Installation Manual WS
Installation Manual WS
WS
Gas-Insulated Switchgear up to 36 kV
Installation Instructions
Ausgabe 11/2011
www.schneider-electric.com
Manufacturer:
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg
Germany
( +49 (0) 9 41 46 20-0
7 +49 (0) 9 41 46 20-418
Service:
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg
Germany
( +49 (0) 9 41 46 20-777
7 +49 (0) 9 41 46 20-418
WS Contents
1 Safety provisions............................................................................... 7
2 Technical Data.................................................................................... 8
2.1 Applicable standards........................................................................................ 8
2.2 Environmental and operating conditions.......................................................... 9
2.3 Intended use.................................................................................................... 9
2.4 Disposal after the end of service life................................................................ 9
3 Variants overview............................................................................. 10
3.1 Single busbar panel WSA.............................................................................. 10
3.2 Double busbar panel WSB............................................................................. 13
14 Installation of IGIS............................................................................ 31
15 Pressure transmitter........................................................................ 32
20 High-voltage connection................................................................. 39
23 Final work......................................................................................... 47
23.1 Final work....................................................................................................... 47
23.2 Commissioning............................................................................................... 47
25 Annex................................................................................................ 52
25.1 Auxiliary products........................................................................................... 52
25.2 Coating of sealing surfaces and seals........................................................... 52
25.3 Coating the contact surfaces.......................................................................... 53
25.4 Screw locking compound............................................................................... 53
25.5 Specifications for screw connections............................................................. 54
As our products are subject to continuous further development, we reserve the right
to make changes regarding the standards, illustrations and technical data.
All dimensions specified in this manual are in millimeters.
Reference documents
The following additional ■■ purchase agreement with the stipulations regarding the switchgear-specific
documents must be complied equipment and the legal details
with: ■■ Operating Manual WS
■■ the appropriate switchgear-specific circuit diagrams / documentation
■■ the Operating Manuals of the devices installed in the switchgear:
–– voltage detection systems, e. g. IVIS (no. AGS 531751-01)
–– system for the detection of internal arcs ILIS (optional)
(no. AGS 531761-01)
–– devices in the low-voltage cabinet.
■■ the Assembly Instructions of the manufacturer of the cable connection systems
to be connected to the switchgear
■■ the Switchgear Configuration „WS”
■■ the assembly drawings supplied with the equipment.
"Danger!"
This danger symbol warns about dangerous electrical voltage.
Contact with voltage may result in fatal injury!
"Warning!"
This danger symbol warns about the risk of injury. Please comply
with all the provisions identified by this symbol in order to avoid
death or serious injury.
"Important:"
This instruction symbol is used for information which is important to
avoid material damage.
Abbreviations used
Ur: Rated voltage
Ir: Rated current
The work described in this manual may only be performed by specialist electricians
with proven experience in conjunction with the WS series and the applicable safety
provisions.
Read the instructions carefully before you work on the switchgear.
Before performing work on the panels, it is essential that you comply with the follow-
ing instructions:
Danger!
Mortal danger due to high voltage. Before performing assembly
or maintenance work, the system must be isolated from high volt-
age, and earthed.
Danger!
Mortal danger due to supply voltage. Before performing assembly
or maintenance work, the system must be isolated from the sup-
ply voltage.
Warning!
Risk of injury from movable parts in mechanical drives. Before
performing maintenance work,
–– isolate the system from the supply voltage
–– release the circuit-breaker’s energy storing device by OFF-
ON-OFF operation
Warning!
After the removal of covers from a switchgear, operator safety
regarding internal arcs may be reduced unless the switchgear is
isolated from the power supply. Optimum operator safety is only
ensured if the switchgear is completely isolated from the power
supply and earthed for assembly work.
Behaviour in case of incidents or For the case of an internal fault, the WS series panels are equipped with pressure
accidents relief ports which ensure operator safety.
This Technical Manual does not include information regarding the safety of buildings
in case of internal faults (pressure load of the switchgear room and necessary pres-
sure relief ports). Pressure calculations for switchgear rooms incl. recommendations
regarding pressure relief ports can be provided on request against a fee. For further
details, please contact the manufacturer.
