2016 Error Codes SHARP
2016 Error Codes SHARP
WALL TYPE:AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
INVERTER & NON
[8] TROUBLESHOOTING GUIDE INVERTER
1. Self-diagnosis Function
1) Indoor Unit
To display the self-diagnosis, hold down the AUX button for over 5 seconds on the indoor unit when the indoor unit
is not operating.
(AH-XP18SHV, AH-XP24SHV, AH-XP18SHV-1, AH-XP24SHV-1)
The operation lamp(red), the timer lamp(orange) and the plasmacluster lamp(blue) lash to indicate the information of
AUX button
OFF
AUX button
OFF
Remark
· If the power cord is unplugged or the circuit breaker is turned off, the self-diagonosis memory is lost.
137
AH-XP18SHV/ AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
2. Outdoor unit
• The self-diagnosis is indicated the error information by lashing LED1 on the outdoor unit.
• The self-diagnosis of outdoor unit is displayed for about 3-10 minutes. Then, the LED1 returns to normal display.
LED1
AU-X18SHV, AU-X18SEV
AU-X18SHV-1, AU-X18SEV-1
AU-X24SHV, AU-X24SEV
AU-X24SHV-1, AU-X24SEV-1 LED1
3. CHART
<INDOOR UNIT> : 1 second ON/ 1 second OFF PCI: Plasmacluster
Indoor and Outdoor Malfunc-
outdor unit indi- Indoor unit Content of diagnosis
tion No. Check point Action
units cation
operate (LED1) Lamp Main Sub Main Sub
Normal con- Normal Timer (Orange) 0 0 Normal
dition blinking Operation (Red)
PCI(Blue)/(Green)
Indoor and 1-time Timer (Orange) 1 0 Outdoor unit Heat exchanger 1) Measure the resist- 1) Replace the out-
outdoor Operation (Red) thermistor thermistor short ance of the outdoor door unit thermistor
units do not short-circuit circuit error unit thermistors. assembly.
PCI(Blue)/(Green)
operate. 2) Check the lead wire 2) Replace the out-
Timer (Orange) 1 Outdoor tempera- of the outdoor unit door unit thermistor
Operation (Red) ture thermistor thermistor for torn assembly.
short circuit error. sheath and short
PCI(Blue)/(Green)
circuit.
Timer (Orange) 2 Suction thermis- 3) No abnormal-
tor short circuit 3) Replace the outdoor
Operation (Red) ity found in above unit control PWB
error inspections (1) and
PCI(Blue)/(Green) assembly.
2).
Timer (Orange) 3 2 way valve ther-
Operation (Red) mistor short circuit
error
PCI(Blue)/(Green)
Indoor and 2 time 2 0 Cycle tem- Compressor 1) Check the outdoor 1) Ensure unobstructed
outdoor perature high temperature unit air outlet for air low from the out-
units do not error blockage. door unit air outlet.
Timer (Orange)
operate. 2) Check if the power 2) Connect power
supply voltage is AC supply of proper
230V at full power. voltage.
3) Check the pipe con- 3) Charge the speci-
nections for refriger- ied amount of
ant leaks. refrigerant.
Operation (Red) 4) Measure resistance 4) Replace the out-
of the outdoor unit door unit com-
compressor ther- pressor thermistor
mistor. assembly.
5) Check the expan- 5) Replace the expan-
sion valve for proper sion valve coil,
PCI(Blue)/(Green) operation. expansion valve or
outdoor unit control
PWB assembly.
238
AH-XP18SHV/ AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
339
AH-XP18SHV/ AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
440
AH-XP18SHV/ AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
541
AH-XP18SHV/ AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
642
AH-XP18SHV/ AU-X18SHV
AH-X18SEV/ AU-X18SEV etc.
*Remark
The malfunction No. is calculated using the following way.
