Power Systems Lab Manual
Power Systems Lab Manual
Aim: To determine Sequence Impedance i.e Positive, Negative and Zero-Sequence Impedance of a 3-
Phase Transformer.
Apparatus Required:
Theory:The sequence Impedances of an equipment or a component of power system are the positive,
negative and zero sequence impedances. They are defined as follows:
The positive sequence impedance of an equipment is the impedance offered by the equipment to
the flow of positive sequence currents.
The negative or zero sequence impedance of the equipment is the impedance offered by the
equipment to the flow of corresponding sequence current.
For a 3-Phase symmetrical static circuit without internal voltages like transformers and
transmission lines, the impedances of the currents of any sequence are the same in the three
phases; also the currents of a particular sequence will produce drop of the same sequence or a
voltage of a particular sequence will be produce current of the same sequence only, which means
there is no, mutual coupling between the sequence networks.
Since for a static device, the sequence has no significance, the positive and negative sequence
impedances are equal; the zero sequence impedance which includes the impedance of the return
path through the ground, in the general case, is different from the positive and negative sequence
impedance.
Procedure:
Calculations:
=10 ohms
=4.77 ohms
=8.98 ohms
Observation:
Calculations:
=5.76 ohms
=6.36 ohms
= i2.69 ohms
Precautions:
1. Avoid loose and wrong connections
2. Ensure that the auto transformer is at minimum position before powering the circuit.
3. Do not exceed the rated current of transformer while conduction experiment.
Result:
Aim: To determine experimentally Positive, Negative and Zero Sequence Impedances of 3-Phase
Alternators.
Apparatus Required:
The sequence Impedances of an equipment or a component of power system are the positive, negative
and zero sequence impedances. They are defined as follows:
The positive sequence impedance of an equipment is the impedance offered by the equipment to
the flow of positive sequence currents.
The negative or zero sequence impedance of the equipment is the impedance offered by the
equipment to the flow of corresponding sequence current.
In a symmetrical rotating machines the impedances met by armature currents of a given sequence
are equal in the three phases. Since by definition the inductance, which forms a part of
impedances, is the flux linkages per ampere, it will depend up on the phase order of the sequence
current relative to the direction of rotation of the rotor; positive, negative and zero sequence
impedances are unequal in the general case.
In fact for a rotating machine, the positive sequence impedance varies, having minimum value
immediately following the fault and then increases with time until steady state conditions are
reached when the positive sequence impedance corresponds to the synchronous impedance.
The positive sequence impedance depends up on the working of the machine, i.e., whether it is
working under sub transient, transient or steady state condition. The impedance under steady
state condition is known as the synchronous impedance measured by the well known open circuit
and short circuit tests.
For the measurement of Negative sequence impedance, the machine is driven at rated speed and
a reduced voltage is applied to circulate approximately the rated current. It is to be noted here
that since negative sequence currents flow in this case, there is possibility of hunting which will
results in oscillation of the pointer of the ammeter. The mean reading may be taken.
The Negative Sequence Impedance is given by
Zero Sequence Impedance is quite variable and depends upon the distribution i.e., the pitch and
breadth factors. If the windings were uniformly distributed so that each phase produced a
sinusoidal distribution of the mmf then the superposition of the three phases with equal
instantaneous currents cancel each other and produce zero filed and consequently zero reactance
except for slot and end-connection fluxes. In general zero sequence impedance is much smaller
than positive and negative sequence impedances. The machine must, of course, be star connected
for otherwise the term zero sequence has no significance as no zero- sequence currents can flow.
The machine is at standstill and a reduced voltage is applied. The zero sequence impedance
Procedure:
Tabular Column:
1. Keeping the previous connections unchanged replace voltmeter by ammeter and short the
other two phase with neutral as shown in the circuit diagram.
2. Run the Alternator set at rated speed and note down the excitation current with respect to
short circuit current.
3. Plot the curve filed current versus Short circuit current on the same graph drawn for Open
circuit test.
Tabular Column:
Model Graph:
Calculations:
Tabular Column:
Calculations:
Sinθ=
Tabular Column:
Calculations:
Precautions:
1. Avoid loose and wrong connections
2. Ensure that the auto transformer is at minimum position before powering the circuit.
3. Do not exceed the rated current of transformer while conduction experiment.
Results:
Aim: To determine the Sequence Impedances of Alternator by creating different faults(without fault
impedance).
