ET-4D A 2 e

The ET-4D(A)2 is a gas detection control unit that can monitor up to 4 gas transmitters with 3 adjustable alarm levels per channel. It has a graphic display, 12 configurable relays, and optional analog outputs. The unit is configurable through the display and menu without tools. It provides alarm indication through LEDs and relays and has features like RS-232/485 interface, digital inputs, and ProfiBus/ModBus options. The unit operates at -10°C to +40°C and conforms to European standards.

Uploaded by

manufesi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views4 pages

ET-4D A 2 e

The ET-4D(A)2 is a gas detection control unit that can monitor up to 4 gas transmitters with 3 adjustable alarm levels per channel. It has a graphic display, 12 configurable relays, and optional analog outputs. The unit is configurable through the display and menu without tools. It provides alarm indication through LEDs and relays and has features like RS-232/485 interface, digital inputs, and ProfiBus/ModBus options. The unit operates at -10°C to +40°C and conforms to European standards.

Uploaded by

manufesi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Gas Detection Control Unit ET-4D(A)2

Description: Gas detection control unit for measurement of flammable and/or


toxic gases as well as oxygen. Smoke detectors as option. Graphic
display. Menu guided configuration. 3 Alarm levels per channel. 12
freely configurable relays. Analog outputs 4…20 mA (only ET-4DA2).

Wall Mounted DIN-Rail Control Panel 19”-Rack


Article-No.
230 V 24 V 230 V 24 V 230 V 24 V 230 V 24 V
ET-4D2 315000 315004 315001 315005 315002 315006 315008 315009
ET-4DA2 317000 317004 317001 317005 317002 317006 317008 317009

Features
Number of Transmitters: 1 to 4 (4-20 mA)
Signal Processing: Microcontroller with A/D-Converter
Alarm/Fault/Indication:  Illuminated graphic display (160 x 80) for indication of measured
values, messages and alarms
 12 (3 x 4) red LEDs for alarm indication
 LEDs for indication of channel fault (4 x yellow), channel opera-
tion (4 x green), operation (1 x green), device fault (1 x yellow)
User Interface:  Menu guided system via graphic display and keys
 Completely configurable at device, no tools needed
 3 password protected servicing levels
Alarm Evaluation:  3 freely adjustable alarm levels per channel
 Monitoring: over-scale, under-scale or min/max
 Latching of each alarm configurable
Relays, potential free:  12 change-over contacts 230 V / 5 A (total power consumption:
max. 10 A), freely configurable with Alarm 1 to 3 and transmitter
fault
 2 change-over contacts 230 V / 5 A for maintenance mode and
device fault
Additional Features:  Adjustment of zero point and sensitivity of measuring channels
 RS 232/RS 485-Interface for communication with external pe-
riphery (PC or PLT-System)
 Key switch function (maintenance mode)
 Horn reset
 Alarm reactivation
 4 Digital inputs, potential free
 4 Analog outputs 4-20 mA/0-10 V, potential free (only ET-4DA2)
Operation Temperature: -10 °C to +40 °C, Humidity: non condensing
Storage Temperature: -25 °C to +60 °C, Humidity: non condensing
Options: ProfiBus, ModBus, Ethernet connection, Visualisation ET-View, …
(with integrated ProfiBus DP-Module: ET-4DP2, 24 V (Art. 315010))

ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]

ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 1 von 4
Gas Detection Control Unit ET-4D(A)2

Electrical Features
Power Supply: ▪ 230 V AC (85…264 V AC, 47…440 Hz / 120…340 V DC) or
▪ 24 V DC
Power Consumption: 45 W (230 V AC: max. 0.2 A , 24 V DC: max 2 A)
Conformity
EC-Directives:   II (3)G
2014/34/EU (ATEX), 2014/30/EU (EMV), 2014/35/EU (LVD)
Type Test: BAM 10 ATEX 0301 X (Art. 315000, 317000, Software ET481118,
acc. to Standards EN 60079-29-1:2007, EN 50271:2001)
Measuring Function: Designed acc. to
 DIN EN 60079-29-1
 DIN EN 45544-1 to DIN EN 45544-3
 DIN EN 50104
I/O-Connection Scheme

Internal
used
0V 24V
PE N L

Relay 1 Relay 5 Relay 9 SLD SLD E1+


E1-

Digital inputs
GND GND
1 2 3 lin lin E2+
+24V +24V E2-

CH1

CH3
A A E3+
24V 24V 24V

Fault
for external devices (e.g. horn)

