0% found this document useful (0 votes)
878 views24 pages

X1 Boost User Manual 614.00392.016368679644974218947218417

Hybrid Inverter Manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
878 views24 pages

X1 Boost User Manual 614.00392.016368679644974218947218417

Hybrid Inverter Manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

X1 Series User Manual

3.0kw - 5.98kw

Solax Power Network Technology(Zhe jiang) Co,. Ltd.


Copyright Declaration
The copyright of this manual belongs to Solax Power Network Technology(Zhe jiang) Co,. Ltd.
Any corporation or individual should not plagiarize, partitially or fully copy (including
software,etc.), and no reproduction or distribution of it in any form or by any means. All rights
reserved. SolaX Power Network Technology (Zhe jiang) Co.,Ltd. reserves the right of final
interpretation.
614.00392.01
Contents

Contents
1 Note on this Manual 03
1.1 Scope of Validity 03
1.2 Target Group 03
1.3 Symbols Used 03

2 Safety 04
2.1 Appropriate Usage 04
2.2 Important Safety Instructions 06
2.3 Explanation of Symbols 09
2.4 EC Directives 10

3 Introduction 11
3.1 Basic Features 11
3.2 Terminals of the Inverter 11
3.3 Dimension 12

4 Technical Data 13
4.1 DC Input 13
4.2 AC Output 13
4.3 Efficiency, Safety and Protection 14
4.4 General Data 14

5 Installation 15
5.1 Check for Transport Damage 15
5.2 Packing Lists 15
5.3 Installation Precaution 16
5.4 Installation Steps 17
5.5 Connections of the Inverter 18
5.6 Run the Inverter 29

6 Operation Method 31
6.1 Control Panel 31
6.2 LCD Structure 32
6.3 LCD Operation 33
6.4 Indicator Information 37
01
Contents Notes on this Manual

7 Troubleshooting 40 1 Notes on this Manual


7.1 Troubleshooting 40
7.2 Routine Maintenance 43 1.1 Scope of Validity
This manual is an integral part of X1 Series, It describes the assembly,
installation, commissioning, maintenance and failure of the product. Please read
8 Decommissioning 44 it carefully before operating.
8.1 Dismantling the Inverter 44 X1-3.0-T-D(L/O) X1-3.3-T-D(L/O) X1-3.6-T-D(L/O) X1-4.2-T-D(L/O)
8.2 Packaging 44 X1-3.0-T-N(L/O) X1-3.3-T-N(L/O) X1.3.6-T-N(L/O) X1-4.2-T-N(L/O)
8.3 Storage and Transportation 44
X1-4.6-T-D(L/O) X1-5.0-T-D(L/O) X1-5.3-T-D(L/O) X1-5.98-T-D(L/O)
X1-4.6-T-N(L/O) X1-5.0-T-N(L/O) X1-5.3-T-N(L/O) X1-5.98-T-N(L/O)

Note: “3.0” means 3.0kW. ”T” means “double” MPPT strings.


“D” means with “DC Switch”, ”N” means without “DC Switch”. “L” means with
“LCD display”, ”O” means without “LCD display”.
X1-5.3-T-D/X1-5.3-T-N/ X1-5.98-T-D/X1-5.98-T-N are only for India.

Keep this manual at where is accessible all the time.

1.2 Target Group


This manual is for qualified electricians. The tasks described in this manual only
can be performed by qualified electricians.

1.3 Symbols Used


The following types of safety instructions and general information appear in this
document as described below:

DANGER!
“Danger” indicates a hazardous situation which, if not avoided,
will result in death or serious injury.

WARNING!
“Warning” indicates a hazardous situation which, if not avoided,
could result in death or serious injury.

CAUTION!
“Caution” indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.