In case of fire or of internal faults, toxic and caustic decomposition products may be
produced. Comply with the locally applicable accident and safety provisions.
Make sure that first-aid measures are taken in case of injury to persons.
Liability Disclaimers The manufacturer shall not be held responsible for damage which occurs if
■■ instructions in this Technical Manual are not complied with;
■■ the switchgear is not operated according to its intended use (see above);
■■ the switchgear is assembled, connected or operated improperly;
■■ accessories or spare parts are used which have not been approved by the
manufacturer;
■■ the switchgear is converted without the manufacturer’s approval, or if inadmis-
sible parts are added.
No liability is accepted for parts provided by customers, e.g. voltage transformers.
1 2
Fig. 1
1 Drive with front control panel 5 Supporting structure with cable connection area
2 Circuit-breaker compartment 6 Low-voltage cabinet
3 Busbar tank with disconnector and earthing switch 7 IVIS voltage information system
4 Cable test sockets
1 2
Busbar Busbar earthing 1 Cable connection and earthing for
metering panel with earthing switch in the busbar run work purposes on the busbar, e. g.
with current transformers for metal-enclosed busbar voltage
in the busbar run transformers or cable connections.
and metal-enclosed voltage transform- Inner cone-type bushings size 1
ers in outgoing feeder area, connected or 2
via cable 2 Fully insulated conductor bar ter-
minal forward, to busbar ends
1
7
Fig. 2
1 Drive with front control panel 6 Low-voltage cabinet
2 Tank with circuit-breaker 7 Cable test sockets
3 Busbar tank 1 with disconnector and earthing switch 8 IVIS voltage information system
4 Busbar tank 2 with disconnector
5 Supporting structure and cable connection
1 2
Busbar metering panel End panel 1 Cable connection and earthing for
with current transformers in the busbar Cable connection in downward and work purposes on the busbar, e. g.
run upward arrangement, depending on the for metal-enclosed busbar voltage
and metal-enclosed voltage transform- busbar position, transformers or cable connections.
ers in outgoing feeder area, connected for inner cone-type bushings Inner cone-type bushings size 1
via cable size 1-3 or fully insulated conductor bar or 2
terminal 2 Fully insulated conductor bar ter-
minal forward, on busbar ends
Packaging ■■ If packed exclusively for truck transport, the panels are delivered on a pallet
with PE protective film.
■■ For sea transport, the units are packed in sealed aluminium foil with desiccant
and in a closed wooden case with tightly closed wooden base (also for con-
tainer transport).
■■ In case of air transport, the panels are packed in wooden crates with a protec-
tive PE film hood (dust protection) or in wooden cases, also with closed wooden
bases, however without protective hoods (dust protection).
Important:
The weight of the entire transport unit is indicated on the packaging.
4.2 Transport
Warning!
Danger due to tipping
load.
Transport units must be
protected sufficiently
against slipping and tip-
ping during transport.
Fig. 3
Transport units must not be tipped over
Transport with forklift truck The panel may only be transported on a pallet. The entire length of the forks must be
placed under the transport unit.
Delivery
Warning!
Sufficient stability and evenness of the supporting area (floor)
must be ensured.
4.3 Storage
Warning!
Sufficient stability and evenness of the supporting area (floor)
must be ensured.
If the panels are not installed immediately after delivery, they can be stored under
the following conditions:
■■ Panels must be stored in vertical position, and must not be stacked.
■■ Storage only admissible indoors
■■ Switchgear panels and accessories must be sealed with desiccant in aluminium
foil and be packed in a wooden crate (storage for max. two years after the date
of packaging).
+ 40 ºC
– 5 ºC
Fig. 4
Schematic diagram of storage conditions
Warning! Lifting
Move panel by rolling it
towards the installation
area over the foundation
bar structure paral-
lel using the transport
device. Pay attention to
Supporting structure
flooring ducts - risk of
accidents! To reduce
the accident hazard, Fig. 5
have the panel rolled Insert and screw-fasten transport device in panel supporting structure
to the installation area
over the foundation bar
structure by two fitters.