L L L

B B E3-
(Relay 13) I out - E4+
Relay 2 Relay 6 Relay 10 I out -
I out + I out + E4-
SLD SLD
GND GND
0V 0V 0V
N N N

Maintenance lin lin


CH2

(Relay 14)
+24V
A CH4 +24V
A
Relay 3 Relay 7 Relais 11
B B RS
I out - I out - 485
PE PE PE

I out + I out + AB

+24V

GND
Relais 4 Relais 8 Relais 12
0V 24V

CH1-4:Measuring channel 1-4


PE N L

SLD PE (or Shielding)


GND Ground
Common

Iin 4 to 20 mA Transmitter signal


Close
Open

Pwr supply +24 V Power supply


230 V AC Transmitter
or A, B RS 485-Interface
24 V DC I out-,+ Analog output ( ET4-DA2 only)
(Smoke detectotrs acc. manual)

Relays Configuration
Relay 1 to 12: Freely configurable at device (Alarm 1 to 3, fault, reset able, open-
circuit/closed-circuit principle, logic linking AND/OR)
Relay 13: Device fault
Relay 14: Maintenance mode
Standard Settings: Relay 1 to 4: 1. Alarm of channels 1 to 4
Relay 5 to 8: 2. Alarm of channels 1 to 4
Relay 9: 1. Common Alarm of channels 1 to 4
Relay 10: 2. Common Alarm of channels 1 to 4
Relay 11: 3. Common Alarm of channels 1 to 4
Relay 12: Common fault of channels 1 to 4
All relays: closed-circuit principle, non reset able
(deviations possible when used in ExTox IMC, in special versions or
in combination with smoke detectors)
Option: Adjustment acc. to customer requirements:
 on factory-sided delivery
 at location by ExTox-Service

ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]

ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 2 von 4
Gas Detection Control Unit ET-4D(A)2

Type Wall Mounted

120 mm 240 mm
Bohrlochabstand: 226 mm

Bohrlochabstand: 146 mm
160 mm

194 mm
Type: Wall mounted housing for fix installation
Dimension (WxHxD): 240 mm x 194 mm x 120 mm
Material: Housing ABS
Enclosure Rating: IP 54
Cable Gland: ▪ 1 x M20 x 1.5 (diameter of cable 7-13 mm)
▪ 10 x M16 x 1.5 (diameter of cable 5-10 mm)
Installation Hints: ▪ Lead-through for mounting screws: d= 4.5 mm
▪ The housing can be opened for installation and maintenance purposes by
tucking up the cover. Provide free space above the housing.

Type DIN-Rail

130 mm 240 mm
40 mm

Hutschiene
Abstand: 86 mm
160 mm

194 mm
Hutschiene

Type: Identical to wall mounted type, but additionally with adapters for installation
on Standard DIN-Rails 35 mm x 7.5 mm
Installation Hints: ▪ Adapters are mounted on the back plate to snap-in the housing on the
DIN-rails. The connection can easily be loosened by a screw-driver. Pull
up the nozzle of the adapter.
▪ The housing can be opened for installation and maintenance purposes by
tucking up the cover. Provide free space above the housing.

ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]

ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 3 von 4
Gas Detection Control Unit ET-4D(A)2

Type Control Panel

296 mm

Abstand Bohrungen: 175 mm


196 mm

187 mm
10,5 mm

10,5 mm
Abstand Bohrungen: 275 mm
287 mm

Type: Installation in control panels or cabinets. Indication/Controller to be installed


in front cut-out. I/O-clamp terminal can freely be positioned on mounting
places.
Dimension (WxHxD): 296 mm x 196 mm x 80 mm (Indication/Controller)
240 mm x 160 mm x 40 mm (I/O-clamp terminal)
Material: Front lid: Polystyrene with double front seal
Enclosure Rating: IP 54 (front lid)
Installation Hints: ▪ Lead-through for mounting screws: d= 3 mm
▪ I/O-clamp terminal for remote installation inside the cabinet:
Bore holes: 226 mm x 146 mm,
Connection cable: ca. 1.8 m (special length on demand)
Options: ▪ I/O-clamp terminal not remote: installation is done on the backside of
the controller PCB. Depth of complete device: ca. 160 mm
▪ Front lid for adaption to customer specific dimensions of control panel
cut-out

Type 19''-Rack
Type: Identical to Control Panel Type, but built-in 19''-frame rack
Dimension (WxHxD): 482.6 mm (84 TE) x 265.35 mm (6 HE) x 185 mm

(Subject to technical changes)

ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]

ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 4 von 4