types of bearings, gears and worm gears as well as
valves in air-blast circuit-breakers. Also suitable for lubrication of silverplated con-
tacts in air (e.g. contacts in disconnectors).
Also used when greasing O-rings made from nitrile rubber and as a crevice corrosion
prevention.
Grease “N” :
For lubrication of moving contacts in SF6-insulated circuit breakers (e.g. puffer
cylinders). A very thin layer of the grease shall be rubbed on the sliding surface of
the contacts.
Grease “L” :
Low temperature grease specially suitable for lubricating of fine mechanics-e.g. catch
devices in operating mechanism which shall operate in strong cold.
Grease “M” :
Low temperature grease for long-duration and permanent lubrication of worm gears
and other machine elements. Prevents wear and corrosion.
Grease “P” :
Grease “R” :
EP-grease for heavily-loaded roller bearings, slide bearings, cam discs and catches
(Lithium grease. Solvent refined mineral oil with lithium soaps and molybdenum
disulphide) in operating mechanisms type FSA.
Grease “S” :
Fluoro-silicone grease for greasing of O-ring made from EPDM and as a corrosion
prevention of gaps in circuit-breakers type ED.
Grease “SV”
Grease for lubricating moving contacts, silver plated connections and brushed
aluminium surfaces in fixed joints outdoors.
1HYB800001-28 Rev. A
Page 3
1HYB800001-29 Rev. A
Page 1
Pre-treatment of surfaces : The surfaces shall be free from oil, grease, wax, paint and
rust-preventive. Locking Liquids “A”, “B” and “C” are designed for use in only surfaces
also.
Locking Liquid “B” : Medium strong locking of threads and sealing of screws and
nuts.
Locking Liquid “C” : Strong locking and sealing of studs and bolts up to M36.
Difficult to dismantle.
LOCTITE Ltd.
LOCTITE Ltd.
1HYB800001-30 Rev. A
Contents :
1. Safety precautions
2. Cleanliness
3. Cleaning
4. Waste disposal
5. Emptying of gas
1HYB800001-30 Rev. A
Page 1
1. Safety precautions
Follow the local high-voltage safety regulations. Put the breaker in the “OPEN”
position.
Disconnect and earth the high voltage side.
Disconnect the operating and heating voltage.
Work on the insulators of the breaker or live parts as well as transport and
dismounting of complete breaking poles may not be done before the breaker is
emptied to a max. pressure of 0.15 MPa abs. Before the opening of the normally
pressurised vessel, it shall be emptied completely to atmospheric pressure. If the
gas is emptied into the free air, this shall be done through a dust and absorption filter.
See under clause “Emptying of gas”.
2. Cleanliness
Very high dielectric requirements are placed on the SF6 gas and on the insulating
parts and correspondingly also on their cleanliness and dryness.
On all work on the open circuit breaker, be aware that not only dirt but also air
moisture and hand perspiration are deleterious.
If for any reason gas spaces or parts thereof are exposed to air for longer than 24
hours, the gas spaces are to be closed temporarily and filled with SF 6 gas to Pabs =
120 kPa (1.2 bar). Single parts are to be sealed in plastic bags and kept in storage.
Unused SF6 gas is non-poisonous, odourless and colourless. However, it is heavier
than air and with substantial outflow, it gathers easily in low situated spaces like
cable trenches, tanks and such.
With large amount of SF 6 in these spaces, there is a risk of suffocation due to lack
of oxygen.
- Perform overhaul work only with adequate room ventilation.
- The decomposition products which are formed in the breaking elements are in
combination with humidity corrosive and can cause skin, eye and mucous
membrane irritation. During the opening and internal cleaning of the breaker, a
close fitted mask with a filter against fine dust and acid gases, protective
plastic or rubber gloves and a long sleeved overall shall be used.
The dust (decomposition products), that is formed in the breaker, shall be sucked
with a vacuum cleaner provided with a dust filter and wiped off with a cloth that is
sprinkled with ethanol or toluol.
All the dust as well as the used absorption agent is stored in a sealed container and
is disposed off as chemical waste according to the valid provisions. During waste
disposal and handling with decomposition products, it is necessary to wear
protective gloves.
Drying cloths, protective gloves and vacuum cleaner bags shall be rinsed carefully
with plenty of water.
1HYB800001-30 Rev. A
Page 2
3. Cleaning
A. Insulator with paint-treated plastic outside surface, silicon rubber sheds or porce-
lain insulator.
Rinse the outside surfaces thoroughly with water and let it dry well before the
breaker is opened.
The end and inside surfaces are cleaned with a non fluffy drying cloth soaked with
ethanol.
Cleaned insulators must be touched only with clean protective gloves (plastic or
rubber).
Cover the end surfaces of the insulators with a strong plastic foil to protect from
recontamination.
B. Single parts
Vacuum immediately after disassembly with a vacuum cleaner with a fine dust
filter. Wipe off persistent dust with a non fluffy cloth.
Remove stubbornly adhering dust with a cloth soaked with ethanol.
Cover cleaned details with plastic foil or put in plastic bag.
Details from spaces not filled with SF6 shall be cleaned with ethanol and then left
to dry in air. Then they are packed in plastic bags.
4. Waste disposal
All the dust as well as the used absorption agent is stored in a sealed container and
is disposed off as chemical waste according to the valid provisions. During waste
disposal and handling with decomposition products, it is necessary to wear protective
gloves.
5. Emptying of gas
The breaker is evacuated by means of the gas treatment equipment, that purifies and
compresses the gas, so that it can be reapplied.
Mixed gas - SF 6 + N2 - can only be reapplied if the mixing conditions are under
control.
After the evacuation, the breaker is filled with nitrogen up to atmospheric pressure
and after this, evacuated again. In this way, the eventual free drifting dust in the
breaker is removed.
Finally the breaker is filled again with dry nitrogen up to atmospheric pressure after
which it is ready for dismounting and transport to the workshop.
NOTE
If work on the circuit-breaker only affects the outside of the breaker, for example
cleaning of the insulators, it is sufficient to empty the breaker down to a pressure of
0.15 MPa abs, normal working pressure.
1HYB800001-31 Rev. A
Page 1
- Up
DO NOT TILT - It is not allowed to tilt the transport unit more than 45 degrees
MORE THAN 45”
- Centre of gravity
Every transport unit must be fixed during the transport. The tying must be so
arranged that the transport units can not move in any direction. Velocity should be
adapted to the road conditions. Violent acceleration or retardation can cause damage
to the contents without damaging the packing.
1HYB800001-31 Rev. A
Page 2
Lifting
Before lifting, the symbols on the transport unit (such as centre of gravity, weight
etc.) should be observed. The transport units should be lifted with a lifting machine
provided with forks of slings (see fig. 2). If a crane is utilised slings should be used.
The units may not be rolled or dropped from the conveying or lifting equipment.
The operating mechanisms FSA should be lifted by the lifting devices on top of the
cubicle. Lifting slings should never be used around the operating mechanism (see fig.
3)
Lifting the breakers out of the transport units is only necessary just before erection
(see product information, which can be found in the cubicle of the operating
mechanism). If they are going to be stored, see “Storage prior to erection”.
1HYB800001-31 Rev. A
Page 3
Stacking
Transport units with different widths may not be stacked (the pressure may break the
cover of the lower transport units. It should be noted that stacking causes sideways
instability, and therefore the load has to be fixed, i.e. prevented from dropping, rolling
or falling. It is not allowed to stack more than three transport units.
Figure 4 Stacking
1HYB800001-32 Rev. A
Page 1
Circuit breakers intended for outdoor operation are generally delivered in units which
are determined for transport reasons. Intermediate storage of these units should be
avoided. If it is not possible to avoid intermediate storage, they should be stored
indoors or under a roof. They must also be stored above ground level to prevent
water damage. On arrival, it is important that plastic sheets are removed in order to
prevent corrosion by condensate water (except for the spare parts).
Storage in a humid climate without proper ventilation may lead to discoloration of the
galvanised surface. This discoloration is commonly known as “white rust”, consisting
mainly of zinc oxide and zinc hydroxide and is a result of a chemical process
between the pure zinc on the surface and moisture.
The long term corrosion protection is not influenced, since the iron-zinc layer below
the surface remains unaffected. The presence of white rust is no reason for rejection
of goods.
On arrival, each unit should be checked in the following way :
- delivery is in accordance with order and delivery documents
- any damage in delivery, and material loss
In cases where damages are detected or suspected, the units should be opened and
damages should be photographed. Both damages and shortages should be reported.
All details should be rationally stored so that they are always available. In general, all
material should be stored in an approved storage (note 1), exceptions are given in
the text below. The ambient air should not be heavily contaminated by dust, smoke,
corrosive or combustible gases, vapours or salt, otherwise the equipment has to be
cleaned before erection.