Fig. 6 Fig. 7
Transport of panel to installation sur- Installation of first panel
face
Remove transport
cover
Remove mounting
cover
Fig. 8
Remove transport covers and mounting covers
Warning!
Roll the individual pan-
els to the installation
area using the transport
device, over the bridge
elements and parallel
over the foundation bar
structure. Pay attention
to flooring ducts! Risk Transport device
of accidents.
Fig. 10
„Lifting“ the panel via the four setscrews
Panel supporting
structure
Fig. 11
Insert transport trolley in panel supporting structure
Fig. 12
Screw-fastening of the panels on the front side
Panel 1
M 8 x 30
20 + 4 Nm
Fig. 14
Panel screw-fastening (with busbar compartment cladding
Panel 1
Sealing surfaces
Panel 2
M 8 x 25
36 + 4 Nm
Fig. 15
Panel screw-fastening (without busbar compartment cladding)
Spacer
M 8 x 25
Washer
Panel supp.
structure
Fig. 19
Bottom mounting, panel supporting
structure
Spacer
M 8 x 25
Washer
Panel supp.
structure
Fig. 23
Bottom mounting, panel supporting
structure
Spacer
M 8 x 25
Washer
Panel supp.
structure
Fig. 26
Bottom mounting, intermediate bar,
panel supporting struture
Drilling
Ø 10 H11
1 Panel supporting
structure
2 U section
3 Angular bracket
4 Side wall
5 Cover
Fig. 29
Installation of side panel
Setting nuts
M 8 x 12
Panel supp.
structure
Side panel
Fig. 30
Bottom mounting, panel supp. structure
1. Before fastening the panel, make sure that all the previous steps have been
accomplished.
2. Drill four fastening points Ø 8.5 mm through the panel supporting structure in
the foundation bar. Tap a thread M10.
3. Slip any required shims in directly besides the fastening points. Relieve set-
screws (turn back).
4. Screw-fasten panel supporting structure with foundation bar. Tighten screw cou-
plings M10 with a minimum torque of 40 Nm (applies only to ratchet bolts with a
sufficient thread depth of 8 mm)
M 10
Fig. 31
Fastening the panels to the foundation bar
Transition resistance Comply with the manufacturer’s specifications regarding the contact resistance
measurement of busbar screw measuring unit.
fastening 1. Measure transition resistance R between the individual busbar sections with
100 A DC.
1. The gas compartments of circuitbreakers and busbars are separated. The clad-
ded compartments of the individual panels are interconnected by piping and, if
necessary, can be disconnected from the gas compartment of the switchgear in
question. Non-cladded gas compartments, e.g. busbar gas compartment of the
WSA type and circuit-breaker gas compartment of the WSA without cladding,
form a common gas compartment.
2. At the left end panel, or - in case of switchgear equipped with bus coupler - on
the left and right end panel, pressure transmitters are installed which transmit
the measured values to IGIS via signal lines.
3. A gas compartment diagram is available in the switchgear's "info" tray.
P2
Pressure transmitter
P1
Fig. 33
Gas compartments of WSA. Busbar compartments not cladded
P3
Pressure transmitter
P2
P1
Fig. 34
Gas compartments in case of WSB. The gas compartments of the switchgear panels
are connected by piping and can be disconnected from the switchgear's gas com-
partments, if necessary.
Fig. 36
Gas line, panel WSA without busbar compartment cladding
3 Circuit-breaker
Fig. 37
Gas line, panel WSB
1 Busbar 1
2 Busbar 2
3 Circuit-breaker
1. IGIS and hardware are included in separate packaging in the switchgear acces-
sories.
2. Open flap for IGIS (magnetic plate).
3. Insert IGIS and attach the clips on the left and right rear sides; tighten by
means of a screw driver.
4. Wiring to Phoenix plug-and-socket connections according to the switchgear's
circuit diagrams.
5. Connectors of the signal cables to the pressure measuring points in question
on the IGIS (P1 - P3).
