VRV Heat Recovery Systems: Application and Sales Guide
VRV Heat Recovery Systems: Application and Sales Guide
Top secret
Secret
Internal use only
Public
1
6/8/2016
2
6/8/2016
This is the
condenser
3
6/8/2016
The ability to transfer heat between different zones can be very useful:
• … when cooling technical rooms (servers, UPS, …) in the autumn, winter and spring
• … when the south façade is being heated by the sun, but in the shade it’s still cold
• … when a room is occupied by so many persons, that cooling is required even though in
the neighboring room you’re heating
• … you can use the system for cooling during summer and at the same time prepare
sanitary hot water
• … during mid-season in the hotels, where some guests are cold, some are hot
4
6/8/2016
Strasbourg
Athens
APPLICATION EXAMPLE
Requirements:
• Cooling for restaurants, kitchens, gyms
• Cooling or heating for guest rooms
• Sanitary hot water
• Air curtains
• Fresh air supply
5
6/8/2016
APPLICATION EXAMPLE
Cooling and Heating load during the week
This is the cooling load This is the heating load
(we must reject this (we must input this
amount of heat from the amount of heat to the
building) building)
Difference of 70 kW
Difference of 150 kW
APPLICATION EXAMPLE
How this extra capacity can be used?
Example: Daikin VRV IV Heat recovery system:
• Extra heat, produced during peak cooling load can be stored for
further domestic hot water production in water storage tank.
6
6/8/2016
APPLICATION EXAMPLE
What if heat recovery possibilities are not used (in similar purpose system)?
Example: Daikin VRV IV Heat Pump system and gas boiler – traditional solution
• Heating or cooling of building zones is provided by indoor units
• Domestic hot water and additional heating of building zones (if necessary ) is
provided by the gas boiler)
APPLICATION EXAMPLE
Results of efficiency comparison
System Efficiencies
System Efficiencies
Heat Pump VRV 6.0
Heat Pump VRV 5.8
Strasbourg Gas 0.9
Gas 0.9
Heat Recovery VRV with 6.9
DHW Heat Recovery VRV with 7.6
DHW
Athens
7
6/8/2016
APPLICATION EXAMPLE
Results of the efficiency comparison – what is the real benefit?
APPLICATION EXAMPLE
Return of investments and lifecycle cost
Payback in 3.8 years
►
(example for Strasburg)
Heat Recovery system is more Lifetime saving € 418,000
►
8
6/8/2016
Supply
Return
Altogether this makes a kind of recuperator, which you This is the DX heat exchanger
often see in AHUs. But in this case heat is transferred not in the return section, it is used
only between supply and return air within AHU itself, but to capture the heat extracted
within the whole system, i.e. can be used in those points from the room
where it is mostly needed.
18 Heat Recovery Basics
20 HR VRF Concepts
9
6/8/2016
3 PIPE CONCEPT
Most Heat Recovery VRF systems on market (including Daikin VRV) use 3-pipe technology.
21 HR VRF Concepts
2-PIPE CONCEPT
2-pipe concept is offered by M company and is heavily promoted as something unique.
10
6/8/2016
Total 1,029mm2
23 HR VRF Concepts
90 @100m DK is 90 @100m DK is
~4% better ~5% better
80 80
23.52kw 39.15kw
(▲2.25kw)
(▲1.12kw)
70 70
11
6/8/2016
Refrigerant volume
Liquid pipe φ15.9
Multi BS Initial amount O/U 11.8 kg
Additional amount 19.2 kg
TOTAL
31.0 kg
I/U I/U I/U I/U I/U (50% less)
25 HR VRF Concepts
Distributor Manifold
BS Unit
Indoor units
Indoor units
12
6/8/2016
28 VRV IV HR Basics
REYQ_T
REMQ5T
HP 8 10 12 14 16 18 20
Casing
Cooling – Nom. capacity 22,4 28,0 33,5 40,0 45,0 50,0 56,0 14,0
Heating – Nom. capacity 22,4 28,0 33,5 40,0 45,0 50,0 56,0 14,0
Heating – Max. capacity 25,0 31,5 37,5 45,0 50,0 56,0 63,0 16,0
Compressors 1 2 1
Fan 1 2 1
Dimensions (W x D x H) 930 x 765 x 1685 1240 x 765 x 1685 930 x 765 x 1685
These units can be combined freely (unlike VRV III HR). If not This unit is only
tabulated combinations are used, different piping limitations used for 10 HP
apply. (5+5 HP) and 13
HP (5+8 HP)
These combinations are needed if we want continuous heating for 10, 12 and 14 HP. combinations.