Apparatus:
Shunt type faults involves power conductor or conductors-to-ground or short circuit between
conductors. When circuits are controlled by fuses or any device which does not open all three phases,
one or two phases of the circuit may be opened while the other phases or phase is closed. These are
called series type of faults. These faults may also occur with one or two broken conductors. Shunt faults
are characterized by increasing in current and fall in voltage and frequency whereas series faults are
characterized by increase in voltage and frequency and fall in the faulted phases.
Of these, the first three are the unsymmetrical faults as the symmetry is disturbed in one or two
phases. The method of symmetrical components will be utilized to analyze the unbalancing in the
system. The 3-phase fault is a balanced fault which could also be analyzed using symmetrical
components.
The series faults are classified as:
These faults also disturb the symmetry in one or two phases and are, therefore, unbalanced faults.
The method of symmetrical components can be used for analyzing such situations in the system.
Procedure:
Tabulation:
Model Calculations:
=
From LL Fault:
= --------------------(1)
From LG Fault:
100+ =58.57,
Z1*Z0+Z1Z2+Z2Z0=6.67*(Z2+Z0)-------------------------(2)
Result: Various faults have been created in an unloaded Alternator and Sequence Impedances can be
determined.
Aim:
To determine A,B,C,D constants of transmission lines for R=4 OHMS, L=80mH, C=0.44 µf.
Apparatus:
Procedure:
THEORITICAL CALCULATIONS:
Z=[R2+(L)2]1/2
B=
=
Observation:
RESULT:
Apparatus required:
Theory:
The oil transformer kit is used to determine the dielectric strength of oil these are
generally used in transformers. It contains two electrodes of a small gap between there
when ever break down voltage occurs there will be a spark is observed at the high voltage
side of the transformer. For calibration the gap in between the two electrodes is 4 mm. the
voltage that is obtained when flash over occurs is rapidly applied voltage.
Oil test set is basically consists of a double wound high voltage transformer with
the H.T. end brought out and terminated on an epoxy insulation. The
lower end of the H.T winding is at earth potential and is also brought out. The
intermediate circuitry included in series with the primary of H.T transformer, if the current
through the test coil exceeds a predetermined value.
The low voltage winding of the main transformer is rated for 230 V or as specified
.It is energized by means of an auto transformer through a fuse link and an intermediate
contactor /relay, the provision of an auto transformer enables gradual application of high
voltage to the oil under test.
A voltmeter is provided on the panel to indicate the applied high voltage. The
voltmeter is connected on the low voltage side of the main transformer but it is calibrated
to read H.T voltage directly .When the failure of the test oil occurs, the supply to the
voltmeter is maintained although the supply to the H.V transformer is instantly cut off.
The voltmeter therefore indicates the voltage at which the oil under test has failed.
(1
The test method consists of subjecting the oil contained in a special apparatus to
an AC 2.5
electric field with continuously increasing voltage till the oil breaks down. The -
electrodes 13
are made of brass-bronze or stainless steel. The brass is an alloy of copper and zinc m
and m
the bronze is an alloy of copper and nickel. The polished electrodes are spherical dia
meter). The electrodes are mounted 2.5 cm apart with an accuracy of 0.1 mm.
Procedure:
1. This test consists of applying to the electrodes an increasing ac voltage of frequency
40-60 Hz, the rate of increase of voltage being uniform and equal to 2kv/sec, starting
from zero up to the value producing breakdown.
2. The test shall be carried out six times on the same cell filling.
3. The first application of voltage is made as quickly as possible after the cell has been
filled, provided there are no longer air bubbles and the oil and at the latest 10 min after
filling, after each break down.
4. The oil is gently stirred between the electrodes by means of a clean, dry glasses
avoiding as far as possible production of air bubbles for the subsequent flue tests the
voltage is re applied one minute after the disappearance of air bubbles that may have
been formed if the observation of the disappearance of air bubbles.
Parts:
1. Main switch
2. Fuse
3. Main pilot lamp L1
4. HT off push button
5. Motor control switch
6. HT on pilot lamp
7. Kilo voltmeter
8. L & N reserve pilot lamp
9. Earth open pilot lamp
Observation:
Table-6.2: Dielectric strength of transformer oil
Average=
Dielectric strength=
Precautions:
1. In motoring mode, the coupling between motor and autotransformer should be
properly done.
2. In manual mode, motor and autotransformer should be recouped.
Result:
Hence the dielectric strength of oil is tested using HT testing kit in manual mode.