6. Close non-used inputs using a cover.
Side panel
Securing damps
left-hand and right-hand
Signal lines to the
pressure transmitter
Fig. 38
Installation and connection of the IGIS
Fig. 39
Pressure transmitter
Fig. 40
Mounting of pressure transmitter,
Example: WSA with busbar compartment cladding
1 Pressure transmitter for circuit-breaker gas compartment
2 Pressure transmitter for busbar gas compartment
Desiccant bag
Cover
Fig. 41
Activating the desiccant
Screw-fasten mounting cover The welding bolts on the busbar chamber must not get into contact with SF6 multi-
purpose lubricant MS.
1. Coat the sealing surfaces on the busbar chamber, the mounting cover and the
toroidal sealing ring with SF6 multi-purpose lubricant MS (refer to Annex).
Insert toroidal sealing ring.
2. Screw-fasten mounting cover. The following tightening torques apply to screw
couplings M8:
–– Steel cover, hex. nut with ratchet 14 +2/-1 Nm.
–– Aluminium cooler cover, hex. nut without ratchet 8 +2/-1 Nm.
Danger!
The switchgear must not yet be energized!
evacuate busbar gas Remove cap from extraction valve. Connect service instrument.
compartments Pre-evacuate to 15 kPa abs. Subsequently, evacuate the busbar gas compartments
The pressure data are referred to of the entire switchgear to ≤ 1 kPa abs.
+20°C and indicated as absolute
Abdeckkappe vom Absaugventil entfernen. Service-Einrichtung anschließen.
values.
Vorevakuieren auf 15 kPa abs. Anschließend die Sammelschienengasräume der
gesamten Schaltanlage auf ≤ 1 kPa abs. evakuieren.
Cap
Cap
Rear wall of
switchgear panel
Fig. 43 Fig. 44
Filling and extraction valve for the Filling and extraction valve for busbar
circuit-breaker compartment gas compartment
Filling the busbar gas Rated filling pressure, refer to name plate: pre 0.03 MPa rel.
compartments to the rated filling pre 0.05 MPa rel.
pressure pre 0.075 MPa rel.
The pressure data are referred
1. Switch service instrument over to "filling" mode. Connect gas filling device.
to +20 °C and an absolute
atmospheric pressure of 2. Insert insulating gas until the rated filling pressure is reached. Watch rated fill-
ing pressure on secondary pressure gauge of the gas refilling device
0.1013 MPa.
3. Disconnect gas refilling device.
Filling the circuit-breaker gas Rated filling pressure, refer to name plate.
compartments to the rated filling 1. Remove cap from filling valve. Connect service instrument ("filling"mode).
pressure 2. Insert insulating gas until the rated filling pressure is reached. Watch rated fill-
ing pressure on secondary pressure gauge of the gas refilling device.
3. Disconnect gas refilling device. Screw-fasten cap on filling valve.
After approx. 24 hours: A test for leakage is required whenever gas-tight flange couplings have been made.
Leakage test by means of 1. Use a leakage detector. Observe the instructions of the leakage detector's
leakage detector manufacturer.
2. Check the flange couplings mounted during installation by holding the leakage
detector close to them. The flange coupling's tightness is ensured if the leakage
detector does not react.
Dew point measurement of the 1. Use a dew point measuring device. Observe the instructions of the manufac-
insulating gas turer of the dew point measuring device.
2. Connect dew point measuring device to a filling valve. The measuring pro-
cedure is described in the operating instructions for the dew point measuring
device. The dew point temperature must not be higher than –15 °C.
3. Disconnect dew point measuring device. Screw-fasten cap on filling valve.
Fig. 45
Pressure monitoring
1 Pressure gauge (pressure measuring device) for circuit-breaker gas compart-
ment
2 Filling and extraction valve with cap (circuit-breaker gas compartment)
3 Pressure gauge for busbar section, right-hand
4 Filling and extraction valve with cap (busbar section, right-hand)
Filling the busbar gas Rated filling pressure, refer to name plate: pre 0.03 MPa rel.
compartments to the rated filling pre 0.05 MPa rel.
pressure pre 0.075 MPa rel.
The pressure data are referred
1. Switch service instrument over to "filling" mode. Connect gas refilling device.
to +20 °C and an absolute
atmospheric pressure of 2. Insert insulating gas until the rated filling pressure is reached. Watch rated fill-
ing pressure on the pressure gauge.
