ET-4D A 2 e
ET-4D A 2 e
Features
Number of Transmitters: 1 to 4 (4-20 mA)
Signal Processing: Microcontroller with A/D-Converter
Alarm/Fault/Indication: Illuminated graphic display (160 x 80) for indication of measured
values, messages and alarms
12 (3 x 4) red LEDs for alarm indication
LEDs for indication of channel fault (4 x yellow), channel opera-
tion (4 x green), operation (1 x green), device fault (1 x yellow)
User Interface: Menu guided system via graphic display and keys
Completely configurable at device, no tools needed
3 password protected servicing levels
Alarm Evaluation: 3 freely adjustable alarm levels per channel
Monitoring: over-scale, under-scale or min/max
Latching of each alarm configurable
Relays, potential free: 12 change-over contacts 230 V / 5 A (total power consumption:
max. 10 A), freely configurable with Alarm 1 to 3 and transmitter
fault
2 change-over contacts 230 V / 5 A for maintenance mode and
device fault
Additional Features: Adjustment of zero point and sensitivity of measuring channels
RS 232/RS 485-Interface for communication with external pe-
riphery (PC or PLT-System)
Key switch function (maintenance mode)
Horn reset
Alarm reactivation
4 Digital inputs, potential free
4 Analog outputs 4-20 mA/0-10 V, potential free (only ET-4DA2)
Operation Temperature: -10 °C to +40 °C, Humidity: non condensing
Storage Temperature: -25 °C to +60 °C, Humidity: non condensing
Options: ProfiBus, ModBus, Ethernet connection, Visualisation ET-View, …
(with integrated ProfiBus DP-Module: ET-4DP2, 24 V (Art. 315010))
ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]
ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 1 von 4
Gas Detection Control Unit ET-4D(A)2
Electrical Features
Power Supply: ▪ 230 V AC (85…264 V AC, 47…440 Hz / 120…340 V DC) or
▪ 24 V DC
Power Consumption: 45 W (230 V AC: max. 0.2 A , 24 V DC: max 2 A)
Conformity
EC-Directives: II (3)G
2014/34/EU (ATEX), 2014/30/EU (EMV), 2014/35/EU (LVD)
Type Test: BAM 10 ATEX 0301 X (Art. 315000, 317000, Software ET481118,
acc. to Standards EN 60079-29-1:2007, EN 50271:2001)
Measuring Function: Designed acc. to
DIN EN 60079-29-1
DIN EN 45544-1 to DIN EN 45544-3
DIN EN 50104
I/O-Connection Scheme
Internal
used
0V 24V
PE N L
Digital inputs
GND GND
1 2 3 lin lin E2+
+24V +24V E2-
CH1
CH3
A A E3+
24V 24V 24V
Fault
for external devices (e.g. horn)
L L L
B B E3-
(Relay 13) I out - E4+
Relay 2 Relay 6 Relay 10 I out -
I out + I out + E4-
SLD SLD
GND GND
0V 0V 0V
N N N
(Relay 14)
+24V
A CH4 +24V
A
Relay 3 Relay 7 Relais 11
B B RS
I out - I out - 485
PE PE PE
I out + I out + AB
+24V
GND
Relais 4 Relais 8 Relais 12
0V 24V
Relays Configuration
Relay 1 to 12: Freely configurable at device (Alarm 1 to 3, fault, reset able, open-
circuit/closed-circuit principle, logic linking AND/OR)
Relay 13: Device fault
Relay 14: Maintenance mode
Standard Settings: Relay 1 to 4: 1. Alarm of channels 1 to 4
Relay 5 to 8: 2. Alarm of channels 1 to 4
Relay 9: 1. Common Alarm of channels 1 to 4
Relay 10: 2. Common Alarm of channels 1 to 4
Relay 11: 3. Common Alarm of channels 1 to 4
Relay 12: Common fault of channels 1 to 4
All relays: closed-circuit principle, non reset able
(deviations possible when used in ExTox IMC, in special versions or
in combination with smoke detectors)
Option: Adjustment acc. to customer requirements:
on factory-sided delivery
at location by ExTox-Service
ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]
ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 2 von 4
Gas Detection Control Unit ET-4D(A)2
120 mm 240 mm
Bohrlochabstand: 226 mm
Bohrlochabstand: 146 mm
160 mm
194 mm
Type: Wall mounted housing for fix installation
Dimension (WxHxD): 240 mm x 194 mm x 120 mm
Material: Housing ABS
Enclosure Rating: IP 54
Cable Gland: ▪ 1 x M20 x 1.5 (diameter of cable 7-13 mm)
▪ 10 x M16 x 1.5 (diameter of cable 5-10 mm)
Installation Hints: ▪ Lead-through for mounting screws: d= 4.5 mm
▪ The housing can be opened for installation and maintenance purposes by
tucking up the cover. Provide free space above the housing.
Type DIN-Rail
130 mm 240 mm
40 mm
Hutschiene
Abstand: 86 mm
160 mm
194 mm
Hutschiene
Type: Identical to wall mounted type, but additionally with adapters for installation
on Standard DIN-Rails 35 mm x 7.5 mm
Installation Hints: ▪ Adapters are mounted on the back plate to snap-in the housing on the
DIN-rails. The connection can easily be loosened by a screw-driver. Pull
up the nozzle of the adapter.
▪ The housing can be opened for installation and maintenance purposes by
tucking up the cover. Provide free space above the housing.
ExTox Gasmess-Systeme GmbH ● Max-Planck-Straße 15 a ● 59423 Unna (Germany) ● Tel. +49 2303 33 247-0 ● Fax +49 2303 33 247-10
Internet: www.extox.de ● mail to: [email protected]
ET-4D(A)2_e_2016-06-07.docx,07/06/2016Seite 3 von 4
Gas Detection Control Unit ET-4D(A)2
296 mm
187 mm
10,5 mm
10,5 mm
Abstand Bohrungen: 275 mm
287 mm
Type 19''-Rack
Type: Identical to Control Panel Type, but built-in 19''-frame rack
Dimension (WxHxD): 482.6 mm (84 TE) x 265.35 mm (6 HE) x 185 mm