Dielectric strength=
Objective:
To Calibrate the tong tester and determine the Percentage of error
Apparatus required:
Sl. No. Name of the apparatus Type Range Quantity
1 Auto transformer 1-Ф 230V/(0-270)V, 8A 1
2 Current transformer --- Precision- 10/5 , 10/1 1
3 Voltmeter DMM (0-600) V 1
4 Ammeter DMM (0-20A) 1
5 TongTester DMM (0-400A) 1
THEORY:
In Power system it is often necessary to measure the high currents in current carrying bus
bars (or) feeders to know the temperature, heating effect and loading permitted.
In many cases, however, it is difficult to find a suitable location where a practical circuit
can be conveniently broken for measuring current and, of course, a ‘live’ circuit will need
to be de-energised before we can break the circuit to insert the ammeter. This requires the
load to be temporarily taken out of service while the ammeter is inserted, which might not
be convenient or practical.
For alternating current, these difficulties can be overcome by using an instrument called a
clamp-on ammeter or clamp-on multimeter (sometimes known as ‘tong testers’). The
accuracy of a current reading taken with a clamp-on ammeter will not be as accurate as a
conventional ammeter but, usually, a great degree of accuracy is unnecessary for those
applications where such an ammeter is used. A clamp-on ammeter can, of course, only
measure alternating current flowing in an individual conductor (e.g the line or the neutral
conductor); it cannot measure the currents flowing in a multicore cable, because the
magnetic fields set up by currents flowing in opposite directions in, say, the line and
neutral conductors act to cancel each other! Similarly, the phasor-sum of identical line
currents in a three-phase cable is zero.
PROCEDURE:
1. Connect the circuit as shown in the Figure 7.2.
2. Apply 1-phase 230 V, 50Hz AC supply to variac.
3. Now connect the tong tester (Clamp on meter).
4. Now by using the variac apply different voltages and note down the corresponding
tong tester and ammeter reading.
5. Calculate the percentage error.
Observation:
Sl. Applied current Voltmeter reading Tong tester reading Error(%) Calibration
No (A) (V) (A)
1
2
Result:
Calibration and % error are calculated for given tong tester.
Aim: To determine transient stability of single machine connected to infinite bus by point by
point method
Apparatus: MATLAB software with PC compatibility
THEORY:
Stability of power system is its ability to return to normal or stable operating conditions after
having been subjected to some form of disturbance. Increase in load is a kind of disturbance.
Causes for disturbances are
Change in load
Loss of excitation
Switching operation
Fault conditions
PROBLEM:
A 20 MVA ,50 HZ generator delivers 18MW over a double circuit line to an infinite bus. The
generator has kinetic energy of 2.52MJ/MVA at rated speed. The generator transient
reactance is X1d =0.35PV. Each transmission circuit has R=0 and reactance of 0.2Pu on a
20MVA base. |E1|=1.1Pu and infinite bus voltage(v)= 1.0<00. A 3-ø short circuit occurs at
midpoint of one of transmission lines. Plot swing curve for 0.25cycles.
CALCULATION:
Base MVA =
Inertia constant M(Pu) = H/180f = /elec.degree
Pre fault:
XL=
Pe1`=pmax1sinδ
=
Pre fault power transfer=
Initial power angle is given by
δ0 =
During fault:
X11 =
Pe11 = pmax11 sin δ
=
Past fault:
X111 = Pe111 = pmax111 sin δ
=
Let us choose ∆t = 0.05S
Pa (n-1) = Pm - Pmax sin δ (n-1)
δn =δn-1 +∆δn
PROGRAM:
APPLICATIONS:
Stability of power system is done by some sessions. So, these sessions need this sort of
analysis for fast operation.
Torque (or) load angle adjustment (or) control uses these in stability (or) transient
analysis of the power system.
TABULAR FORM:
t(sec) Pmax(pu) sinδ Pe= Pmsinδ(Pu) Pa=0.9-Pe (∆t)2/m Pa ∆δ Δ
(Pu) (deg) (deg)
RESULT:
Swing curve for the given problem is observed using MATLAB software program
Swing equation, M d2δ/dt = Pa
8. LOAD FREQUENCY CONTROL WITHOUT CONTROL
OBJECTIVE:
To find frequency deviation for a single area case without control.
OUTCOME:
After doing this experiment student will be able to student will be able to determine dynamic
response of frequency for a step change in load
Fig: 8.4. Block diagram model of load frequency control (isolated powers system)
Dynamic response: To obtain the dynamic response giving the change in frequency as function
of the time for a step change in load, we must obtain the Laplace inverse of ∆F(s). The
characteristic equation being of third order, dynamic response can only be obtained for a specific
numeric case. However the characteristic equation can be approximated for first order by
examining the relative magnitudes of time constants involved. Typical values of the time
constants of load frequency control system are related as, Typically Tg = 0.4 Sec, Tt = 0.5 Sec
and Tps = 20 Sec, Kt=0.1.