For storage the original transport unit may be used, but the plastic sheeting should
be removed. The coupling joints of the assemblies, as well as all connections, are
fitted with transport covers or protective caps which shall not be removed until
immediately before erection.
Operating mechanism (for circuit breakers)
The operating mechanism should be unpacked on arrival. If it is not going to be
stored in an approved storage (note 1), the heating elements must be connected and
supplied permanently with power to protect the control equipment from corrosion or
freezing damages.
Circuit Breakers
The breakers should be stored in their original transport unit, where they are well
protected from damages. The units shall be prevented from standing in water. The
breakers may be stored outdoors, except for the EDI-breaker, which should be stored
in an approved store. If the breakers are stored outdoors they should be covered with
a tarpaulin. (Note 1)
1HYB800001-32 Rev. A
Page 2
The tarpaulin should not be placed directly on the galvanised surface. An air gap
should be left to prevent condensation. Condensation that may occur should be self-
draining.
For the outdoor breakers, the minimum ambient temperature allowed is -300C. For the
indoor breakers, the minimum ambient temperature allowed is -50C.
Spare parts
The spare parts shall be stored indoors in an approved storage (note 1), in their
original units. This is in particular valid for rubber parts (sealings etc.), which also
have to be protected against light and sun, in order to prevent them from ageing.
Gaskets can be stored only for limited periods, so avoid storage of these parts.
Structures may be stored outdoors.
Notes 1 :
- roof
- solid ground
- relative humidity less than 50%
- temperature 20 0C (+/-100C)
1HYB800001-33 Rev. A
Contents :
1. Introduction
2. Thermal and dielectric breaking capacity
3. Chemical reactions in Circuit Breakers
4. Criteria for choice of mixed gas
5. Filling mixed gas
6. Measuring gas mixing proportions
7. Technical data for SF 6, CF4 and N2 gases
8. Safety regulations
8.1 Safety regulations for SF 6 gas
8.2 Safety regulations for CF4
8.3 Safety regulations for SF6 and CF 4 gases which
are exposed to arcs
9. Environmental effect.
1HYB800001-33 Rev. A
Page 1
1. Introduction
SF6 gas has become the predominant breaking and insulation media for circuit-
breakers of puffer and Auto-PufferTM types.
Information on characteristics and regulations for SF6 gas, N2 gas and CF4 gas is
stated in this product information.
2. Dielectric region
Figure A.
Stress on a circuit-breaker at breaking moment
Gas flow
Figure B.
Cooling SF6 arc by cold gas mixture
1HYB800001-33 Rev. A
Page 2
1. Thermal range
At current zero the hot arc channel shall be cooled down quickly to a temperature
which makes it electrically non-conductive, Figure B. Cooling capacity depends on
how quickly the current decreases towards zero, di/dt, and on the rate-of-rise of the
recovery voltage after current zero, du/dt, Figure A.
2. Dielectric range
After current zero the circuit-breaker must, for a short moment, withstand the full top
value of the transient recovery voltage without dielectric breakdown.
Breaking of terminal fault often gives low rate-of-rise of the recovery voltage and is
often a problem in the dielectric range.
SF6 is an electronegative gas of high density with good characteristics in both the
thermal and dielectric ranges.
Mixed gas filling of SF6 and N 2 gives a somewhat deteriorated thermal breaking
capacity as well as a slightly deteriorated dielectric breaking capacity compared with
only SF6 gas filling. Mixed gas filling with nitrogen often results in a reduction of
breaking capacity, e.g., a rated breaking current of 40 kA is reduced one step to 31.5
kA. The deteriorated dielectric characteristics can be compensated by nitrogen gas
filling to a slightly higher pressure than with only SF6 gas.
Mixed gas filling of SF6 and CF6 results in practically unchanged thermal and
dielectric breaking characteristics. A mixed gas filled circuit-breaker with SF 6/CF4
often retains its breaking capacity down to the lowest ambient temperature.
heat
CF3-(CF 2)N - CF3 ➞ CF 2 (1)
heat
2CF2 ➞ C + CF 4 (2)
Arc in SF 6 gas
heat
SF 6 ➞ S + 6F (3)
1HYB800001-33 Rev. A
Page 3
The carbon which is formed according to (2) reacts with fluorine atoms which are
produced according to (3) and form CF4 gas, whereby the carbon is bound and
carbonisation is avoided.
4F + C ➞ CF 4 (4)
CF 4, which is an electronegative gas, is therefore formed when the arc affects the
teflon nozzle and SF 6 gas.
Chemical reactions between gas formation and possible moisture residue on surfaces
in breaking units.
heat
SF6 + Cu ➞ SF 4 + CuF2 (8)
heat
3SF6 + W ➞ 3SF4 + WF6 (9)
Degraded gases which can appear in SF6 breakers after a number of years’ service
are SOF2, CF4, SiF 4 and SO2.
The powder which remains in the breaker poles consists of formation of fluorides.
In the gas analysis of mixed gas circuit-breakers with SF6/N2 and SF6/CF4 no other
degraded products than the above mentioned have been identified.
SF6/N2 -550C 0.36 MPa SF6+0.34 MPa N2=0.7 MPa Reduction one
breaking current step
SF 6/CF4 -550C 0.36 MPa SF6+0.34 MPa CF4=0.7 MPa Retains breaking capacity
This table is only for information. It is always the relevant product information for
respective circuit breakers which is valid.
The instrument measures the sound velocity of the gas mixture and it is calibrated for
SF6/N2 gas. The instrument shows directly on the display the volume of the SF6 part.
If the instrument is used to measure SF6/CF4 gas mixture, the result shown on the
display must be corrected according to figure C. (Example: If 51% is read on the
instrument, the SF 6 part is 0% and the CF4 part 100%)
100
SF6 (%)
In 90
SF6/CF4
80
70
60
50
40
30
20
10 DILO
0
50 60 70 80 90 100 DISPLAY
Figure C.
SF 6 part in SF6/CF4 gas as a function of
the shown result on the display of DILO 3-027.
1HYB800001-33 Rev. A
Page 5
Boiling point
at 1.013 bar 0C -63.8 -127.94 -195.8
Density
(1.013 bar 150C)kg/m3 6.25 3.74 1.185
Vapour pressure
at 00C MPa 1.26 - -
Vapour pressure
at 200C MPa 2.3 - -
Critical temperature 0C 46
8. Safety Regulations
8.1 Safety Regulations for SF 6
“SAFETY REGULATIONS FOR SULPHURHEXAFLUORIDE”
HEALTH RISK
INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.
PREVENTIVE MEASURES
Good ventilation.
Safeguard gas bottles with chains.
FIRST AID
Airing
MEASURES AT FIRE
Gas containers near the fire must be removed immediately or cooled with
water.
HEALTH RISK
INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.
PREVENTIVE MEASURES
Good ventilation.
Safeguard standing gas bottles with chains.
1HYB800001-33 Rev. A
Page 7
FIRST AID
Airing
MEASURES AT FIRE
Gas containers near the fire shall be removed immediately or cooled with
water.
8.3 Safety Regulations for SF6 and CF4 gases which are exposed to arc
HEALTH RISK
Air humidity together with degraded products can cause irritation of skin,
eyes, and mucous membranes.
INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.
Since the gas has been exposed to high temperatures degraded products,
which cause irritation, have been formed.
PREVENTIVE MEASURES
Good ventilation.
Gas from circuit-breakers can be recovered in gas treatment equipment and reused.
Fresh air mask or mask with filter against fine dust and gases with acid content.
Plastic or rubber gloves.
Overalls with long sleeves.
Vacuum cleaner with filter for fine dust.
FIRST AID
Airing
Dust and filters shall be stored sealed and handled as chemical refuse according to
local regulations.
MEASURES AT FIRE
Gas containers near the fire must be removed immediately or cooled with
water.
9. Environmental Effect
SF6 and CF4 gases can leak out into the surrounding environment due to leakage in
the circuit-breaker.
CF 4 and SF6 are very stable gases and make no detectable contribution to ozone
destruction and photochemical smog, and they have negligible influence on the green
house effect. The latter applies especially when used in circuit-breakers where, from
the global point of view, gas volumes are small.
1HYB800001-35 Rev. A
Page 1
WARNING TEXTS
Warning texts are stated in 5 different degrees of urgency which should be carefully
observed. These are described below :
DANGER indicates an immediate risk situation that can lead to death or serious
personal injury if not avoided.
DANGER
Warning indicates a risk situation that can lead to death or serious personal injury if
not avoided.
Warning
Caution indicates a risk situation that can lead to small or moderate damage.
Caution
Note Note is used when there is danger that can lead to equipment damage only.
1. Safety Regulations
When working on high-voltage circuit-breakers the below-mentioned risks must be
taken into consideration and corresponding safety measures taken.