Example)
Lamp Calculation Main Sub
Indoor unit lamp
16 8 4 2 1
Timer (Orange) O O O O O
Operation (Red) O O 4+1=5 5
PCI (Blue)/(Green) O 2 2
2 Malfunction diagnosis display one (Displays "17-0" when malfunction code is called out.)
3 Malfunction diagnosis display None (Displays "17-0" when malfunction code is called out.)
743
6HUYLFH0DQXDO
0DLQWHQDQFH AH-A9/12/18/24NCV
(UURU&RGH AH-A9/12/18/24PCV
'LVSOD\0HWKRGRI,QGRRU8QLW
,QGLFDWRUODPS2QO\IRU
WKHXQLWZLWKLQGLFWRU 3RVVLEOH&DXVHV)RUVSHFL¿FPDLQWHQDQFH
1R 0DOIXQFWLRQ
(UURU GXULQJEOLQNLQJ21IRU $&6WDWXV PHWKRGSOHDVHUHIHUWRWKHIROORZLQJSURFHGXUH
1DPH
&RGH 6DQG2))IRU6 RIWURXEOHVKRRWLQJ
2SHUDWLRQ &22/ +($7
/DPS /DPS /DPS
7KHXQLWZLOOVWRSRSHUDWLRQ 7KHZLULQJWHUPLQDOEHWZHHQLQGRRUDPELHQW
DVLWUHDFKHVWKHWHPSHUDWXUHWHPSHUDWXUHVHQVRUDQGPDLQERDUGLVORRVHQHG
,QGRRUDPELHQW RUSRRUO\FRQWDFWHG
%OLQNV SRLQW'XULQJFRROLQJDQG
WHPSHUDWXUH 7KHUH¶VVKRUWFLUFXLWGXHWRWULSRYHURIWKHSDUWV
RQFH GU\LQJRSHUDWLRQH[FHSW,'8
VHQVRULV ) RQFRQWUROOHU
HYHU\ IDQPRWRURSHUDWHVRWKHU
RSHQVKRUW ,QGRRUDPELHQWWHPSHUDWXUHVHQVRULVGDPDJHG
V ORDGVVWRSRSHUDWLRQ'XULQJ 3OHDVHFKHFNLWE\UHIHUULQJWRWKHUHVLVWDQFH
FLUFXLWHG
KHDWLQJRSHUDWLRQWKHV\VWHPWDEOHIRUWHPSHUDWXUHVHQVRU
VWRSVRSHUDWLRQ 0DLQERDUGLVEURNHQ
7KHXQLWZLOOVWRS 7KHZLULQJWHUPLQDOEHWZHHQLQGRRUHYDSRUDWRU
RSHUDWLRQDVLWUHDFKHV WHPSHUDWXUHVHQVRUDQGPDLQERDUGLVORRVHQHG
,QGRRU
WKHWHPSHUDWXUHSRLQW RUSRRUO\FRQWDFWHG
HYDSRUDWRU %OLQNV
'XULQJFRROLQJDQGGU\LQJ 7KHUH¶VVKRUWFLUFXLWGXHWRWKHWULSRYHURIWKH
WHPSHUDWXUH WZLFH
) RSHUDWLRQH[FHSW,'8IDQ SDUWVRQFRQWUROOHU
VHQVRULV HYHU\
RSHUDWHVRWKHUORDGVVWRS ,QGRRUHYDSRUDWRUWHPSHUDWXUHVHQVRULV
RSHQVKRUW V
RSHUDWLRQ'XULQJKHDWLQJ GDPDJHG3OHDVHFKHFNLWE\UHIHUULQJWRWKH
FLUFXLWHG
RSHUDWLRQWKHFRPSOHWHXQLWUHVLVWDQFHWDEOHIRUWHPSHUDWXUHVHQVRU
VWRSVRSHUDWLRQ 0DLQERDUGLVEURNHQ
7KHIHHGEDFNWHUPLQDORI3*PRWRULVQRW
,'8IDQ2'8IDQ FRQQHFWHGWLJKWO\
%ORFNHG %OLQNV FRPSUHVVRUDQGHOHFWULF 7KHFRQWUROWHUPLQDORI3*PRWRULVQRW
SURWHFWLRQRI + WLPHV KHDWWXEHVWRSRSHUDWLRQ FRQQHFWHGWLJKWO\
,'8IDQPRWRU HYHU\V +RUL]RQWDOORXYHUVWRSVDWWKH )DQEODGHURWDWHVXQVPRRWKO\
FXUUHQWSRVLWLRQ 0DOIXQFWLRQRIPRWRU
0DLQERDUGLVEURNHQ
2SHUDWLRQRIUHPRWH 7KHUH¶VQRWMXPSHUFDSRQWKHPDLQERDUG
0DOIXQFWLRQ %OLQNV
FRQWUROOHURUFRQWUROSDQHOLV -XPSHUFDSLVQRWLQVHUWHGSURSHUO\DQGWLJKWO\
SURWHFWLRQRI & WLPHV
DYDLODEOHEXWWKHXQLWZRQ¶W -XPSHUFDSLVGDPDJHG
MXPSHUFDS HYHU\V &RQWUROOHULVGDPDJHG
DFW
=HURFURVVLQJ
4XLFNGHHQHUJL]DWLRQDQGHQHUJL]DWLRQ:URQJ
LQVSHFWLRQ 2SHUDWLRQRIUHPRWH
%OLQNV MXGJHPHQWE\WKHFRQWUROOHUEHFDXVHWKHHOHFWULF
FLUFXLW FRQWUROOHURUFRQWUROSDQHOLV
8 WLPHV GLVFKDUJLQJRIFDSDFLWRULVVORZ
PDOIXQFWLRQ DYDLODEOHEXWWKHXQLWZRQ¶W
HYHU\V =HURFURVVLQJ LQVSHFWLRQ FLUFXLW RI PDLQ ERDUG
RIWKH,'8IDQ DFW
IRUFRQWUROOHULVDEQRUPDO
PRWRU
,QVWDOODWLRQDQG0DLQWHQDQFH
8
GX-A24/36/48PCV
GX-A24 Fixed-Frequency
/ 36 / 48PCV U-Match MAINTENANCE
Air Conditioners Service Manual
94
939
MAINTENANCE GX-A24
Fixed-Frequency / 36 / 48 PCV
U-Match
Air Conditioners Service Manual
Trouble Origin of
rouble Name Control Description
Code Trouble Signal
If detect evaporator temp sensor is open circuit or short circuit for continuous
5s, system will be turned off when cooling and dehumidifying, and all loads will