0.1013 MPa..
3. Disconnect gas refilling device. Screw-fasten cap on filling valve.
Filling the circuit-breaker gas Rated filling pressure, refer to name plate:
compartments to rated filling 1. Remove cover from filling valve (Fig. 45, 2, page 35), connect service instru-
pressure ment ("filling mode").
2. Insert insulating gas until the rated filling pressure is reached.
3. Disconnect gas refilling device. Screw-fasten cap to filling valve.
front shutter
Fig. 46
Pressure monitoring
1 Gas line, circuit-breaker gas compartment
2 Gas line, busbar gas compartment
3 Feeder, low-voltage cubicle
Pressure indication on pressure The pressure indication on the pressure gauge is ambienttemperature compensated,
gauge i.e. the pressure indicated corresponds to a temperature of 20 °C in the switchgear
room.
The pressure indication remains constant if the operating mode remains unchanged,
even if the temperature in the switchgear room changes.
Fig. 47
Pressure monitoring
1 Pressure gauge (pressure measuring device) for circuit-breaker gas compart-
ment
2 Pressure gauge (pressure measuring device) for circuit-breaker gas compart-
ment
3 Pressure gauge for busbar section, right-hand
4 Filling and extraction valve with cap (busbar section, right-hand)
front shutter
Fig. 48
Pressure monitoring
1 Gas line, circuit-breaker gas compartment
2 Gas line, busbar gas compartment
Fig. 50
Attachment of earthing bus line to busbar tank SS1
Fig. 51
Connecting external control lines
Screw-fastening the cable iron 1. Cable irons, angular brackets and hardware are included in switchgear acces-
sories.
2. Insert cable irons and angular brackets in panel supporting structure, and screw
them down.
Connector bushings Outer cone-type or inner cone-type sockets acc. to EN 50181 are standard equip-
ment of the panels.
Available connection types: see Switchgear Configuration.
Important:
●● Cable connectors, tools, accessories (cable clips, screws, spring
washers etc.) are not included in the scope of supplies.
●● Mount cable connectors according to the mounting instructions
of the cable connector's manufacturer. While mounting the cable
connectors, observe the specified tightening torques.
●● When shrink-fitting cable boxes, make sure that the cable connec-
tion area of the panel is not heated beyond the admissible service
temperature.
●● We cannot accept any liability for consequential damage (charred
cables of the capacitive indicator) which might result from shrink-
fitting components in the cable connection compartment using an
open flame.
Important:
After the cable connector
has been inserted and
screwed down, no canti- Cable clip Adjustable
lever loads and torsional cable iron
forces must act on the
inner conetype connection
bushing (risk of damage
to the inner cone-type
connection bushing).
Earth conductor
3. If necessary, re-adjust cable iron,
Abb. 52
align cables and fasten them to the
Example of cable connector for inner
cable iron using cable clips.
cone-type coupler, make Pfisterer,
system CONNEX
Connector shell with conductive If the metallic connector shell features a conductive surface in contact with the metal
contact surface with reference to cladding of the switchgear (this applies for the Pfisterer brand, system CONNEX),
switchgear's metal enclosure: the cable's Cu shield must not be connected to the connector shell (contacting). If for
operational reasons it is not possible to provide an insulation between the cable's Cu
shield and the connector shell, consult the manufacturer.
1. Coat contact surfaces of earth connection (cable's Cu shield) withcontact lubri-
cant KL (refer to Annex).
2. Screw-down Cu shield of cable to cable iron.
3. Close unused inner cone-typeconnection bushings with surgeproof dummy
plugs.
Cable connectors for outer 1. Mount cable connector according to the instructions of the cable connector
cone-type connection bushings manufacturer. Torque for tightening the cable connection (flat termination) to the
outer cone-type connection bushing (thread M16): 40 ± 5 Nm.
Important:
If the cable connector's manufacturer specifies a different tightening
torque, the latter must be used. Do not use tightening torques exceed-
ing 50 Nm.