RISK MEASURE
1. Work next to high-voltage Warning plate placed inside the door to the
operating device
2. Work on ladders and platforms The work shall follow the directions of the Authority
for occupational safety and health. Avoid work in
severe weather conditions which entails a great
deal of climbing for short periods.
3. Work with low-voltage. Do not connect control or heating voltage until all
Both D. C. and A. C. voltage may have been connection work is completed.
connected on the operating device.
4. Squeezing risk in operating device and Warning plate is placed on the supporting frame.
link system.
No work must be carried out unless the closing and
The spring operated device has energy opening springs are uncharged and the circuit-
stored in the closing spring. The opening breaker in position OFF “O” disconnect voltage to
spring, which is on the mechanism housing of the motor.
pole C1, or on every pole for one-pole
- The operating device must not be operated
operation, has energy stored. The device can
unless it is connected to the circuit-breaker
be activated by heavy vibrations or
and the electric cables are connected. The
unintentional slight touch on mechanical latch
circuit-breaker shall be filled with SF 6 gas to
parts.
a pressure of 0.7 MPa. The closing springs
should for safety reasons be uncharged
during transport and when the circuit-breaker
is off duty.
5. Work on pressurized porcelain insulators. Work close to the insulators of the circuit-breaker,
Normally, the work pressure is up to 0.7 MPa. which entails risk to damage the porcelain, must
Damage in the porcelain can cause the not be carried out until the gas pressure has been
porcelain to break, lowered to 0.125 MPa absolute pressure.
1HYB800001-35 Rev. A
Page 3
2. Unpacking
Place the case hoizontally on a flat surface before opening the cover.
Check that all parts are included in the delivery. Check-off on the accompanying
packing list.
Check that no parts have been damaged during transport, especially the porcelain
insulators.
Information
The information in this document is subject to alteration without prior notice and should not be regarded as an
undertaking from ABB Limited. ABB Limited takes no responsibility for errors that can occur in the documen-
tation.
ABB Limited is not responsible for damage incurred due to the misuse of this document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB Limited.
It may not either be imparted to third pary or otherwise be used without authorisation. Infringement hereof will
be subject to action in accordance with applicable laws.
© ABB Limited
1HYB800001-36 Rev. A
Contents
ABB Limited attempts to minimize environmental impact during the entire product’s
service life. Environment aspects are held in focus during technical and product
development. We always try to consider the eco-cycle while the material’s impact on
the environment and possibilities of recycling are observed. Manufacturing processes
are selected that are as gentle as possible on the environment.
When discarding used equipment a great deal of material and the energy content of
the material can, after sorting and cleaning, be recycled. The degree of material that
can be recycled varies depending on the technical resources and experience
available in respective countries.
1.4 SF 6-gas
The SF6-gas must be emptied before discarding a circuit-breaker. Care shall be
exercised in accordance with applicable regulations with all handling of SF 6-gas, to
prevent gas leakage. The gas can be taken care of in different ways depending on
the circumstances :
In those cases where the circuit-breaker is filled with mixed gas, the SF6-gas is
separated from the mixture for continued handling as set out above. Alternatively, the
gas mixture can be sent for destruction without being separated.
ABB Limited will willingly take care of the gas when the circuit-breaker is to be
discarded.
1HYB800001-36 Rev. A
Page 2
1.5 Porcelain
Porcelain can, after cleaning, be left for disposal or used for other purposes, for
example, as a filling material.
1.6 Electronics
1.7 Metals
Sort metals according to type and surface finish and leave at an approved recycling
company. After the removal of any paint or other surface treatment, the metal can
generally be melted down and used in new products. Many iron, steel and aluminium
parts are large and easy to identify, for example, the frame and mechanism housing.
ABB Limited aims for a reduction in the use of noble metal, or with discharge
environmentally hazardous metals. Recycling of these is extremely important.
Noble metals such as copper and silver are expensive and only occur is small
quantities in the earth’s crust. Copper is primarily used in the current paths, puffer,
contactors and cables. Silver plating of contactors can occur. Some metals can cause
damage if discharged. This applies, among others, to copper, but also to zinc and
nickel which are used sparingly in the form of surface treatment.
1.8 Plastics
Composites found in small quantities in isolators, pipes and cable glands consist of
thermosetting plastic. Thermoplastics can be found in components such as guide
rings, belts bushings and support rings. Thermoplastic in ferrules, nozzles, pipes and
collars contains fluorine and is not suitable for recycling, however, it can be disposed
of without the risk of leaking hazardous substances.
1HYB800001-36 Rev. A
Page 3
Empty oils, grease and the like before discarding and leave at an approved recycling
centre or at a recycling company. Oil waste can be separated into oil, water and
different contamination through the use of gravimetric forces. In many cases the oil
can be reused. Alternatively, the oil’s energy content can be recovered through
combustion in purpose built installations.
1.10 Rubber
Rubber can be left at an approved recycling centre either for disposal or reused for
different purpose.
CONTENTS
1. GENERAL
2. DESIGN
3 . FUNCTION
4. ERECTION
5. COMMISSIONING
6. TROUBLESHOOTING
7. MAINTENANCE
8. SPARE PARTS AND MATERIAL FOR OVERHAUL
11 APPENDIX
1HYB800001-54 Rev. A
6 TROUBLESHOOTING 13
6.1 SF 6 gas system 13
6.2 Control circuits 13
7. MAINTENANCE (OVERHAUL) 14
7.1 Maintenance Summary 15
7.2 Maintenance category A 16
7.3 Maintenance category B 17
7.4 Maintenance category C 19
7.5 Maintenance category D 24
7.6 Table of parts to be serviced 25
1HYB800001-54 Rev. A
Page 1
1 GENERAL
1.1 Validity
This document covers high-voltage circuit-breakers, type EDF SKS.
Type designation EDF SKS means that the circuit-breaker has been adapted to
synchronous coupling. The adaptation is carried out in the mechanical arm and link
system in the circuit-breaker mechanism housing, so that there is a time difference in
contact closing or contact opening.
When connecting capacitor stacks, for example, the following time differences can occur.
Generation
Outdoor design
Synchronous coupling
Circuit-breaker design
Insulation BIL Rated voltage
1 ~ 325 kV ~ 52/72.5 kV
Number of breaker chambers
1.4 Masses
Information about masses for a three-pole circuit-breaker can be found in the order
documentation and delivery documents. For internal transport, see fig. 1/2.
1.5 Storage
The circuit-breakers intended for outdoor operation are usually dismantled in suitable
units for delivery. Before erection, these units should as far as possible be stored
indoors or under roof. If the units are to be stored outdoors, they shall be blocked up so
that they do not stand in water. If the units are to be stored outdoors for a long time,
they should be covered with tarpaulins and have their heating elements switched on.
1HYB800001-54 Rev. A
Page 2
*) On this flange there is a cover which can easily be exchanged by a safety disc
unit, if the customer so wishes.
The poles are filled with SF6 gas (transport pressure) and connected to a header
block via tubes (fig. 4/la,c).
3 FUNCTION
3.1 Control and monitoring (Fig. 3/2)
The electrical principle drawing shows how the switching commands enter the control
circuit of the circuit-breaker, the monitoring units which are built in to sense any
interference which might occur, and the signals which are then triggered.
The control circuit itself can be seen in the order-related circuit diagram.
Monitoring unit:
- Gas density
The density monitor 10112 (temperature compensated pressure monitor)
monitors the insulation gas pressure in the breaker poles and sends, via its
auxiliary contactor, the signal “filling of SF6 gas” if gas losses have occurred. If
the gas pressure decreases to a value below that shown in the blocking
pressure curve, fig. 5/1, the CLOSE and OPEN operations are blocked and
simultaneously an alarm signal is given.
1HYB800001-54 Rev. A
Page 3
4 ERECTION
4.1 General
- All adjustments have been carried out in the works.
All moving parts which shall be assembled together have already been adjusted
and fixed in correct position in the works.
- Transport packing for breaker poles should be suitably kept to facilitate transport,
if necessary, at later overhaul.
- Breaker poles are filled with insulation gas Pabs. = 150 kPa (~ 1.5 bar) in order to
prevent any moisture absorption.
- Check the SF 6 gas pressure by pressing the disc of the check valve inwards
with a ø 5 pin. A distinct blow-off sound from the pole shall be heard. If there is no
blow-off sound, the pole has a leak which must be repaired.
Place frame support 10174 on the foundation. The top supporting surfaces, where the pole
beam is mounted, must be at the same level (horizontally). Screw the frame support to the
foundation. Observe tightening torque MD, fig. 2/1. The exact location is shown on the
installation layout. Observe the location of the holes for the earthing clamp (fig. 2/1).
Mount the frame 10172, with assembled poles 10171, on the support 10174 with
screw, nut and washer, 49069, 49622 and 89027. Observe the tightening torque
MD=190 Nm, fig. 4/1a:1, 2.