Failure of Evaporator Indoor Evaporator be turned off except for 4-way valve when heating. LED will blink or display
F1
Temp. Sensor Temp Sensor error code F1. When error is cleared, it can resume running automatically
and clear error display. Under air supply mode, only display error and
inner fan runs normally. After error is cleared, error display disappears.
If detect that condenser temp sensor is open circuit or short circuit for 5s,
system will be turned off when cooling and dehumidifying, and all loads will
be turned off except for 4-way valve when heating. LED will blink or display
Failure of Condenser Outdoor Condenser
F2 error code F2. When error is cleared, it can resume running automatically and
Temp. Sensor Temp Sensor
clear error display. Under air supply mode, only display error and inner fan
runs normally. After error is cleared, error display disappears. For cooling-only
unit, no models but air duct type unit detect the condenser temp sensor error.
If detect that outdoor ambient temp sensor is open circuit or short circuit for
5s, system will be turned off when cooling and dehumidifying, and all loads will
Failure of Outdoor Outdoor Ambient be turned off except for 4-way valve when heating. LED will blink or display
F3
Ambient Sensor Temp Sensor error code F3. When error is cleared, it can resume running automatically
and clear error display. Under air supply mode, only display error and
inner fan runs normally. After error is cleared, error display disappears.
After startup of compressor, if detect that discharge temp sensor is open circuit
for continuous 5s, Under cooling and dehumidifying, all loads will be turned
off. When heating, all loads will be turned off except for 4-way valve when
heating. LED will blink and E4 will be displayed.At the same time, buzzer will
Failure of Exhaust Discharge Temp sound. When error is cleared, it can resume running and erase the error code.
F4
Temp. Sensor Sensor If discharge temp sensor is short circuit, Under cooling and
dehumidifying, all loads will be turned off. When heating, all loads
will be turned off except for 4-way valve when heating. LED will blink
and E4 will be displayed.At the same time, buzzer will sound. When
error is cleared, it can resume running and erase the error code.
If detect that temp sensor of wired controller is open circuit or short circuit
for continuous 5s, ambient temp will be compulsively set as 24 ć , and
Failure of Indoor
there is no any performance of the system. Only LED blinks or display
F5 Room Sensor at Wired Controller
error code F0. When error is cleared, it can resume running automatically
Wire Controller
and clear error display. Under air supply mode, only display error and
inner fan runs normally. After error is cleared, error display disappears.
93
10
38
GX-A24 Fixed-Frequency
/ 36 / 48PCV U-Match MAINTENANCE
Air Conditioners Service Manual
4MAINTENANCE
4.1 ERROR CODE TABLE
Origin of
2! Name Control Description
Code Signal
If full water protection has not been recovered for continuous 2
E0 Pump Failure Water Pump hours, it is believed that there is water pump error. All loads will
be turned off and it cannot be automatically recovered.