2. Slip cable connector onto outer cone-type connection bushing, and screw it
down. Tighten screw couplings M8 with a torque of 10 ± 2 Nm.
Important:
After the cable connector has been slipped on and screwed down, no
cantilever loads and torsional forces must act on the outer conetype
connection bushing (risk of damage to the outer cone-type connection
bushing)..
3. If necessary, re-adjust cable iron, align cables and fasten them to the cable iron
using cable clips.
4. Coat contact surfaces of earth connection (cable connector shell and cable Cu
shield) with contact lubricant KL (refer to Annex).
5. Screw-down earth connection of cable connector shell and Cu shield of cable to
cable iron.
6. Close non-used outer cone-type connection bushings with surgeproof caps.
Connector for belted cable (only Mount hose-type cable box and connecting adapter according to manufacturer's
up to 24 kV) for outer cone-type mounting instructions.
connection bushing
Connecting
pin
Connecting
adapter
Adjustable
Cable clip cable iron
Adjustable
cable iron
Earth conductor
Fig. 53 Fig. 54
Example of cable connector for outer Belted cable for outer cone-type cou-
cone-type coupler, make pler, make F&G, type SKV 10D
KABELRHEYDT, type AGG 20/400
(plug-in contact)
M 8 x 40
20 ± 2 Nm
Fig. 55
Example of fully insulated conductor
bar connection, make Meßwandlerbau,
system DURESCA
Current transformer in line with 1. Trailing cables ready for installation included in switchgear accessories.
busbar (current measurement on 2. Take account of obligatory assembly drawing.
the busbar) 3. Remove transport protective caps from the connection bushings (socket-con-
tacts).
4. Mount cable connector according to the instructions of the cable connector
manufacturer. Insert cable-con-nector in inner cone-type connection bush-
ing (press down) and screw-fastensafely. Tighten screw couplings M8 with a
torque of 15 ± 3 Nm.
Important:
After the cable connector has been inserted and screwed down, no
cantilever loads or torsional forces must act on the inner conetype
connection bushing (risk of damage to the inner cone-type connection
bushing).
5. If necessary, re-adjust cable iron, align cables and fasten them to the cable iron
using cable clips.
Screw-fastening the dummy plug
Important:
Close unused outer or inner cone-type connection bushings with surge-
proof dummy plugs (surgeproof dummy plugs are not included in the
scope of supplies). Surge-proof dummy plugs are available from the
manufacturer of the cable connection system.
Dummy Transport
plug protection
cap
Fig. 57
Example of dummy plug for inner cone-
type connection bushing
Screw-fasten cover plates to the rear of the panel supporting structure (cover plate
and hardware are included in the switchgear accessories).
Fig. 58
Screw-fastening the cover plate
22.1 Overview
Voltage transformers are normally designed as metal-enclosed flange-mounted
transformers with single-pole insulation. The transformers are flange-mounted via
pluggable inner cone-type connections and can be replaced without gas handling.
Fig. 59 Fig. 60
Voltage transformer in outgoing feeder Voltage transformer on single and double busbar (flange-mounted transformer with
cable (flange-mounted transformer with disconnecting device)
disconnecting device)
Danger!
When performing assembly work on voltage transformers, the ap-
propriate disconnecting device must be in earthed position (see
Operating Manual).
Warning!
After the removal of covers from a switchgear, operator safety
regarding internal arcs may be impaired unless the switchgear is
isolated from the power supply. Optimum operator safety is only
ensured if the switchgear is completely disconnected from the
power supply and earthed during assembly.
Important:
●● Remove grease and silicone from the contact surfaces and insu-
lating areas on the inner cone-type connectors in the tank and on
the voltage transformers before assembly.
●● Comply with the assembly instructions of the voltage transform-
ers.
●● The weight of the transformers must be taken into consideration.
Support the transformer or secure it by attaching a crane hook to
the transformer jack rings.
6
2
3 4
2
Fig. 61
Mounting a voltage transformer to the busbar
1 Voltage transformer
2 Self-locking screw M8 x 20
3 Angle bracket
4 Setting nut M8
5 Inner cone-type connection system
6 Self-locking nut M8
Fig. 62 Fig. 63
Design as multiple cable connection: Design as single cable connection:
current transformer package current transformer package
Danger!
