0% found this document useful (0 votes)
146 views6 pages

Transformadores Nucleo Cerrado

This document provides specifications for several ring/busbar type current transformers for currents ranging from 100A to 1000A. It includes details on standards compliance, technical specifications, accuracy classes, voltage and frequency ratings, temperature ranges, insulation standards, and dimensional specifications. An example order is provided for a SF 74/40 current transformer with a primary current of 500A, secondary current of 5A, and accuracy class of 0.5S.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
146 views6 pages

Transformadores Nucleo Cerrado

This document provides specifications for several ring/busbar type current transformers for currents ranging from 100A to 1000A. It includes details on standards compliance, technical specifications, accuracy classes, voltage and frequency ratings, temperature ranges, insulation standards, and dimensional specifications. An example order is provided for a SF 74/40 current transformer with a primary current of 500A, secondary current of 5A, and accuracy class of 0.5S.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

CURRENT TRANSFORMERS

SF 62/30
For currents from 100A to 800A.
Type: ring/busbar
Standards: acc. to BS 3938, EN 60044-1.
Technical data:
Class of accuracy: 0.2S…0,5S (see table).
Rated burden: max. 10 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5A
Security factor: FS 5 FS10
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class:E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0.

Rated Type: SF 62 / 30 Rated Type: SF 62 / 30


primary Acc. Busbar hole 31x11 mm (see fig.) primary Acc. Busbar hole 31x11 mm (see fig.)

current cl. Rated burden (VA) current cl. Rated burden (VA)

In 1 1.5 2.5 3.75 5 7.5 In 1,5 2,5 3,75 5 7,5 10 15

100 A 0,2S  300 A 0,2S 

0,5S  0,5S  

125 A 0,2S  400 A 0,2S 


0,5S  0,5S 

150 A 0,2S  500 A 0,2S  

0,5S  0,5S  

200 A 0,2S  600 A 0,2S  

0,5S  0,5S  

250 A 0,2S   750 A 0,2S  

0,5S   0,5S  

800 A 0,2S 
 Ni-Fe  Si-Fe
0,5S  
Dimension in mm
Order specification:
-Ring-type current transformer.
-Class of accuracy: 0.5S
-Rated primary current: 300 A.
-Rated secondary current 5 A
-Rated burden 2,5 VA
-Busbar dimension: 30x10 mm.
SF 62/30 300/5A Cl. 0,5S 2,5VA

Weight:200…380gr
CURRENT TRANSFORMERS
SF 62/40
For currents from 200A to 750A.
Type: ring / busbar
Standards: acc. to BS 3938, EN 60044-1.
Technical data:
Class of accuracy: 0.2S …0,5S (see table).
Rated burden: max. 5 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5 A
Security factor: FS 5
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class: E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0.

Rated Type: SF 62 / 40 Rated Type: SF 62 / 40

primar Acc. Busbar hole 40,5x11 mm (see fig.) primary Acc. Busbar hole 40,5x11 mm
y

current cl. Rated burden (VA) current cl. Rated burden (VA)

In 1 1,5 2,5 3,75 5 In 1,5 2,5 3,75 5 7,5 10

200 A 0,2S  500 A 0,2S 

0,5S  0,5S  

250 A 0,2S  600 A 0,2S  

0,5S  0,5S  

300 A 0,2S  750 A 0,2S  

0,5S   0,5S  

400 A 0,2S  

0,5S 
Dimension in mm
 Ni-Fe  Si-Fe

Order specification:
-Ring-type current transformer.
-Class of accuracy: 0.2S
-Rated primary current: 600 A.
-Rated secondary current 5A
-Rated burden: 3,75 VA
-Busbar dimension: 40x10 mm.

SF 62/40 600/5A Cl. 0,2S 3,75VA

Weight:180…250gr
CURRENT TRANSFORMERS
SF 74/40
For currents from 200A to 1000A
Type: ring / busbar
Standards: acc. to BS 3938, EN 60044-1
Technical data:
Class of accuracy: 0.2S 0,5S (see table).
Rated burden: max. 15 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5 A.
Security factor: FS 5 FS10
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class: E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0.