29 VRV IV HR Basics
13
6/8/2016
30 VRV IV HR Basics
SPECIAL TYPE INDOOR UNITS Hydroboxes are the important component for Heat
Recovery VRV – they are the easiest way to use
1. Hydroboxes excessive heat.
Low Temperature HXY-A Can heat water up to 450C (underfloor heating, domestic
hot water, convectors). Can also cool water down to 100C
(to be used in AHUs, FCUs)
2. Biddle air curtains
VAM-
Heat Recovery
31 VRV IV HR Basics
14
6/8/2016
90
80
70
60
50
Modular
40
Up to 25,000m3/h
20
500m3/h 750m3/h 750m3/h
0
For coil capacity, approx. (kW x 10)
The following is also required: Product
Type 63 80 100 125 140 200 250 400 500
3a. Expansion valve set(s) name
3b. Control box(es) EEV set EKEXV
32 VRV IV HR Basics
These can be used during initial These can be used in project These can be used to make
discussions with the customer, design to lock the competition comparisons and
to differentiate Daikin VRV IV specification, so no other VRF to influence the customer
from competitors… can be specified… final decision…
33 VRV IV HR Basics
15
6/8/2016
50% more
compression volume Mixture of needle graphite and pearlite. Mixture of Granular graphite and
20% higher Smooth sliding, but weak. pearlite. Smooth sliding with
high strength.
34 VRV IV HR Basics
50% more
compression Compression volume increases
volume
35 VRV IV HR Basics
16
6/8/2016
36 VRV IV HR Basics
37 VRV IV HR Basics
17
6/8/2016
• Rotates smoothly at low speeds due to larger magnets surface -> has wider
operation range, thus provides more stable refrigerant pressure.
Motor efficiency comparison :350W class Motor efficiency comparison :750W class
ODM motor
Motor efficiency
Motor efficiency
Around 3% Conventional
Around 1%
38 VRV IV HR Basics
39 VRV IV HR Basics
18
6/8/2016
DK
t t 2t
Time Time
This is predictive PI logic (based on result This is normal PI logic (based on
measurement and corresponding input result measurement and
correction, but also using trends to get corresponding input correction)
necessary result faster)
19
6/8/2016
Load Improved by up
to 15% mix mode
control
Tamb
Fan Interlocked
operation of all
the
2. Optimized heat exchanger EV Switch HE components
division and mode switching. (compressors,
Will be explained further. EEVs, fans,
Comp. condenser
switching)
42 VRV IV HR Basics
43 VRV IV HR Basics
20
6/8/2016
Multi BS box
(BC controller)
45 VRV IV HR Basics
21
6/8/2016
46 VRV IV HR Basics
◆Sound countermeasure 1
Sound insulation kit (option) ◆Sound countermeasure 2
optional kit
BS-box
BS-box
Duct
insulation
material
How is this possible?
22
6/8/2016
For technical cooling to be possible, the evaporating temp has to be lower than outdoor temperature
in winter time:
1. To avoid re-solidification of refrigerant in the indoor unit
2. In case of multi module, to avoid refrigerant stored in the outdoor unit that is not operating.
Daikin Competition
The pressure control valve inside BS box can lower Te below There is a risk to the system reliability:
Tamb. <= Daikin original technology (No similar function in • Worst case:
main competitor) • compressor problem
• Often case:
Liquid piping • ON-OFF operation of indoor units to avoid freezing of the
Subcooling heat exchanger heat exchanger (Te is lower than 0°C)
Refrigerant EVSC
piping
Dual pressure Ta:-5℃ Not applicable for server rooms
piping
Gas piping
EVH
Outdoor
Indoor unit Te:6℃
unit EVL Suction pipe
BS box
Pressure reduction(EVL)
Te:-8℃
48 VRV IV HR Basics
BS BS BS BS BS
EKEXV+EKEQ
Altogether this is a total HVAC solution, satisfying all building needs, from one manufacturer
Why this total solution All components are supplied,
is good for me? commissioned and controlled and
maintained from the single point.