Place the mechanism on a wooden structure in correct position for mounting between
the frames.
- Lift up the operating mechanism by the four upper eyes, place the bolts for the
operating mechanism in the holes intended for them and fasten with enclosed
fasteners “h” (note the MD). Make sure the middle pole is not damaged by the sling.
CAUTION
During lifting the upper joint head of the connecting rod must be fitted into the fork on
the actuating lever 10154.
- However, if holes do not correspond, the operating rod length must be adjusted.
- This is done by releasing the lower fasteners “g” (fig. 4/1a) and by lowering the cubicle.
- Release locknuts “h” and “k” of the operating rod (fig. 4/1b) , turn operating rod to
adjust length. Tighten locknuts by holding the operating rod (Observe MD)
Connect the density monitor 10112, density monitor cables and pressure gauge, if
any, according to fig. 2/1, 4/1:1,2.
The assembly parts for high-voltage connections consist of screw M12 (8.8) and at
least 1 washer 13/28x3 mm, 1 locking washer 13.5/28x1.6 mm on each side of the
screw. (Observe the tightening torque MD)
1HYB800001-54 Rev. A
Page 5
5. Commissioning
All data which are checked or measured are to be entered in a commissioning record
and preserved for comparisons.
As the circuit-breaker poles are delivered vacuum processed and filled with SF6 gas
at a transport pressure of 0.150 MPa abs (200C), during commissioning only one
filling of SF6 gas is required, to top up pressure up to the filling pressure given on the
rating plate.
In the filling process the dependence of the nominal pressure on temperature (Fig. 5/
1) must definitely be taken into account. After a temperature equalization period of
approx. 1 hour, check the pressure and correct if necessary by adding or releasing
gas. Check all sealing joints on the breaker poles and the gas supply system for
leaks with a leak detector. Repair any leaks found according to chapter 6.
1HYB800001-54 Rev. A
Page 6
When the circuit-breaker is erected in a climate with temperatures below -30°C, fill
“mixed gas” instead of pure SF6.
In order to avoid condensation at temperatures below -30°C, mix the SF6 gas
with CF4 (carbon tetrafluoride) or N2 (nitrogen gas). The CF 4 gas has good breaking
capabilities, like SF6, while N2 gas often reduces the breaking capacity.
SF6/N2 25 kA 50 Hz
20 kA 60 Hz
SF6/CF4 25 kA 50 Hz
25 kA 60 Hz
The rating plate states the total filling pressure for mixed gas. The breaker poles are
delivered vacuum processed or filled to pressure 0.15 MPa abs. (20°C). When
commissioning, first fill the SF 6 gas proportion, 0.36 MPa abs. at 20°C, and there-
after N2 or CF4 proportions up to the total filling pressure according to the
rating plate.
with SF6/CF4
0.36 MPa SF6 + 0.34 MPa CF4 = 0.7 MPa abs.
When filling gas after possible leakage, refill with SF6 and N2 or CF4, respectively,
in the proportions stated above. For example, leakage to blocking level 0.6 MPa
abs. entails refilling with SF6/N2.
- spring charging indicator on the spring operated mechanism is in position “b2” (fig.
2/1) “charged”
1HYB800001-54 Rev. A
Page 7
Measure the function times. Fig. 5/2a shows the principle diagram for such a
measurement. Thereby, each breaker pole has its own measuring circuit. The time
diagram in fig. 5/2b is solely intended as an explanation of the time expression used.
- CLOSING operation (C) (fig. 5/2b) Closing time “t1. ≤ 60 ms is the time from
switching command issue to contact closing in the arcing chamber. This shall be
measured on each breaker pole.
The time differences between the poles are:
For earthed capacitor stack
Pole A1 Pole B1 Pole C1
+6.66 ms +2/-0.5 ms 3.33 ms ±1 ms 0
(after pole C1) (after pole C1).
- When the thermostat controlled additional heater is installed, check the thermostat
setting.
- Check that the safety regulations are followed. Put the circuit-breaker into service.
1HYB800001-54 Rev. A
Page 9
STORAGE YES NO
1 a Complete material is available as per packing list ?
If NO mention the shortages :
b Instruction manual available ?
c G.A. and erection drawing available ?
d Schematic drawing available ?
2 a Operating drives box stored indoor ?
b Accessories box stored indoor ?
c Was the outdoor equipment stored above HFL (Highest flood level ) ?
d Any equipment damaged during re-transportation / unloading at site ?
ERECTION YES NO
1 Is foundation and location of equipment as per G.A. drawing ?
2 STRUCTURE ERECTION
a Is length of the foundation bolts (projecting outside) sufficient to put checknuts ?
b Is there levelling nut available below structure ?
c Is the top side of the structure base plate as per G.A.. Drawing ?
d Is direction of the structure as per G.A. drawing ?
e Is the structure levelled in x , y and z axis as per G.A. drawing ?
X = Pole to pole distance (Measuring tape)
Y = Structure Height (Water tube level)
Z = Alignment of all the structures in one line (Line thread)
f Tightness of the nuts and checknuts done ?
g Are the foundation bolts filled with mortar ?
h Are the serial nos. of all the equipment matching with the serial numbers
mentioned in the packing list ?
1HYB800001-54 Rev. A
Page 10
● Lift the mechanism and fix the 04 mounting bolts with the pole beam.
● Match the Eye-bolt of the mechanism connecting rod with the lever on pole.
● Apply thin layer of grease on the pin before inserting in the eye bolt.
● After insertion of pin, tighten the locking screw with locking washers.
● Spanners
● Cloth
● Cleaning agent
REFILL ALARM
OP. BLOCK –I
OP.BLOCK – II
TIME AT WHICH CALIBRATION DONE : AM / PM
e SF6 GAS PRESSURE FILLED AFTER CALIBRATION OF DENSITY SWITCH
● SF6 gas filled in the breaker : Bar
● Temperature at which gas filled . degree C
● Time at which gas filled AM / PM
f SF6 GAS LEAKAGE TEST : YES NO
● Is Leak detector available?
● If NO , do not proceed further till leak detector is arranged.
● Is the complete SF6 gas system in the breaker (which includes pole,
gas pipes & density switch / monitor ) free from any SF6 gas leakage ?
● If NO , describe leakage found from which joints :
7 COMMISSIONING :
a Connection of density switch cables :
●Density switch cable
closing circuit terminals : &__
trip 1 circuit terminals : &__
trip 2 circuit terminals : &__
b Control coil resistance :
CLOSE COIL : W
TRIP COIL - 1 W
TRIP COIL - 2 W
c Requirement of DC control voltage in ideal condition : dc
Measured control voltage dc
SWITCH “ ON “ AC / DC supply.
d Local operation of the breaker ( electrically) :
Local closing operation OK
Local tripping operation for trip coil 1 OK
Antipumping function OK
* Open command provided directly on terminal number :
e Remote operations :
Close command given on terminal number :
Open command (T1) given on terminal number :
Open command (T2) given on terminal number :
f SPARE CONTACTS OF AUXILIARY SWITCH :
● Position of the breaker : TRIP
● Serial number of contacts found NC :
B ms
C ms
1HYB800001-54 Rev. A
Page 12
B ms
C ms
B ms
C ms
B ms
C ms
B ms
C ms
l Are insulators, operating mechanism, pole beam thoroughly cleaned and free
from dust and dirt?
* If NO , clean it thoroughly with dry cloth , before charging.
If points 1-7 as set out above have been completed, the circuit-breaker
can be commissioned.
1HYB800001-54 Rev. A
Page 13
6 Troubleshooting
Before any activity is started, the circuit breaker has to be isolated from the high-
voltage system and earthed according to regulations. The control and heating
currents are to be interrupted.
7. Inspection intervals
Important checkpoints, acceptable tolerances, certain functional values for
adjustments, and recommended inspection intervals can be found in the following
inspection chart.
In corrosive or polluted air and in climates with a high relative humidity, it can be
necessary to halve the inspection intervals.
Condition of Com-
Explan- circuit- petence
Type of measure Inspection interval
ation breaker require-
during work ments
A Ocular inspection 1-2 years a1 a2
B Preventive maintenance
Intermediate inspection
• Operation testing including 3-6 years, 2 000 mech. 1) b1 b2
time checks oper.
• Heat measurements
Explanation:
1) Mech. oper. =Mechanical Close-Open operations.
2) El. oper.= Close-Open operations with electrical load
3) Special demands on resistance inspections for circuit-breakers operated
> 100 Close and Open operations/year.
1HYB800001-54 Rev. A
Page 16
Competence requirements :
a2) Substation personnel with no special training.
b2) Personnel authorised by ABB to carry out assembly, commissioning and
maintenance work.
c2) Personnel authorised by ABB to carry out assembly, commissioning and
maintenance work. In certain cases, with instructions from ABB.
