Instrumentation Cables: Multipair Individual and Overall Screen, Armoured and Lead Sheathed
Instrumentation Cables: Multipair Individual and Overall Screen, Armoured and Lead Sheathed
INSTRUMENTATION CABLES
Multipair Individual and Overall Screen,
Armoured and Lead Sheathed
PE/IS/OS/PVC/LC/PVC/SWA/PVC CABLE CONSTRUCTION
XLPE/IS/OS/LSZH/LC/LSZH/SWA/LSZH
Conductors Plain annealed electrolytic copper wire according to
APPLICATIONS EN 60228 class 1(U) solid, class 2 (R) stranded, class 5 (F) flexible.
Insulation PVC, PE, XLPE or LSZH thermoplastic material.
Can be used in cable tray or conduit to connect electrical
instrumentation and communication circuits in industrial process Twisting The insulated cores shall be twisted in pairs for a good
controls, refineries, oil and gas plant. reduction of the electromagnetic noise.
Excellent protection against corrosion, humidity and poor vibration Individual screen Aluminium/polyester tape, coverage >100%,
resistance. aluminium in contact with tinned copper drain wire.
Cabling The screened pairs are cabled with suitable non
OPERATING TEMPERATURE hygroscopic fillers (when necessary) and wrapped with polyester
tape if required.
-20 °C to +80 °C (for general use); -40 °C to +90 °C (on request).
Overall screen Aluminium/polyester tape, coverage >100%,
aluminium in contact with tinned copper drain wire.
MINIMUM BENDING RADIUS
Bedding PVC or LSZH thermoplastic material.
20 times the outer diameter.
Lead Sheath Lead alloy.
Inner sheath PE, PVC or LSZH thermoplastic material.
Armour Single layer of galvanized steel wires (SWA).
Outer sheath PVC or LSZH thermoplastic material.
APPLICABLE STANDARDS
Basic design 50228-7 or PAS 5308 Halogen free properties (only for LSZH cables) IEC 60754-1
Flame retardant IEC 60332-1 Low smoke emission (only for LSZH cables) IEC 61034-2
Fire retardant (cat. C or A according to requirements) IEC 60332-3
12