This makes your life much easier!
49 VRV IV HR Basics
23
6/8/2016
50 VRV IV HR Basics
VRV IV HR
04. Application information
In this chapter we will learn about:
• How to compose VRV IV HR properly
• What limitations and restrictions does it have
24
6/8/2016
-5
-20
10 15 20 27 14 20 27
Tamb (°CDB) -5
Tamb (°CDB)
indoor unit indoor unit
14 25 28
Heat recovery operation is both heating Tamb (°CWB)
and cooling, so we have to apply both indoor unit
:depending on
operation conditions
pull down area
5
Continuous
field setting.
25
6/8/2016
5 start-up Continuous
area Heating DHW
VRV indoor LT + HT LT HT
LT LT + AHU HT AHU
HT HT + AHU AHU
AHU
AHU LT + HT + AHU HT + AHU +
AHU
26
6/8/2016
Discharge gas
Suction gas
VRV IV HR is ONLY compatible with NEW BS-BOXES. You cannot use older BS-boxes
with new outdoor units. You will get UA-28 error and system will not start. There is
no way to overcome this incompatibility issue!
LSV
SVH
To outdoor unit(s)
EEV
Liquid line
Max. 8 units can be
connected to single
Suction line BS box
SVL
LSV
SVH
EEV
Liquid line This unit is working in
heating mode
• SVL, SVH – gas line step motorized valves, 0-6000 pulses control range. Used to connect suction or
discharge gas to the IU depending on the mode;
• LSV – liquid subcool valve. Used to provide 100% liquid return to liquid line after heating indoor units
working in heating mode;
• EEV – indoor unit expansion valve.
57 Title - Internal use only
27
6/8/2016
Discharge gas
Liquid Liquid
Suction
gas
Liquid Suction gas
• At least 50% of the outdoor unit load must be connected via BS-boxes (it is also
possible to connect units directly).
• Do not place BS-boxes to the area with low background sound level. This is
because mode changeover noise, which is 5-6 dBA (~2 times) higher than average
declared in the specification. This is only for 1-2 seconds, but can create
discomfort.
• Multi BS-boxes require condensate drain connection!
28
6/8/2016
Suction line
Dual pressure line
Liquid line
Min. 5 m to the
indoor unit
6 cm
1m 1m
min. 1 m min. 1 m
Top
29
6/8/2016
F1/F2 IN
(indoor) F1/F2 IN F1/F2 OUT
F1/F2 IN
Q1-Q2
P1/P2
P1/P2
30
6/8/2016
Simplified R/C
Individual
R/C Local control for the
R/C end users
Small building Mid- building Large building
Office
Shops Bank Restaurant
• VRV IV HR system has some limitations in terms of allowed temperatures. Not all
of the special types indoor units can be used together at the same time in the same
system. This is useful to know when considering the possibility of HR system
application.
• There are some points to know about BS-boxes. First of all, VRV IV HR outdoor units
must be used only with new generation BS-boxes, because they have different
refrigerant circuit and different control algorithm. There are also some tips on how
to use BS-boxes properly and effectively.
• HR system creates more data traffic on indoor-outdoor data exchange line, so there
are some additional rules compared to heat pump systems. If you want to apply the
centralized control, it is important to understand the composition of your system –
different components have different limitations.
65 VRV IV HR Basics
31
6/8/2016
32
6/8/2016
UK – ECO-FRIENDLY OFFICE
The building:
Velocity Brooklands • 9885 m2 of open plan office spaces (4 floors);
• Modern building with good heat insulation and
low level of heat loss;
• Energy Efficiency Class B (according to EPC);
• BREEAM Excellent;
33
6/8/2016
UK – ECO-FRIENDLY OFFICE
Floor plan
Velocity Brooklands
Heat transfer
This zone is served by HP system,
the mode is chosen according to
the loads
This zone is served by HR system,
the mode is chosen according to
the loads.
Heat transfer
UK – ECO-FRIENDLY OFFICE
Velocity Brooklands What are the results?
34
6/8/2016
UK – ECO-FRIENDLY OFFICE
Proper building design together with Heat Recovery
Velocity Brooklands systems application can result in 70% lower
running costs compared to the typical building of
this size and purpose!
35
6/8/2016