When high pressure protection has been detected for continuous
3s, all loads will be turned off( except for 4-way valve for heating).
Compressor High
E1 High Pressure Switch Sheild all buttons and remote signal except ON/OFF button. They
Pressure Protection
cannot be recovered automatically. The error cannot be cleared until
turn on/off the unit or de-energized error has been recovered.
When defrosting and dehumidifying have been executed for a period of
Indoor Frost-Proof Evaporator Temp. time, if detect that evaporator temp. sensor is lower than -2ć , the unit
E2
Protection Sensor of indoor unit ! !!
!#
#^ć
and the compressor has been stopped for 3min, the unit can run.
When the unit is on or standby(if the compressor is on, detection will
be executed after 3min of the running), if detect that low pressure
Compressor Low
E3 Low Pressure Switch switch breaks up for continuous 30s, this error will be warned. The
Pressure Protection
! !
^J J!
!
J+
but over 3 times, the error cannot be automatically recovered.
After the running of compressor, if detect that discharge temp. is higher that
Compressor 130ć in continuously 30s, error code “E4”will de displayed and all loads will
Exhaust High Discharge Temp. be turned off. After 3min stop of compressor, if detect that the discharge temp.
E4
Temperature Sensor is lower than 90ć for continuously 5s, the compressor will resume running.
Protection if detect that there are 3 times of high temp. protections,
it cannot be recovered automatically.
After running of compressor, if detect that overload switch of compressor
breaks for continuous 3s, this error will be warned. All loads will be turned
off( except 4-way valve for heating) and the error will be displayed.
After the compressor has been stopped for 3min, if the error has been
Compressor
E5 Compressor J! +
#=!
!
J
+
Overheat
of compressor overload protections have been detected within 30min,
it cannot be recovered automatically and buzzer will sound. Press ON/
OFF button to clear the sound. By press it again, it will resume running
if high pressure protection disappears. If not, error will be displayed.
After energization, if the outdoor unit has not received any data
from indoor unit for continuous 30s, there is communication error
of indoor unit. Compressor and outer fan will stop and when
heating, 4-way valve will stop after 2m stop of compressor
Communications If indoor unit has not received the data from outdoor unit, there
E6 Communication
Failure is communication error. Indoor unit will stop and LED will blink. If
display panel has not received any data from outdoor unit, it will
judge as communication error and display the error. The unit will stop
but after the communication becomes normal, the system will run
at the previous status, which can be recovered automatically.
If fan overload protection has been detected for continuos 3s,
Indoor Fan compressor and fan will stop immediately, E8 will be displayed
E8 Inner Fan
Protection and buzzer will sound. If the error is cleared, press ON/OFF button
and the error display will disappear. Press it again to restart it.
After energization, full water is detected for continuous 8sm, full water
protection will be entered and LED will blink (or E9 will be displayed):
Full Water Under cooling and dehumidifying, outer fan and compressor will stop and
E9 Liquid Level Switch
Protection inner fan will stop 1min later; under heating, outer fan and compressor
will stop, 4-way valve keep previous status and inner fna will stop 1min
delay; under air supply mode, loads of indoor unit will not be turned off.
If detect that indoor temp sensor is short circuit or open circuit for
continuous 5s, indoor ambient temp will be compulsively set as
Failure of Indoor
Indoor Ambient 24ć and there is no any performance of the system..LED will blink
F0 Room Sensor
Temp. Sensor or display error code F0. After clearing the error, it can automatically
at Air Intake
resume running. Under air supply mode, just display error code which
will disappear after error is cleared and inner fan will normaly run.
92
37
11
U-Match Series DC Inverter Service Manual
MAINTENANCE GX-X18/24/36/42SCR
GB-X18/24/36SCR
1 TROUBLE TABLE
1.1 Main Control Malfunction
Table 1 Fault Display on Indoor Wired Controller
Origin of
Error Malfunction
No. malfunction Control description
code name
signal
When outdoor unit detects the high pressure switch is cut off for 3s
successively, high pressure protection will occur. All the loads (except
High pressure High pressure the 4-way valve in heating mode) will be switched off. In this case, all
1 E1
protection switch the buttons and remote control signals except ON/OFF button will be
disabled and cannot be recovered automatically. Switch off the unit or
re-energize the unit after cutting off power to eliminate this protection.