NOTE!
“Note” provides tips that are valuable for the optimal
operation of your product.
02 03
Safety Safety

2 Safety ► Surge protection devices (SPDs) for PV installation

2.1 Appropriate Usage WARNING!


Over-voltage protection with surge arresters should be provided
The X1 Series are PV inverters which have two types (with screen interface and no when the PV power system is installed.
screen) for user to choose, both can convert the DC current of the PV generator into The grid connected inverter is fitted with SPDs in both PV
AC current and feed it into the public grid. Their differences are the control panel and input side and MAINS side.
the operation.
Lightning will cause a damage either from a direct strike or from surges due to a
nearby strike.
Induced surges are the most likely cause of lightning damage in majority or installations,
especially in rural areas where electricity is usually provided by long overhead lines.
Surge may be included on both the PV array conduction and the AC cables
leading to the building.
Specialists in lightning protection should be consulted during the end use application.
1 2 3 4

X1
Using appropriate external lightning protection, the effect of a direct lightning
X1
strike into a building can be mitigated in a controlled way, and the lightning
current can be discharged into the ground.
Installation of SPDs to protect the inverter against mechanical damage and
excessive stress include a surge arrester in case of a building with external
lightning protection system (LPS) when separation distance is kept.
LED LCD
To protect the DC system, surge suppression device (SPD type2) should be fitted
at the inverter end of the DC cabling and at the array located between the
inverter and the PV generator, if the voltage protection level (VP) of the surge
arresters is greater than 1100V, an additional SPD type 3 required for surge protection
for electrical devices.
To protect the AC system, surge suppression devices (SPD type2) should be
fitted at the main incoming point of AC supply (at the consumer’s cutout),
located between the inverter and the meter/distribution system; SPD (test
impulse D1) for signal line according to EN 61632-1.
X1 All DC cables should be installed to provide as short a run as possible, and positive
and negative cables of the string or main DC supply should be bundled
PV array
together. Avoid creating loops in the system. This requirement forshort runs
and bundling includes any associated earth bundling conductors.
Spark gap devices are not suitable to be used in DC circuits once conducting,
DC distribution box AC distribution box they won’t stop conducting until the voltage passes through their terminals
Surge arrestor typically less than 30 volts.
Surge arrestor
Fuse
Fuse
DC breaker
AC breaker ► Anti-Islanding Effect

Islanding effect is a special phenomenon that grid-connected PV system


still supply power to the nearby grid when the voltage loss is happened in
the power system. It is dangerous for maintenance personnel and the
public.
X1 series provide Active Frequency Drift(AFD) to prevent islanding effect.

Electrical Electric meter, NFI


grid Load
bidirectional

04 05
Safety Safety

2.2 Important Safety Instructions

DANGER! WARNING!
Danger to life due to high voltages in the inverter! Do not operate the inverter when the device is running.
All work must be carried out by qualified electrician.
The appliance is not to be used by children or persons with
reduced physical sensory or mental capabilities, or lack of WARNING!
experience and knowledge, unless they have been given Risk of electric shock!
supervision or instruction.
Children should be supervised to ensure that they do not play
with the appliance.