Type: SF 74/40 Type: SF 74/40


Rated Rated
primary Acc. Busbar hole 41x12,5 mm primary Acc. Busbar hole 41x12,5 mm (see fig.)
current cl. Rated burden (VA) current cl. Rated burden (VA)
In 1 1,5 2,5 3,75 5 In 1,5 2,5 3,75 5 7,5 10 12,5 15

200 A 0,2S   500 A 0,2S 

0,5S   0,5S 

250 A 0,2S  600 A 0,2S  

0,5S  
0,5S  

750 A 0,2S 
300 A 0,2S  
0,5S  
0,5S  
800 A 0,2S  
400 A 0,2S  
0,5S   
0,5S  
1000 A 0,2S  

0,5S   
 Ni-Fe  Si-Fe

Order specification:
-Ring-type current transformer
-Class of accuracy: 0,5S
-Rated primary current: 500 A.
-Rated secondary current: 5 A.
-Rated burden: 3,75 VA
-Busbar dimension: 40x12,5 mm

SF 74/40 500/5 A Cl. 0,5S 3,75VA

Weight:400…500gr
CURRENT TRANSFORMERS
SF 74/50
For currents from 250 A to 1000 A.
Type: ring / busbar
Standards: acc. to BS 3938, EN 60044-1
Technical data:
Class of accuracy: 0.2S …0.5S (see table).
Rated burden: max. 15 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5 A.
Security factor: FS 5 FS10
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class: E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0

Rated Type: SF 74/50


primary Acc. Max. busbar hole 51x12,5 mm (see fig)
current class Rated Burden [VA]

In 1 1.5 2.5 3.75 5 7.5 10 12.5 15

0,2S 
250 A
0,5S 
0,2S 
300 A
0,5S   
0,2S  
400 A
0,5S 

0,2S 
500 A
0,5S 

0,2S  
600 A
0,5S  

0,2S 
750 A
0,5S   

0,2S 
800 A
0,5S  

0,2S 
1000 A
0,5S   
 Ni-Fe  Si-Fe
Order specification: Dimension in mm

-Ring-type current transformer


-Class of accuracy: 0,5S
-Rated primary current: 400 A.
-Rated secondary current: 5 A.
-Rated burden: 2,5 VA
-Busbar dimension 50x12,5 mm or 41

SF 74/50 400/5 A Cl. 0,5S 2, 5VA

Weight: 350…450gr
CURRENT TRANSFORMERS

SF 140/100
For currents from 500 A to 3000 A
Tpye: ring / busbar
Standards: acc. to BS 3938, EN 60044-1

Technical data:
Class of accuracy: 0,2S … 0,5S (see table).
Rated burden: max. 20 VA (see table).
Rated voltage: 720 V.
Rated frequency: 50-60 Hz.
Rated sec. current: 5 A.
Security factor: FS 5 FS10
Working temperature range: -20 … +45°C.
High voltage test: 4 kVeff, 50 Hz, 1 min.
Insulation class: E (max. 120°C)
Protection: IP 00.
Case: non-flammable plastic, UL 94 V-0.

Outline drawing of SF 140/100


104

Dimensions in mm.

53

155
 86 31 51 61 71 81

74
51

 6.6 61
71
81
37 101
59 121
73 140

Weight: 900...1100gr

Different types of MAK140/100 current transformers see table on next page


CURRENT TRANSFORMERS

Table with different types of SF 140/100 current transformers.


Rated Type: SF 140/100
primary Acc. Max. busbar hole dimension: 101x31 mm or  86 mm
current class (see outline drawing)
Rated burden (VA)
In 1.5 2.5 3.75 5 7.5 10 12.5 15 20

400 A 0,2S

0,5S 

500 A 0,2S 

0,5S 

600 A 0,2S 

0,5S  

750 A 0,2S 

0,5S 

800 A 0,2S 

0,5S 

1000 A 0,2S  

0,5S  

1200 A 0,2S  

0,5S   

1250 A 0,2S  

0,5S   

1500 A 0,2S  

0,5S   

1600 A 0,2S  

0,5S   

2000 A 0,2S  

0,5S   

2500 A 0,2S  

0,5S    

3000 A 0,2S  

0,5S    

 Si-Fe
Order specification: SF 140/100 2500/5 A Cl. 0,5S 20VA
-Ring-type current transformer.
-Class of accuracy: 0.5S
-Rated primary current: 2500 A.
-Rated secondary current: 5 A.
-Rated burden: 20 VA
-Busbar dimension: 2x100x10 mm or  86 mm