The high-voltage supply must not be connected. All active parts
must be earthed.
Clean and check assembly work 1. Clean the switchgear to eliminate soiling due to assembly work.
2. Remove all the attached information tags, cards, brochures and instructions no
longer needed.
3. Have all parts removed during the work on site been re-mounted?
Damaged paint The components are powder-coated. Minor damage to the paint can be repaired
using commercially available paint (standard colour RAL 7044 or corresponding
colour).
Checking ■■ Check the switchgear for damage which might be due to transport or assembly
work.
■■ Comparea data on the nameplate to the required ratings.
■■ Check supply voltage of the control and operating devices.
■■ Check wiring laid on the site.
■■ Check insulation gas monitoring and rated filling pressure indication on the
IGIS/pressure gauge.
23.2 Commissioning
Danger!
The high-voltage supply must not be connected. All active parts
must be earthed.
Important:
●● Refer to the operating manual of the WS series.
●● While the power supply is not available, blocking coils (locking the
interrogation lever and circuit-breaker push-button, depending on
design), are in “locked” position. An undervoltage release (option-
al) has dropped out. In this case, first perform items 3 to 5.
●● The energy storing device of the circuit-breaker drive mechanism
is charged automatically, as soon as the power supply is avail-
able.
General Optionally, the busbar can be subjected to a power frequency withstand test. The
test voltage is supplied via the high-voltage terminal of a panel. To this effect, a test
unit and test cables are required, which are not included in the scope of supplies.
Warning!
Please comply with the safety provisions in Chapter 1, page 7.
Danger!
No high-voltage cables must be connected in the incoming feeder
panel for the voltage test and to the busbar. All high-voltage termi-
nals must be closed surge-proof during the test phase. Earth the
residual phases using commercially available earthing devices.
Important:
All the switching operations mentioned in this context must be per-
formed in accordance with the applicable Operating Manual WS.
Preparations 1. All panels must be isolated from the power supply, and earthed.
2. Incoming feeder panel for voltage test:
–– Remove the cable compartment cover. Mount test cable to a phase of the
high-voltage terminal. Open high-voltage terminals must be closed surge-
proof during the test phase. Earth the residual phases using commercially
available earthing devices.
–– Earth the voltage transformers and capacitive measuring connectors.
Disconnect the surge arrester.
7
4
1 3 2
6 5
Fig. 64
1 Outgoing feeder panels
2 Incoming feeder panel for voltage test
3 Voltage transformer
4 Busbar
5 Test unit (e g. high-voltage source, test transformer)
6 Test cable(s)
7 Busbar voltage transformer
3. Busbar:
–– Earth voltage transformer / surge arrester.
–– Earth capacitive measuring connectors.
–– Close open high-voltage terminals in a surge-proof fashion.
Power frequency withstand test: 4. Power frequency withstand test of the busbar:
–– Connect test unit to the test cable.
–– Switch earthing switch in the incoming feeder panel OFF.
–– Switch disconnector and circuit-breaker in the incoming feeder panel ON.
–– Perform power frequency withtstand tests successively for all phases (L1,
L2, L3) according to the specifications of the test unit manufacturer.
Important:
Observe admissible test values for the switchgear and the admissible
test values for power frequency withstand tests after installation of the
switchgear in accordance with IEC 62271-200.
5. Once the power frequency withstand test has been completed, earth all the
tested high voltage lines again.
Comply with the applicable safety provisions!
Once the power frequency 6. Once the power frequency withstand test has been completed,
withstand test has been –– remove the test unit and the test cable,
completed, –– reconnect earthed or removed voltage transformers, capacitive measuring
connectors or surge arresters,
–– mount high-voltage cables or surge-proof covers on the incoming feeder
panel and reinsert cable compartment cover.
Warning!
Please comply with the safety provisions in Chapter 1, page 7!
Important:
The busbar can be operated with rated voltage during cable tests in the
outgoing feeder (see nameplate).
Observe the assembly and test instructions for the cable fittings and
the terminating connectors!