7
1HYB800001-54 Rev. A
Page 17
7
1HYB800001-54 Rev. A
Page 20
1HYB800001-54 Rev. A
Page 21
1HYB800001-54 Rev. A
Page 22
1HYB800001-54 Rev. A
Page 23
1HYB800001-54 Rev. A
Page 24
4
1HYB800001-54 Rev. A
Page 25
- Set of hexagon sockets 5-10 mm ((connection 3/8") and special tools, jigs and
fixtures as per fig 7/2b.
In principle, all sealing units, spring washers and locking rings which are dismantled
during maintenance work shall be replaced by new such parts.
- Operate the circuit-breaker to position “b1” (uncharged and position OPEN) (fig. 2/1).
- Open the disconnectors on both sides of the circuit-breaker.
- Switch off control, signal, motor, and heating voltages.
Loosen the fastening bolts of the gas system so that it can be moved lengthwise.
Remove the cap nuts on the check valves so that the groove in its threads is
visible. Move the gas tube as far as possible to the side so that it comes against the
cap nut. In this position, all three check valves are closed and the cap nuts can be
completely loosened while moving the tube system further to the side.
- Fasten lifting ropes under the upper flange of the breaker chamber insulator and
tension them slightly. Remove screw, washer and nut, 49621, 49063, 89026 (fig. 4/
1a:1,2).
- Move out the breaker poles to the side. Thereby, the coupling shaft 10005 (fig. 4/
1:1,2) slides out of its coupling sleeve 10180. Transport the breaker poles to the
assembly shop and place them on an assembly block (supplied by the customer).
1HYB800001-54 Rev. A
Page 27
- Fasten the lifting rope under the flange and tension it slightly. Remove screw,
washer and nut, 49621, 49063, 89026.
- Lift the breaker pole upwards and transport it to the assembly shop.
- Parts from the various poles must not be interchanged. This is important since
parts in the arm and link systems are not identical.
The following description applies for pole B1, shown in fig. 7/2a:2. All poles are
disassembled in the same way.
- Place the breaker pole on the assembly table. Fastening points are the post and
breaker chamber insulator’s upper flanges and the adapter plate 10098.
Remove screws 49756/2 and the washers 89026/1 and lift the cover 10056/1.
Then lift out the desiccant container. Treat this according to prevailing local
regulations.
Remove screw, nut and washers 49756, 49621/2, 89026/2, and carefully lift off the
flange 10099/2 with the fixed contact.
- Place the flange on a sturdy base taking care of the O-ring groove.
- Support the mechanism housing, included in the link gear 10185/2, with a suitable
wooden base. Unscrew and pull it out as far as possible.
- Hold firmly the socket of the operating insulator 10042/2 with wrench SW28, loosen
the locking nuts 49695/1, 49586, and turn the set screw 10041/2, until the operating
insulator socket 10042/2 and the linkage joint 10043/2, are free. Take out the
mechanism housing completely. Remove O-rings 10038/3 and 10038/4.
- Disassemble the screw joint which holds together the support and breaker
chamber insulator, with the intermediate connector flanges (49333, 49621, 89026/
2) Lift off the breaker chamber insulator 10106
- Now lift off the moving contact and place it on a wooden base.
- Remove the pin 10050 and operating insulator socket 10042/2 from the operating
insulator 10049.
- Thread off the set screw in 10051 with its locking nut 49505 from adjusting ring
10053.
- Knock out the flow direction tube base with dismantling rod and adapter 00104 (fig.
7/2b). Remove pin 10029.
1HYB800001-54 Rev. A
Page 28
- Do not damage the sealing surfaces on the insulators and mechanism housing. Be
careful also with the O-ring grooves in the flanges.
7.11.4 Cleaning
- Treat the contact surfaces of the fixed contact pins with polishing cloth and grease
“N”, and the contact fingers with grease “N’ but no polishing cloth.
- Screw the fixed contact pin 10056 with hexagon wrench 00103 (fig. 7/2b) and
secure with locking fluid “B” (see 1HYB800001-29). Observe the tightening torque.
NOTE
Only the last two threads of the fixed contact holder 10097 are to be treated with
locking fluid. There must be no locking fluid on the contact surfaces, see fig. 7/3, 2*).
1HYB800001-54 Rev. A
Page 29
Slide the finger cage 10058 over the fixed contact holder 10097 up to 15 mm
before the end position. Insert fingers 10059, including springs, and then push the
finger cage to the end position. Screw in the countersunk screws 10057 and
secure with locking fluid “B”. NOTE: Only on the last four threads. Observe the
tightening torque.
- Screw the assembled contact 10030 to the connection flange and do not forget to
lubricate the contact surface at 3*) (fig. 7/3) with grease “N”.
NOTE
- Clamp the piston 10060 in wooden jaws or prisms.
- Treat the fixed contact surfaces on erosion finger and piston with polishing cloth
and grease “N”, 2*.
- Mount the erosion finger 10068 by special wrench 00102 (fig. 7/2b) and secure
with locking fluid “B”. Observe the tightening torque.
Apply fluid “E” on the thread on sleeve 10067. Mount by hand and secure with
locking fluid “C”.
Note
Only the last thread shall be treated with locking liquid (fig. 7/4, *).
Remember to remove the inside catch piece of the special wrench 00102.
- Clean and grease the fixed contact surfaces between the contact ring 10065
and piston 10060 with grease “N”. Mount the contact ring, including insulating
nozzle 10066, screw and washer, 49318, 10064, on the piston. Observe the
tightening torque and locking.
- Mount the piston base 10062 with torque wrench 00106 (fig. 7/2b) and secure with
locking fluid “B “
NOTE
Apply locking agent to the last two threads only.
- Replace cylinder guide rind 10077 in the cylinder base 10070, piston guide rinds
10073, and multi-contact rings 10074 in the piston 10060. Observe, when doing so,
the direction of the multi-contact firings.
- Clean and grease the moving contact surface on cylinder 10076 and the piston in
the area of the multi-contact rings with grease “N”, see 2*) (fig. 7/4).
- Insert carefully the assembled middle part into cylinder 10076 and flow direction
tube 10061, in cylinder base 10070. Note that there shall be an angle of 90° between
the flow direction tube window and the cylinder base window. Thereby, the middle part
must not be turned, but if so happens only in the direction of the arrow.
- Mount the long screws 10069, with pressure relief flap 10071 and compression
springs 10072. Secure with locking fluid “B”. Observe the tightening torque.
1HYB800001-54 Rev. A
Page 30
- Remove screw and washer 49705 and 89025, or 49701 and 89154, with shaft
guard 10179 , and disassemble completely. Pull out the crankshaft 10083 and
lever 10084/2 with linkage joint 10085/2. Unscrew socket head screw 10086
with washers 10088 and 89004, and pull out the joint pin 10087.
O-ring 10090.
X-ring10081
Sealing ring 10182
- Clean the metal parts that are not changed. Reassemble in reverse order. Grease
X-rings 10081 with grease “S”and sealing ring 10182, pack with grease “G” (Mobile
Grease 28). Be careful that the sealing rings are not damaged by the splines.
Apply grease “G” on joint pin 10087.
NOTE
For the relative positions of the punch marks, see “e” in fig. 7/5:2. Apply
grease (fluor-silicone grease) “S” on the outer diameter “c” and assembly surface
“a” on shaft guard 10179 10179.
- Place the snap ring 10055 in the groove on the flow direction tube base 10054.
- Push in the flow direction tube base 10054 and retaining ring 10055 so far into the
flow direction tube 10061 that the pin 10029 can be inserted.
- Slide the operating insulator 10049 with screen 10095 over the flow direction tube.
Insert pin 10029 so that the bore in the bolt is in line with the centre-line of
the operating insulator. Insert the flow direction tube base 10054 through the
bore in pin 10029 until it reaches stop. Check that the rear blow-off hole is com-
pletely open.
- Place the ring 10053 so that the set screw 10051 can be screwed into the bore in
the flow direction tube 10061. Insert set screw 10051, tighten lock nut 49505 and
secure with locking fluid “B”. Observe the tightening torque.
- Assemble the operating insulator socket 10042 and pin 10050 on the operating
insulator. At this assembly the bore in the pin must be in line with the centre-line
of the operating insulator.
- Clean the contact surface on the terminal flange. Rub the fixed contact surface on
the cylinder base with a polishing cloth. Apply grease “N” on the rubbed surfaces.
Mount with screw and washers, 49332, 10047 and 89006/1, and secure with
locking fluid “B”. Observe the tightening torque.
- Apply grease “N”, Fomblin, on the marked moving contact surface of contact ring
10065 (fig. 7/4).