Prior to the application, please read this section carefully to ensure correct and
CAUTION ! safe application. Please keep the user manual properly.
Danger of burn injuries due to hot enclosure parts! Use only attachments recommended or sold by SolaX. Otherwise may result in
During operation, the upper lid of the enclosure and the a risk of fire, electric shock, or injury to person.
enclosure body may become hot. Make sure that existing wiring is in good condition and that wire is not
Only touch the lower enclosure lid during operation. undersized.
Do not disassemble any parts of inverter which are not mentioned in
installation guide. It contains no user-serviceable parts. See Warranty for
CAUTION ! instructions on obtaining service. Attempting to service the X1 Series inverter
yourself may result in a risk of electric shock or fire and will void your warranty.
Possible damage to health as a result of the effects of radiation!
Keep away from flammable, explosive materials to avoid fire disaster.
Do not stay closer than 20 cm to inverter for any length of time.
The installation place should be away from humid or corrosive substance.
Authorized service personnel must use insulated tools when installing or
working with this equipment.
NOTE ! PV modules shall have an IEC 61730 class A rating.
Grounding the PV generator. Never touch either the positive or negative pole of PV connecting device. Strictly
Comply with the local requirements for grounding the PV prohibit touching both of them at the same time.
modules and the PV generator. SolaX recommends connecting The unit contains capacitors that remain charged to a potentially lethal voltage
the generator frame and other electrically conductive surfaces after the MAINS and PV supply has been disconnected.
in a manner which ensures continuous conduction and ground Hazardous voltage will present for up to 5 minutes after disconnection from power
these in order to have optimal protection of system and persons. supply.
CAUTION-RISK of electric shock from energy stored in capacitor,. Never operate on
the solar inverter couplers, The MAINS cables, PV cables or the PV generator when
power is applied. After switching off the PV and Mains, always wait for 5minutes to
WARNING! let the intermediate circuit capacitors discharge before you unplug DC and MAINS
Ensure input DC voltage ≤Max. DC voltage .Over voltage may couplers.
cause permanent damage to inverter or other losses, which will When accessing the internal circuit of solar inverter, it is very important to wait 5
not be included in warranty! minutes before operating the power circuit or demounting the electrolyte
capacitors inside the device. Do not open the device before hand since the
capacitors require time to sufficiently discharge!
Measure the voltage between terminals UDC+ and UDC- with a multi-meter
WARNING! (impedance at least 1Mohm) to ensure that the device is discharged before
Authorized service personnel must disconnect both AC and DC beginning work (35VDC) inside the device.
power from X1 series before attempting any maintenance or
cleaning or working on any circuits connected to the X1 series.

06 07
Safety Safety

PE Connection and Leakage Current 2.3 Explanation of Symbols


• The inverter incorporates a certified internal Residual Current Device (RCD) This section gives an explanation of all the symbols shown on the inverter and
in order to protect against possible electrocution and fire hazard in case of a on the type label.
malfunction in the cables or the inverter. There are two trip thresholds for the RCD
Symbols on the Inverter
as required for certification (IEC 62109-2:2011). The default value for eletrocution
protection is 30mA, and for slow rising current is 300mA.
• If an external RCD is required by local regulations, check which type of RCD Symbol Explanation
is required for relevant eletric code. It recommends using a type-A RCD. The
recommended RCD values is 100mA or 300mA unless a lower value is required The inverter is working normally, when the blue light is on.
by the specific local electric codes. When required by local regulations, the use of
an RCD type B is permitted.
An error has occurred, when the red light is on.

The device is intended to connect to a PV generator with a capacitance limit of


approx 700nf. Symbols on the Type Label

Symbol Explanation
WARNING!
• High leakage current! CE mark.
• Earth connection essential before connecting supply. The inverter complies with the requirements of the applicable
CE guildlines.

• Incorrect grounding can cause physical injury, death or equipment malfunction RCM remark.
and increase electromagnetic.
• Make sure that grounding conductor is adequately sized as required by safety
regulations. SAA certification.
• Do not connect the ground terminals of the unit in series in case of a multiple
installation. This product can cause current with a d.c component, Where a residual Beware of hot surface.
current operated protective (RCD) or monitoring (RCM) device is used for protection The inverter can become hot during operation. Avoid contact
in case of direct or indirect contact, only one RCD or RCM of type B is allowed during operation.
on the supply side of this product. Danger of high voltages.
For United Kingdom Danger to life due to high voltages in the inverter!
• The installation that connects the equipment to the supply terminals shall
comply with the requirements of BS 7671. Danger.
• Electrical installation of PV system shall comply with requirements of BS 7671 Risk of electric shock!
and IEC 60364-7-712.
• No protection settings can be altered. Observe enclosed documentation.
• Installer shall ensure that equipment is so installed and operated to maintain
at all times compliance with the requirements of ESQCR22(1)(a).
For Australia and New Zealand The inverter can not be disposed together with the household waste.
• Electrical installation and maintenance shall be conducted by licensed Disposal information can be found in the enclosed documentation.
electrician and shall comply with Australia National Wiring Rules. Do not operate this inverter until it is isolated from mains
and on-site PV generation suppliers.