First order approximation block diagram: Letting Tsg = Tt = 0 Sec and Ksg*Kt = 1,
complete block diagram of single area system reduces to the Figure 8.5.
Fig: 8.5. First order approximate block diagram of load frequency control of an isolated area
Dynamic response of change in frequency for a step change in load with ∆P D = 0.01 pu, Tg = 0.4
Sec, Tt = 0.5 Sec, Tps = 20 Sec, Kps = 100 and R = 3, Kg=10 is given in the Figure 3.6.
Theoretical calculations:
Δf (t)=[-R*KPS /(R+KPS)]*[1-exp(-t/Tps(R/(R+Kps)))]* ΔP
Steady state frequency drop is =
Proportional plus integral control: It is seen that with the speed governing system installed on
each machine, the steady load frequency characteristics for a given speed changer setting has
considerable droop. System frequency specifications are rather stringent and, therefore, so much
change in frequency cannot be tolerated. In fact, it is expected that the steady change in
frequency will be zero. While steady state frequency can be brought back to the scheduled value
by adjusting speed changer setting, the system could undergo intolerable dynamic frequency
changes with changes in load. It leads to the natural suggestion that the speed changer setting be
adjusted automatically by monitoring the frequency changes. For this purpose, a signal from ∆f
is fed through an integrator to the speed changer resulting in block diagram configuration shown
in the Figure 9.1. The system now modifies to a proportional plus integral controller, which, as is
well known from control theory, gives zero steady state error, i.e. ∆f| steady state = 0.
Fig: 9.1. Proportional plus integral load frequency control
Where Ki – Gain of integral controller.
The signal ∆Pc(s) generated by the integral control must be of opposites sign to ∆F(s) which
accounts for negative sign in the block for integral controller.
ΔF(S)= [-S*KPS*R*(1+S* τsg)(1+ S* τt)/(s*(1+ S* τps)(1+ S* τsg) *(1+ S* τt)R+ KPS*)(S+ R* Kt))]* ΔPD/S
Δf│steady state = S*ΔF(s)=0
QUESTIONS FOR SELF ASSESSMENT:
1. What is area control error?
2. Why negative feedback is given for integral controller?
3. How can we improve the dynamic response of a single area system with controller in
terms of speed of response?
10.ECONOMIC LOAD DISPATCH WITHOUT LOSSES
OBJECTIVE:
To find economic dispatch of generation of the given set of generators for the given
power demand using Lambda iteration method without considering transmission line loss.
OUTCOME:
Student will be able to determine economic dispatch of generation of the given set of
generators for the given power demand using Lambda iteration method without
considering transmission line loss.
Software used: MATLAB/SIMULINK
THEORY:
Power is allowed to vary within certain limits so as to meet a particular load demand with
minimum fuel cost. This is called the optimal power flow (OPF) problem. The OPF is
used to optimize the power flow solution of large scale power system. This is done by
minimizing selected the same distance from the Centre of loads and their fuel costs are
different. Also under normal operating conditions, the generation capacity is more than
the total load demand and losses. Thus, there objective functions while maintaining an
acceptable system performance in terms of generator capability limits and the output of
the compensating devices. The simplest economic dispatch problem is the case when
transmission line losses are neglected. This is the problem model does not consider
system configuration and line impedances. In essence, the model assumes that the system
is only one bus with all generation and loads connected to it as shown in figure below
Since transmission losses are neglected, the total demand PD is the sum of all generation.
A cost function Ci is assumed to be known for each plant. The problem is to find the realpower
generation for each plant such that the objective function as defined by the
equation,
is minimum, subject to the constraint,
Where, Ct is the total production cost, Ci is the production cost of ith plant, Pi is generation
of the ith plant, PD is the total demand and ng is the total number of despicable generating
plants.
A rapid solution is obtained by the use of the gradient method (Lambda iteration).
Let f(2) = PD
Expanding the left hand side of the above equation in Taylor’s series about an operating
point 2k and neglecting the higher-order terms result in,
Algorithm:
Result analysis:
Questions for self assessment:
1. What is economic load dispatch?
2. What is incremental production cost
3. How incremental production cost affects the economic dispatch?
4. Write the Lagrangian equation for economic load dispatch without considering
transmission line loss.
5. What could be the optimum value of incremental production cost for optimal
scheduling of generators?