1HYB800001-54 Rev. A
Page 31
- Apply grease “S”, fluor-silicone grease on 0-rings 10038/1 and 10038/2 and the
grooves for the terminal flanges 10108. Place the O-rings in the grooves.
- Place the breaker chamber insulator on the flange and thereby try to locate the
moving contact as far as possible in the middle of the insulator.
Place the post insulator over the operating insulator and screw both the insulators
to the flange with screw, nut and washers, 49333, 49621 and 89026/3 (fig. 7/2a:2)
- Apply grease “S” on the O-rings and the groove for these in the adapter plate, and
put the O-rings in the groove.
- Screw the adapter plate against the flange on the post insulator with screw and
washer, 49726/1 and 89026/1.
- Place the depth gauge 00109 on the flange 10016 of the breaker chamber
insulator. Push the operating insulator 10049 upwards to stop. Place the straight
edge 00114 on the lower insulator flange. Measure the “X” measurement.
The setting values of the two remaining poles are measured in the same manner but
the calculation formula for the measurement “A” is:
At unearthed capacitor stack, the circuit-breaker consists of one pole marked A1(Fig.
7/2a:1), and two poles, marked B1 and C1 (7/2a:3). B1 and C1 have the same setting
value A.
For assembly of the complete fixed contact 10030, see fig. 7/2a:2.
- Apply grease “S” in the 0-ring groove on the upper terminal flange 10099/2 and the
two O-rings, before placing them in the groove.
- Now mount the contact 10030 with flange on the upper flange of the breaker
chamber insulator and try to place the contact as far as possible in the middle of
the insulator. Use screw, washers and nut, 49756, 49621/2 and 89026/2.Observe
tightening torque 79 Nm.
- Install the desiccant container filled with desiccant (see fig. 7/2a:1,2,3).
- Finally, treat the O-rings and groove on the upper connection flange with grease
“S” and mount the cover 10056/1 with screw and washer 49756/2 and 89026/2.
(MD = 45 Nm).
- Apply “S” grease in the O-ring groove of the adapter plate and on the O-rings.
Place the O-rings in their grooves.
1HYB800001-54 Rev. A
Page 32
- Place the link gear 10185/2 at a distance of 50 mm in front of the lower flange on
the post insulator.
- Place the adjusting screw 10041/2 (with only one tightening turn), with hexagon
nuts 49586 and 49695 fully backed off on their threads, on the operating insulator
socket 10042/2 and the linkage joint 10043/2.
- Tighten the adjusting screw 10041/2 to the measurement “A” by means of pre-set
compass 00115, according to fig. 7/2c:2, and secure on both sides with locking
fluid “B”. Observe the tightening torque.
- Mount the link gear 10185/2 with hexagon nuts 49621/2 and 89026/2 and secure
as above. Observe the tightening torque 79 Nm.
- Filling gas :
After the circuit-breaker has been dismantled for overhaul or repair it shall (before
trial switching operation) be filled with SF6.
Evacuate down to the pressure 1 mbar and continue to pump at least one hour
after that pressure has been reached.
Stop evacuating and fill the circuit-breaker with dry and pure nitrogen gas to the
atmospheric pressure. Let it stand two hours at this pressure.
Evacuate again to 1 mbar and fill with pure SF6 gas to 0.15 MPa abs. Observe
thereby the safety regulations for gas filling.
- Set the outer poles in OPEN position and push them from the outside with
coupling sleeves as far as possible over the coupling shafts. Insert the hexagon
screws 49063, fit the nuts 49621 and spacers 89026, and then tighten after
adjusting the breaker poles into correct position. The joint heads on the connecting
rod must be moveable, and the coupling shafts must be moveable axially.
- Apply grease “G” (Mobile Grease 28, see 1*), (fig. 4/lc), on the flange surfaces of
the gas nipples.
Clean the gas system by blowing SF6, gas via the. header block for approx. 3 min.
Allow the gas to continue to flow while the system is connected to the check
valves of the mechanism housing, according to fig. 4/1c. Screw on all cap
nuts up to the groove. Then tighten all cap nuts fully while moving the com-
plete tube system to the side. Lock all fastening bolts. If the connections of the
gas system to the header block have been dismantled, they shall be secured
with locking fluid “B” when re-installed. Observe the tightening torque 45 Nm.
Fill with pure gas to normal working pressure 0.7 MPa abs. After conclusion of
gas treatment, fit the nut and , O-ring L10112/c.
1HYB800001-54 Rev. A
Page 33
- Clean and grease sparingly the transfer cam disc “B”, latches “C” and “D”, levers
“E” and “F”. Use grease “G”.
- After 5000 switching cycles, the spring operating mechanism shall be overhauled.
Contact ABB.
8. Spare parts
8.1 General
8.1.1 Important notes
- Replace all uncovered sealing rings of the insulating gas space.
- Unpacking : shortly before use.
8.1.2 Ordering of spare parts
For ordering, the following data are essential :
- Order no 1......... See order documentation
- Type designation See nameplate
- Serial number See nameplate
- Publication number See end paper
- Part number See spare parts list
- Part designation See spare parts list
1 2 3
11. Appendix
11.1 Figures
Fig. Designation
1/1 Nameplate
1/2 Tabulated masses
2/1 Circuit breaker
3/1a:1,2,3 Breaker Pole (“OPEN” Position)
3/1b:1,2,3 Breaker Pole (“CLOSED” position)
3/2 Schematic control diagram
4/1a:1,2 Circuit breaker, complete
4/1b Connecting rod securement
4/1c SF6 gas line
4/1d Gas filling with SF6
4/2 Transport instructions
5/1 SF6 filling pressure diagram
5/2a Measurement layout for function tests
5/2b Simultaneity monitoring
7/1 Admissible switching cycles for contact overhaul
7/2a:1,2,3 Breaker pole, complete
7/2b Tools and overhaul tools
7/2c:1,2,3 Length adjustment of moving contact
7/3 Fixed contact
7/4 Moving contact
7/5:1,2,3 Link Gear
7/6 Spring stored-energy actuator
1HYB800001-54 Rev. A
Page 38
Fig. 1/1
1HYB800001-54 Rev. A
Page 39
Type EDF
Mass per citruit breaker (net)
kg lb
Fig. 1/2
1HYB800001-54 Rev. A
Page 40
10173 Control cubicle with stored-energy spring operating mechanism and connecting rod
10174 Support
b1 Breaker position “OPEN” and springs untensioned (not ready for switching)
b3 Breaker position “CLOSED” and springs tensioned (ready for O-CO Switching)
C Earthing connection
Fig. 2/1
1HYB800001-54 Rev. A
Page 42
10017 Cover
10099
10106
10030
10165 k-l
g-h
10013
O C
10108
10171
10049
10157
10041/1
10098
10185/1
10017 Cover
10099
10106
10030
10165 k-l
g-h
10013
O C
10108
10171
10049
10157
10041/2
10098
10185/2
10017 Cover
10099
10106
10030
10165
k-l
g-h
10013
O C
10108
10171
10049
10157
10041/3
10098
10185/3
1) Remote control
10171 10171
10171
S13
Fig. 3/2
1HYB800001-54 Rev. A
Page 50
Nm ft. lbf
13 10
45 33
79 58
190 141
