KT Factor Calculation

The document provides discharge current data for a sealed lead-acid battery (SLBE) over various hours and minutes of discharge time. It also includes equations and factors for calculating the capacity rating factor (Kt) of batteries based on discharge times and currents in the data.

Uploaded by

DEADMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views1 page

KT Factor Calculation

The document provides discharge current data for a sealed lead-acid battery (SLBE) over various hours and minutes of discharge time. It also includes equations and factors for calculating the capacity rating factor (Kt) of batteries based on discharge times and currents in the data.

Uploaded by

DEADMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Discharge Current Data - Manufacturer

Hours Minutes Seconds


Cell Type Rated Ah
10 8 5 3 2 1.5 1 30 20 15 10 5 1 30 5 1

SBLE 830 83 102 156 217 272 313 370 464 501 550 606 636 761 830 1010 1108

� �=�� � − ((� ��−�� 𝟏) (� �−�))/


Capacity Rating Factor (Kt) ((� �−� 𝟏))
REFERENCE:

Discharge Time t1 from Time t2 from Ampere for Ampere for Factor Kt1 for Factor Kt2 for Factor Kt for
Time t (min) data (min) data (min) time t1 (A) time t2 (A) time t1 time t2 time t
299.680 180.0 300.000 217.000 156.000 3.825 5.321 5.317
599.680 480.00 600.000 102.000 83.000 8.137 10.000 9.995 IEEE RECOMMENDED
0.0200 0.0167 0.0833 1108.000 1010.000 0.749 0.822 0.753 PRACTICE FOR SIZING
1.170 1.0 5.0 761.000 636.000 1.091 1.305 1.100 NICKEL-CADMIUM
0.170 0.08 0.50 1010.000 830.000 0.822 1.000 0.859 BATTERIES FOR
STATIONARY APPLICATION
(IEEE Std 1115-2000)