Fig. 65 1. Isolate the outgoing feeder cable of the appropriate switchgear panel from the
perform high-voltage cable test via power supply.
rear-side test adapters 2. Isolate outgoing feeder cable in the remote station.
3. Earth the outgoing feeder cable.
4. Disconnect the following devices or earth them if this is envisaged:
–– Pluggable voltage transformers
–– Pluggable surge arresters
–– Measuring amplifiers for capacitive voltage measurement.
If non-detachable voltage transformers (connected via cable) are used, these must
be disconnected on the switchgear end and the sockets must be closed “surge-
proof” using dummy plugs.
5. Remove the test connector's dummy plugs.
6. Connect the test adapter/test cable to test sockets and test unit (observe the
manufacturer’s instructions).
Panel in test position:
Important:
Make sure that the distance between the metallic components of the
test set-up and the earthed switchgear supporting structure is suffi-
ciently dimensioned.
Once the cable test has been 9. Re-earth outgoing feeder cable:
completed –– Switch earthing switch completely OFF
–– Charge energy storing device
–– Switch earthing switch ON again
10. Re-connect the disconnected devices.
11. Remove test set and close test socket “surge-proof” using the dummy plug.
Cable test from the opposite side with the cables connected, on the WS switchgear:
For test set-up and implementation, refer to the instructions of the cable manufac-
turer. Refer to items 1-4 and 7-10 of this section!
Admissible limits for the UO/U DC test voltage for 0.1 Hz AC test volt- 40–65 Hz AC test
switchgear panels in case of (Um)1 initial / repeat test age [kV] voltage [kV]
cable tests [kv] [kV] max. 15 min max. 60 min max. 60 min
6/10 (12) 34 18 12
12/20 (24) 67 36 24
18/30 (36) 76 54 36
1 Description U0/U (Um): HD 620/621 S1 or IEC 60502-2
Warning!
Risk of injury if these products are handled improperly. Observe
the safety data sheets of the manufacturers of the auxiliary prod-
ucts.
Important:
Sealing surfaces, once coated with SF6 multi-purpose lubricant, should
not be touched, if possible. Any contamination may impair function
(leakage).
1. Sealing surfaces, seals (cord sealing rings) and grooves for cord sealing rings
must be cleaned with particular care using cleaning agent for insulating gas
compartments and a lint-free cloth.
2. Check visually for cleanness.
3. Immediately afterwards, apply SF6 multi-purpose lubricant MS using a nylon
brush or a leather cloth.
4. Use the nylon brush or the leather cloth only for this work and store them in a
place where they are protected against soiling.
Important:
Contact areas, once coated with synthetic lubricant (KL), must not be
touched.
Important:
●● Observe the specifications of the manufacturer of the screw lock-
ing compound.
●● In case the thread reach exceeds 1.2 x the screw diameter and in
case of blind hole threads, only wet the nut's thread.
1. Preparing the thread surfaces: clean and degrease thread surfaces using
cleaning agent and a lint-free cloth.
2. Application of adhesive: Coat the entire circumference of 2 or 3 threads in the
area to be glued with liquid screw locking compound.
Max. time for positioning: 60 sec.
Important:
●● The threads of screws and bolts must generally not be pre-treat-
ed!
●● Max. tolerance for the effective tightening torques: ±15%
●● The nut must correspond in strength to the grade of the screw/bolt
used or be of better quality.
General screw connections
Grade or material
Self-locking screw
Screw/bolt Plastic ≥ 8.8 ≤ 10.9
≥ 8.8
Thread Ø Tightening torques [Nm]
M4 0.25 2.6
M5 0.5 5.0 7.0
M6 0.8 8.8 12.3
M8 1.8 21.0 30.0
M 10 3.5 42.0 59.0
M 12 6.0 70.0 97
M 16 12 170
M 20 330
Schneider Electric As our products are subject to continuous development, we reserve the
35, rue Joseph Monier right to make changes regarding the standards, illustrations and technical
CS 30323 data described in this Technical Manual. For any requests, please contact
92506 Rueil-Malmaison Cedex, France the address given below.