Installation of breaker poles with grounded capacitor bank
A1, B1 and C1 are markings of
Fig 7/2a:1 Fig 7/2a:2 Fig 7/2a:3
respective pole mechanisms
A1 B1 C1
49705
D 89025
MD=79Nm MD=38 Nm
10176
10179
49701
10126 89154
10183
g g
10174
C
OPE
A-A
*) Rotation by 1800
Fig. 4/1a:1
1HYB800001-54 Rev. A
Page 52
Nm ft. lbf
13 10
45 33
79 58
190 141
Installation of breaker poles with ungrounded capacitor bank
A1, B1 and C1 are markings
Fig 7/2a:1 Fig 7/2a:3 Fig 7/2a:3 respective pole mechanisms
A1 B1 C1
49705
D 89025
MD=79Nm MD=38 Nm
10176
10179
E
10154 10005 49063
L10177/a 49621
10112 89026
E MD=79Nm
h
MD=190Nm 10118
F
10161
10180 10182 1
L10177/b
L10178
f
49069
49622
89027
10173
E
49701
89154
10126 10183
g g
10174
A-A
*) Rotation by 1800
Fig. 4/1a:2
1HYB800001-54 Rev. A
Page 54
10064 Lockwasher
10083 Crankshaft
89224 Washer
c Installation location
d Rubber collar *)
e Clamp *)
h,k Locknuts
MD Torque
Nm ft. lbf
6 4
c=360
h
Fig. 4/1b
1HYB800001-54 Rev. A
Page 56
L 00111 Washer
L 10112/b Manometer *)
*) At request of customer
Mobil Grease 28
Fig. 4/1c
1HYB800001-54 Rev. A
Page 58
2 Coupling
3 Regulator
4 Coupling
5 Gas Valve
7 Density Switch
8 Gas Valve
9 Pressure Gauge
Fig. 4/1d
1HYB800001-54 Rev. A
Page 60
a Supporting timber
Fig. 4/2
1HYB800001-54 Rev. A
Page 62
Conversion of :
Pabs (kPa) to Pe (gauge) lbf/in2
Pabs - 100 x 0.145 (kPa) = Pe (gauge) lbf/in2
➤
Pabs Pabs
1000
9 130.5 900 1
8 116 800
2
7 101.5 700 3
6 87 600
5 72.5 500
4 58 400 4
3 43.5 300
2 29.0 200
100
0
-30 -20 -5 0 10 20 30 40 50 60 70 80
Pabs t0C
kPa -30 -20 -5 0 10 20 30 40 50 60 70 80
1 500 580 625 640 670 700 730 760 790 820 850 880
2 490 520 555 570 590 620 650 670 700 730 750 770
3 470 500 540 550 580 600 630 650 680 700 720 750
4 290 300 330 340 350 360 370 380 400 420 430 440
Pabs t0C
bar -30 -20 -5 0 10 20 30 40 50 60 70 80
1 5.0 5.8 6.2 6.4 6.7 7.0 7.3 7.6 7.9 8.2 8.5 8.8
2 4.9 5.2 5.6 5.7 5.9 6.2 6.5 6.7 7.0 7.3 7.5 7.7
3 4.7 5.0 5.4 5.5 5.8 6.0 6.3 6.5 6.8 7.0 7.2 7.5
4 2.9 3.0 3.3 3.4 3.5 3.6 3.7 3.8 4.0 4.2 4.3 4.4
Pabs t0C / F
lbf/in2 -30/-22 -20/-4 -5/23 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158 80/176
1 72.5 84.1 90.7 92.3 97.2 101.5 105.9 110.2 114.5 118.9 123.3 127.6
2 71.1 75.4 80.5 82.7 85.6 89.9 94.3 97.2 101.5 105.9 108.8 111.2
3 68.2 72.5 78.4 79.3 84.1 87.0 91.4 94.3 98.6 101.5 104.4 108.8
4 42.1 43.5 47.9 49.3 50.8 52.2 53.7 55.1 58.0 60.9 62.4 63.8
Fig. 5/1
1HYB800001-54 Rev. A
Page 64
Y1 Coil CLOSE
Q Auxiliary switch
M1 Time recorder
K1 Terminal 1 on M3
K2 Terminal 2 on M3
UM Measurement voltage
US Control Voltage
C CLOSED
O OPEN
I Coil current
t1 Closing time
t2 Opening time
t3 Close-open time
Fig. 5/2b
Fig. 5/2a,b
1HYB800001-54 Rev. A
Page 66
I Breaking current
10016 49621/2
10045
10030
10106
10013
10054
10171 10061
10055
10038/1
10038/2
10108
49333 10053
89026/2 10051
49621 49505
M D =79Nm 10029
10095
89006/1
10047
49332 10049
MD =40Nm
10050
10042/1
10038/1
49695/1 10038/2
10041/1 49726/1
49586
89026/2
10098
49726/2 10038/4
89026/2 10038/3
10043/1 49621/2
89026/2
10185/1
10172
Fig. 7/2a:1
1HYB800001-54 Rev. A
Page 70
Nm ft. lbf
6 4
20 15
45 33
79 58
10056/1
49756/2 10038/1
89006/2 10038/2
49756
10099/2 89026/2
49621/2
10016
10045
10030
10106
10013
10054
10171 10061
10055
10038/1
10038/2
10108
49333 10053
89026/2 10051
49621 49505
M D =79Nm 10029
10095
89006/1
10047
49332 10049
MD=40Nm
10050
10042/2
10038/1
49695/1 10038/2
10041/2 49726/1
49586
89026/2
10098
49726/2 10038/4
89026/2 10038/3
10043/2 49621/2
89026/2
10185/2
10172
Fig. 7/2a:2
1HYB800001-54 Rev. A
Page 72
Nm ft. lbf
6 4
20 15
45 33
79 58
10056/1
49756/2 10038/1
89006/2 10038/2
49756
10099/2 89026/2
49621/2
10016
10045
10030
10106
10013
10054
10171 10061
10055
10038/1
10038/2
10108
49333 10053
89026/2 10051
49621 49505
MD=79Nm 10029
10095
89006/1
10047
49332 10049
MD=40Nm
10050
10042/3
10038/1
49695/1 10038/2
10041/3
49726/1
49586
89026/2
10098
49726/2 10038/4
89026/2 10038/3
10043/3 49621/2
89026/2
10185/3
10172
Fig. 7/2a:3
1HYB800001-54 Rev. A
Page 74
00115 Compass
89026/2 Washer
89026/3 Washer
A Setting dimension x-29 mm=A (~51.5) for compass 00115 (Fig. 7/2b)
mm in
50 1.97
10049 X
10016 d
49756
89026/2/3
49621
001
00109
10185/1
10043/1
A
10042/1
Fig. 7/2c:1
1HYB800001-54 Rev. A
Page 78
89026/2 Washer
89026/3 Washer
A Setting dimension x+32.5 mm=A (~45.5) for compass 00115 (Fig. 7/2b)
mm in
50 1.97
10049 X
10016 d
49756
89026/2/3
49621
0
00109
10185/2
A 10043/2
10042/2
Fig. 7/2c:2
1HYB800001-54 Rev. A
Page 80
89026/2 Washer
89026/3 Washer
A Setting dimension x-14 mm=A (~66.5) for compass 00115 (Fig. 7/2b)
mm in
50 1.97
10049 X
10016 d
49756
89026/2/3
49621
00109
10043/3 10185/3
A
10042/3
Fig. 7/2c:3
1HYB800001-54 Rev. A
Page 82
89006/2 Washer
MD Torque
Nm ft. lbf
6 4
26 19
49 36
10099/2
10097
10059
Fig. 7/3
1HYB800001-54 Rev. A
Page 84
Nm ft. lbf
6 4
11 8
79 58
Fig. 7/4
1HYB800001-54 Rev. A
Page 86
10081 X-ring
10083 Crankshaft
10084/1 Lever
10088 Washer
10183 Cover
89004 Washer
89025 Washer
89154 Washer
MD Torque
Nm ft. lbf
6 4
45 33
110 81
10185 e
49705
b 89025
MD=45Nm
10090 10081
10183
10080
10182
10083
C
89154
49701 00112
10092
10091
d
Fig. 7/5:1
1HYB800001-54 Rev. A
Page 88
10081 X-ring
10083 Crankshaft
10084/2 Lever
10088 Washer
10183 Cover
89004 Washer
89025 Washer
89154 Washer
MD Torque
Nm ft. lbf
6 4
45 33
110 81
10185 e
49705
89025
b MD=45Nm
10090 10081
10183
10080
a
10182
10083
C
89154
49701 00112
d 10092
10091
Fig. 7/5:2
1HYB800001-54 Rev. A
Page 90
10081 X-ring
10083 Crankshaft
10084/3 Lever
10088 Washer
10183 Cover
89004 Washer
89025 Washer
89154 Washer
MD Torque
Nm ft. lbf
6 4
45 33
110 81
10185 e
49705
b 89025
MD=45Nm
10090 10081
10183
10080
10182
10083
C
89154
49701 00112
10092
10091
d
Fig. 7/5:3
1HYB800001-54 Rev. A
Page 92
A Transmission roller
B Transmission cam
C Locking pawl
D Locking pawl
E Level
F Lever
G Worm wheel
H Worm
Fig. 7/6
1HYB800001-38 Rev. A
Contents :
1. General
2. Construction
3. Function
4. Erection
5. Commissioning
6. Maintenance
7. Spare Parts
8. Appendix
1HYB800001-38 Rev. A
Page 1
Contents Page
1. GENERAL 1
1.1 Validity 1
1.2 Specification 1
1.3 Masses 1
2. CONSTRUCTION 1
2.1 Operating mechanism cubicle 1
2.2 Drive mechanics 1
2.3 Driving units 2
2.4 Electrical components 3
3. FUNCTION 3
3.1 Functions of the basic mechanism 3
3.2 Charging the closing spring 3
3.3 Closing - operation 4
3.4 Opening - operation 5
4. ERECTION 5
4.1 Delivery 5
4.2 Installation 5
5. COMMISSIONING 5
5.1 Function tests 5
5.1.1 Manual operation 5
5.1.2 Motor operation 5
6 MAINTENANCE (Overhaul) 6
6.1 Duty-related overhaul 6
7 SPARE PARTS 7
7.1 Storage instructions 7
7.2 Spare parts list 7
8 APPENDIX 8
8.1 Figures 8
1HYB800001-38 Rev. A
Page 2
1. General
1.1 Validity
1.2 Specifications
Specifications are contained in the order documentation and on the rating plate.