Danger to life due to high voltage.


There is residual voltage in the inverter which needs 5 min to
discharge.
• Wait 5 min before you open the upper lid or the DC lid.

08 09
Safety Introduction

2.4 CE Directives 3. Introduction


This chapter follows the requirements of the European low voltage directives,
which contains the safety instructions and conditions of acceptability for the 3.1 Basic Features
endues system, which you must follow when installing, operating and servicing Thanks for your purchasing with SolaX X1 Series inverter. The X1 Series
the unit. If ignored, physical injury or death may follow, or damage may occur to inverter is one of the finest inverters on the market today, incorporating state-
the unit. Read this instructions before you work on the unit. If you are unable to of-the-art technology, high reliability, and convenient control features.
understand the dangers, warnings, cautions or instructions, please contact an
authorized service dealer before installing,operating and servicing the unit. Advanced DSP control technology.
The Grid connected inverter meets the requirement stipulated in Low Voltage Utilize the latest high-efficiency power component.
Directive (LVD) 2014/35/EU and Electromagnetic Compatibility (EMC) Directive Optimal MPPT technology.
2014/30/EU. The unit is based on: - Two independent MPP Tracking.
EN 62109-1:2010 ; EN 62109-2:2011 ; IEC 62109-1(ed.1) ; IEC62109-2(ed.1) - Wide MPPT input range.
EN 61000-6-3:2007+A:2011 ; EN 61000-6-1:2007 ; EN 61000-6-2:2005 Advanced anti-islanding solutions.
In case of installation in PV system, startup of the unit (i.e. start of designated IP65 protection level.
operation) is prohibited until it is determined that the full system meets the Max. efficiency up to 97.8%.EU efficiency up to 97%.
requirements stipulated in EC Directive (2014/35/EU,2014/30/EU, etc.) THD<2%.
The grid connected inverter leave the factory completely connecting device and Safety &Reliability: transformerless design with software and hardware
ready for connection to the mains and PV supply ,the unit shall be installed in protection.
accordance with national wiring regulations. Compliance with safety regulations Power factor regulation.
depends upon installing and configuring system correctly, including using the Friendly HMI.
specified wires. The system must be installed only by professional assemblers - LED status indications.
who are familiar with requirements for safety and EMC. The assembler is - LCD display technical data, Human-machine interaction through press
responsible for ensuring that the end system complies with all the relevant laws key.
in the country where it is to be used. - Dry contact communication interface.
The individual subassembly of the system shall be interconnected by means of - PC remote control.
the wiring methods outlined in national/international such as the national - Romote upgrade and upgrade through USB interface.
electric code (NFPA) No.70 or VDE regulation 0107. - Pocket Wi-Fi monitoring.
- Energy conservation.

3.2 Terminals of the Inverter

G H

A B C D E GF

10 11
Introduction Technical Data

Object Description 4. Technical Data


A DC Switch (optional)
B Waterproof Lock Valve 4.1 DC Input
C DC Connector
X1-3.0-T-D X1-3.3-T-D X1-3.6-T-D X1-4.2-T-D X1-4.6-T-D X1-5.0-T-D X1-5.3/5.98-T-D *
D Ground screw Model
X1-3.0-T-N X1-3.3-T-N X1-3.6-T-N X1-4.2-T-N X1-4.6-T-N X1-5.0-T-N X1-5.3/5.98-T-N
E Pocket WiFi/LAN/GPRS (optional)
Max. recommended DC power [W] 3250 3500 4000 4600 5200 5200 5300/5980
F USB for Upgrade
Max. DC voltage[V] 550 550 550 550 550 550 550
G RS 485/ NFI/ DRM(optional)
Norminal DC operating voltage[V] 360 360 360 360 360 360 360
H AC Connector
MPPT voltage range [V] 70-550 70-550 70-550 70-550 70-550 70-550 70-550
MPPT voltage range@full load [V] 100-500 100-500 160-500 190-500 220-500 220-500 220-500
Max. input current [A] 12/12 12/12 12/12 12/12 12/12 12/12 12/12
Max. short circuit current [A] 12.8/12.8 12.8/12.8 12.8/12.8 12.8/12.8 12.8/12.8 12.8/12.8 12.8/12.8
Start input voltage [V] 80 80 80 80 80 80 80
NOTE! Start output voltage [V] 100 100 100 100 100 100 100
The X1 series with LCD or not, have the same functions, which are No. of MPP trackers 2 2 2 2 2 2 2
different from the appearance display and operation . Strings per MPP tracker 1 1 1 1 1 1 1
DC disconnection swtich Optional