If detecting that the evaporator temperature is lower than protective
Indoor temp. Value after the unit has been running for a period of time under
Freeze evaporator cooling or dry mode, the unit will report this fault, in which case the
2 E2
protection temperature compressor and outdoor fan motor will be stopped. The unit will not run
sensor until evaporator temperature is higher than the protective temp. value
and the compressor is stopped for 3min.
If it is detected within 30s successively that the low-pressure switch is
Low pressure Low pressure cut off under ON or standby state, the unit will report low pressure
protection switch protection. If the fault occurs successively 3 times within 30min, the unit
cannot be recovered automatically.
3 E3 Refrigerant If the unit reports system refrigerant lacking within 10min after turning
lacking on the unit, the unit will stop operation. If the fault occurs successively 3
protection times, the unit cannot be recovered automatically.
If enter refrigerant recycling mode through special operation, E3 will be
Refrigerant
displayed. After exiting refrigerant recycling mode, the code will
recycling mode
disappear.
If outdoor unit detects that the discharge temperature is higher than
Compressor Compressor
protective temp. Value, the unit will report high discharge temperature
high discharge discharge
4 E4 protection. If the protection occurs over 6 times, the unit cannot be
temperature temperature is
recovered automatically. Switch off the unit or re-energize the unit after
protection high
cutting off power to eliminate this protection.
Communicatio
If the outdoor unit does not receive data from indoor unit,
n between
Communicatio communication malfunction will be reported. If there is communication
6 E6 indoor and
n malfunction abnormity between display board and indoor unit, communication
outdoor
malfunction will be reported too.
mainboard
If the indoor unit does not receive signal from indoor fan motor for 30s
successively when the fan motor is operating, indoor fan motor
malfunction will be reported. In this case, the unit can automatically
Malfunction of
Indoor fan resume operation after stopping. If the malfunction occurs 6 times
8 E8 indoor fan
motor within one hour, the unit cannot be recovered automatically. Switch off
motor
the unit or re-energize the unit after cutting off power to eliminate this
malfunction.
83
12
U-Match Series DC Inverter Service Manual
Origin of
Error Malfunction
No. malfunction Control description
code name
signal
If the outdoor condenser temperature sensor is detected of open circuit
Malfunction of or short circuit for 5s successively, condenser temperature sensor
Condenser
condenser malfunction will be reported. The unit can automatically resume
12 F2 temperature
temperature operation after the malfunction disappears. If condenser temperature
sensor
sensor sensor malfunction occurs in fan mode, only the error code is displayed
and the indoor unit can work normally.
If the outdoor ambient temperature sensor is detected of open circuit or
Malfunction of
Outdoor short circuit for 5s successively, outdoor ambient temperature sensor
outdoor
ambient malfunction will be reported. The unit can automatically resume
13 F3 ambient
temperature operation after the malfunction disappears. If outdoor ambient
temperature
sensor temperature sensor malfunction occurs in fan mode, only the error code
sensor
is displayed and the indoor unit can work normally.
If the outdoor discharge temperature sensor is detected of open circuit
Malfunction of
Discharge or short circuit for 5s successively after the compressor has been
discharge
14 F4 temperature operating for 3min, outdoor discharge temperature sensor malfunction
temperature
sensor will be reported. The unit can automatically resume operation after the
sensor
malfunction disappears.
Malfunction
If the wired controller detects open circuit or short circuit of its
wired controller Wired
15 F5 temperature sensor for 5s successively, wired controller temperature
temperature controller
sensor malfunction will be reported.
sensor
If the memory chip of outdoor drive board is broken, the unit cannot be
Malfunction of
Outdoor drive started. The unit cannot be recovered automatically. If the malfunction
18 ee outdoor drive
board cannot be eliminated after switching off the unit and then energizing the
memory chip
unit for several times, please replace the outdoor drive board.
Communicatio Communicatio
n malfunction n between If the outdoor main control board does not receive data from drive
35 P6 between main main control board, communication malfunction between main control and drive will
control and board and drive be reported. This malfunction can be eliminated automatically.
drive board
If the memory chip of outdoor main control board is broken, the unit
Malfunction of
cannot be started. The unit cannot be recovered automatically. If the
outdoor main Outdoor main
47 EE malfunction cannot be eliminated after switching off the unit and then
control control board
energizing the unit for several times, please replace the outdoor main
memory chip
control board.