1.3 Masses
The masses (kg/lb) can be obtained from the order documentation and the shipping
documents. For internal transport and assembly see the instructions for erection and
operation of the circuit breaker, Fig. 1/2
2. Construction
The stored-energy spring operating mechanism comprises the following main parts :
In the operating mechanism FSA 1 (outdoor), the electrical components and the
basic mechanism are placed in the operating mechanism cubicle EV 11851.
There is a door with an inspection window for reading the position indicator
EV11825 and the spring charge indicator EV11824 on the operating mechanism
front. The door can be locked with a padlock. When the door is opened, the
electrical panel with its electrical components becomes accessible and the hand
crank can be inserted.
The operating mechanism cubicle is designed so that the basic mechanism and the
electrical components are hermetically protected against the effects of the weather.
The outdoor circuit breaker type EDF has the cubicle mounted below the pole
beams of the breaker. The connecting rod projects upwards.
1HYB800001-38 Rev. A
Page 3
- Lever EV 11848 is located on the output shaft and when it rotates, it transmits
the rotary movement to the connecting rod.
In the mechanism type FSA 1, the electrical control and monitoring elements
necessary for the control of the circuit breaker are additionally arranged on the
switchgear panel.
If the operating mechanism is to be stored outdoors for periods longer than four
weeks, the heater should be connected.
1HYB800001-38 Rev. A
Page 4
3. Function
3.1 Function of the basic mechanism (Fig. 7/1)
- The main shaft EV 11815 serves as the drive shaft for charging the closing spring.
- By means of lever EV 11848, the output shaft EV 11816 transmits the closing
or opening movement to the connecting rod, and hence to the circuit breaker.
- The motor EV 11843 with reducer gear EV 11842 charges the operating
mechanism mechanically (tensions the closing spring). The motor limit switch,
EV 11826, opens when the closing spring is tensioned.
- Hand crank EV 11812 (FSA 1) is used to charge the closing springs by hand
(e.g. on power failure).
- On discharging, opening spring EV 11814 release uses the energy to open the
breaker.
- Closing unit EV 11811 holds the closing spring in the charged condition or it
releases it on command electrically via the CLOSE magnet coil or
mechanically (by hand).
- Opening unit EV 11810 holds the opening spring in the charged condition or
releases it on command electrically via the OPEN magnet coil or mechanically
(by hand).
As an emergency charging feature the closing spring EV 11813 is charged with hand
crank EV 11812 via bevel gear EV 11818 and worm gear EV 11819 by turning the
main shaft EV 11815. The main shaft EV 11815 is turned via worm wheel and pull
hook EV 11830 which engages the coupling ring EV 11829.
For charging the closing spring approx. 30 rotations of the hand crank are necessary.
On a 1800 rotation the crank EV 11828 runs through top dead center.
The pawl on the control disk EV 11820 is held by lever EV 11832, and the blocking
hook EV 11834 of the closing unit.
The switching cam of crank EV 11828 simultaneously reaches the motor limit switch
EV 11826 and cam follower lever EV 11827 is lifted.
The following functions are thereby initiated :
- Turning off the power supply to the motor by the motor limit switch.
- Preparation of the closing operation by the motor limit switch.
- Spring charge indicator indicates “Spring charged”.
Time necessary for charging the spring at nominal tension : < 15 seconds.
When the engagement lever EV 11837 or the closing coil EV 11839 are actuated by
hand or electrically, the lever 11832 and the blocking hook EV 11834 of the closing
unit release the control disk pawl EV 11820.
By releasing the closing spring EV 11813, the main shaft EV 11815 rotates in the
direction shown on fig. 7/1 and in turn the control disk EV 11820 transmits the
rotational movement to the cam follower EV 11836 and operating lever EV 11835.
The output shaft EV 11816 is thereby rotated and the circuit breaker is closed via
operating lever EV 11848 and connecting rod compl. EV 11780/EV 11822.
Simultaneously, opening spring EV 11814 is charged.
When the output shaft has rotated by 60 o, the control disk pawl passes over the cam
follower EV 11836 and then the output shaft is released and can rotate in the
opposite direction.
However, this is not possible as long as holding cam EV 11847 is held by lever EV
11832 and blocking hook EV 11834 of the opening unit. The closing spring EV
11813 is automatically recharged again.
At power failure the closing spring can be recharged by hand with hand crank EV
11812 (FSA 1).
In this position the following indications are visible :
- Position indicator : “I” (circuit breaker in closed position)
- Spring charge indicator : “Spring charged”
1HYB800001-38 Rev. A
Page 6
The operating mechanism is ready for another rapid closing operation but the
interlock hook EV 11833 prevents the execution of a closing operation, while the
circuit breaker is closed. Both springs (EV 11813 and EV 11814) remain charged
and both shafts are blocked by the two blocking units (EV 111810 and EV 11811).
4. Erection
4.1 Delivery
Each circuit breaker is delivered with its corresponding operating mechanism which
is packed separately or already mounted on the circuit breaker pole beams. At
delivery, both springs are uncharged and the circuit breaker is in open position.
The operating mechanism must be mounted on the circuit breaker according to the
instruction for erection and operation of the circuit breaker.
Never operate the operating mechanism if it is not connected to the circuit breaker (filled
with SF6-gas to 0.7 MPa) and the electrical connecting lines are not connected.
5. Commissioning
5.1 Function tests
Function tests are performed after the commissioning work and immediately before
the circuit breaker is taken into service, as well as after overhaul work.
Function tests may only be performed with the circuit breaker disconnected from the
high-voltage system and filled with SF6-gas to 0.7 MPa (abs).
5.1.1 Manual operation
For this purpose hand crank EV 11812 is used for charging the closing spring. When
the closing spring has reached the desired tension, it automatically uncouples the
pull hook (EV 11830) of the main shaft, thereby releasing the hand crank.
During these trial switching operations, the position indicators (EV 11824 and EV
11825) and the counter must be tested for proper functioning.
1HYB800001-38 Rev. A
Page 7
The motor should be turned on only after the hand crank has been removed, even
though it is uncoupled automatically when the motor is started.
The charging of the closing springs starts as soon as the motor supply is switched
on. The supply of power to the motor is turned off automatically (by microswitch EV
11826) when the closing spring is adequately charged.
- Proper functioning of the operation mechanism should be tested by several
CLOSE and OPEN switching operations.
- Also a test for correct functioning of the selector switch LOCAL-REMOTE
should be performed.
- Motor running time for charging springs at rated voltage : < 15 seconds.
6. Maintenance
6.1 Duty-related overhaul (Fig. 7/1)
After 2000 CO Switching operations, the following parts must be cleaned and
lubricated without being disassembled :
- Cam follower EV 11836 with roller shaft, greased with grease G, (Mobile
Grease 28*)
- Worm gearing EV 11819 (worm and worm wheel), grease G (Mobile Grease 28)
- Rollers of levers EV 11832 of closing and opening units, grease L (Aseol
Sylitea 4-018)
Clean and lubricate the machined surfaces of the following cams :
- Control disk with pawl EV 11820, grease L (Aseol Sylitea 4-108)
- Holding cam EV 11847, grease L (Aseol sylitea 4-108)
Treat the worm surfaces of the following pins or cranks with :
- Crank pin EV 11853, grease L (Aseol sylitea 4-108)
- Spring fixation pin EV 11856, grease L(Aseol sylitea 4-108)
- Spring fixation pin EV 11857, grease L(Aseol sylitea 4-108)
- Crank with switching cams EV 11828, grease L(Aseol sylitea 4-108)
Change the following details of the connection rod if required (Fig. 2/2):
- Rod end joint EV 11858 or EV 11782 (in case of obvious wear)
- Bellows EV11781 when there are cracks in material, leaks.
No work is allowed to be carried out until the closing and opening springs are
discharged, and the circuit breaker is in the OPEN “O” position. The power to the
motor must be disconnected.
*As an alternative to Mobile Grease 28, Molykote Long term 2 plus or Aseol Sylitea
4-108 may be used.
1HYB800001-38 Rev. A
Page 8
7. Spare parts
For ordering, the following data are essential :
- Order number See order documentation
- Type designation See rating plate
- Serial number See rating plate
- Publication number See spare parts list
- Part number See spare parts list
- Design Outdoor
- Part designation See spare parts list
Reserve parts :
8 Appendix
8.1 Figures
Fig. Title
Fig. 2/1
1HYB800001-38 Rev. A
Page 13
ABB Ltd.
Maneja, Vadodara
Gujarat, (INDIA)
Tel. : +91 265 2642141
Fax : +91 265 2638918, 2638911
visit us at : www.abb.com