Note: The four models(X1-5.3-T-D/X1-5.3-T-N/X1-5.98-T-D/X1-5.98-T-N)


with signal “*” are only for India.
WARNING!
Only authorized personnel is allowed to set the connection.
4.2 AC Output

X1-3.0-T-D X1-3.3-T-D X1-3.6-T-D X1-4.2-T-D X1-4.6-T-D X1-5.0-T-D X1-5.3/5.98-T-D


3.3 Dimension Model
X1-3.0-T-N X1-3.3-T-N X1-3.6-T-N X1-4.2-T-N X1-4.6-T-N X1-5.0-T-N X1-5.3/5.98-T-N
5000
Ø Dimension Rated output power [W] 3000 3300 3680 4200 4600 5000
(4600for VDE4105)
5000
Max.apparent AC power [VA] 3000 3300 3680 4200 4600 (4600for VDE4105) 5000
341.5mm 143mm
Rated grid voltage and range [V] 220/230/240 (180-280)
Rated AC frequency and range [Hz] 50(45-55)/60(55-65)
AC norminal current [A] 13 14.3 16 18.3 20 21.7 21.7
(20for VDE4105)
Max. output fault current [A] 14 15 16(16.8forG83) 19 21 22.7
(21.7for AS4777) 22.7
Max. output overcurrent protection(A) 45
430mm

Max. inverter backfeed current to 0


the array(mA)
Inrush current(A) 37
Total harmonic distortion(THDi) <2%
Displacement power factor 0.8 leading-0.8lagging
X1
Feed in phase Single-phase
Over voltage category III (electric supply side), II (PV side)

12 13
Technical Data Installation

4.3 Efficiency, Safety and Protection 5. Installation


X1-3.0-T-D X1-3.3-T-D X1-3.6-T-D X1-4.2-T-D X1-4.6-T-D X1-5.0-T-D X1-5.3/5.98-T-D*
Model
X1-3.0-T-N X1-3.3-T-N X1-3.6-T-N X1-4.2-T-N X1-4.6-T-N X1-5.0-T-N X1-5.3/5.98-T-N 5.1 Check for Transport Damage
Inverter+BMU
MPPT efficiency 99.90% 99.90% 99.90% 99.90% 99.90% 99.90% 99.90%
Make sure the inverter is intact during transportation. If there are some visible
Euro efficiency 97.00% 97.00% 97.00% 97.00% 97.00% 97.00% 97.00%
damages, such as cracks, please contact your dealer immediately.
Max. efficiency 97.80% 97.80% 97.80% 97.80% 97.80% 97.80% 97.80%
Safety & Protection 5.2 Packing Lists
Over/under voltage protection YES Open the package and fetch out the product, check the accessories at first.
DC isolation protection YES The packing list shows as below.
Monitoring ground fault protection YES
Grid protection YES
DC injection monitoring YES
Back feed current monitoring YES X1

Residual current detection YES


Anti-islanding protection YES A B C D E
Over load protection YES
Over heat protection YES
X1 Series User Manual
3.0kw - 5.98kw

X1 Series 3.0KW-5.98KW

4.4 General Data Copyright Declaration


The copyright of this manual belongs to Solax Power Network Technology(Zhe jiang) Co,. Ltd.
Any corporation or individual should not plagiarize, partitially or fully copy (including software,etc.),
and no reproduction or distribution of it in any form or by any means. All rights reserved. SolaX
Power Network Technology (Zhe jiang) Co.,Ltd. reserves the right of final interpretation.

F G H
X1-3.0-T-D X1-3.3-T-D X1-3.6-T-D X1-4.2-T-D X1-4.6-T-D X1-5.0-T-D X1-5.3/5.98-T-D
Model
X1-3.0-T-N X1-3.3-T-N X1-3.6-T-N X1-4.2-T-N X1-4.6-T-N X1-5.0-T-N X1-5.3/5.98-T-N
Dimension [W/H/D](mm) 430*341.5*143
Dimension of packing [W/H/D](mm) 514*439*233
Net weight [kg] 13.5 13.5 13.5 14.5 14.5 14.5 14.5
Gross weight [kg] 16.0 16.0 16.0 17.0 17.0 17.0 17.0
I J K( Optional )
Installation Wall-mounted
Operating temperature range[℃] -25~+60 (derating at 45)
Storage temperature [℃] -25~+60
Object Quantity Description
Storage/Operation relative humidity 0%~100%, condensation
A 1 X1 series inverter (with bracket)
Altitude [m] ≤2000
B 4 DC connector
Ingress Protection IP65 C 1 AC connector
Isolation type Transformerless D 3 Expansion tube
Protective Class Ⅰ E 3 Expansion screw
Night-time consumption <0.5w F 1 Product manual
G 1 Warranty card
Over Voltage Category Ⅲ(MAINS),Ⅱ(PV)
H 1 Quick installation guide
Pollution Degree Ⅲ
I 4 DC pin contact(2*positive, 2*negative)
Cooling Natural air ow
J 1 Earth terminal
Noise level <25dB
K 1 Pocket WiFi/LAN/GPRS( Optional )
Inverter Topology Non-isolated
Communication interface RS485/ WiFi(optional) /NFI(optional)/ USB/ DRM
Standard warranty [year] 5years (10 optional)

14 15
Installation Installation

5.3 Installation Precaution 5.4 Installation Steps

X1 Series inverter is designed for outdoor installation (IP 65). Ø Preparation


Make sure the installation site meets the following conditions:
Below tools are needed before installation.
Not be exposed to glare.
Not in areas where highly flammable materials are stored.
Not in potential explosive areas.
Not in the cool air directly.
Not near the television antenna or antenna cable.
Not higher than altitude of about 2000m above sea level.
Not in environment of precipitation or humidity(100%) . Installation tools : crimping pliers for binding post , screwdriver, manual
Be sure the ventilation is good enough. wrench and Φ10 driller.
The ambient temperature in the range of -25℃ to +60℃.
The slope of the wall should be within ±5°. Ø Step 1: Unscrew the bracket from the back of the inverter.
The wall hanging the inverter should meet conditions below:
1) Solid brick/concrete, or strength equivalent mounting surface; a) The wall bracket is fixed on the inverter, and the user should remove it
2) Inverter must be supported or strengthened if the wall’s strength isn’t enough(such firstly. (Φ10 driller.torque: 0.8±0.1Nm)
as wooden wall, the wall covered by thick layer of decoration)
Ø Step 2: Screw the wall bracket on the wall
Please avoide direct sunlight, rain exposure, snow laying up during installing and
operating. b) Use the wall bracket as a template to mark the position of the 3 holes
on the wall.
c) Drill holes with driller, make sure the holes are deep enough (at least
50mm) for installation, and then tighten the expansion tubes.
d) Install the expansion tubes in the holes, and tighten them. Then install
the wall bracket by using the expansion screws.(Φ10 driller.torque: 0.8±
0.1Nm)
Ø Available Space Size Ø Step 3: Match the inverter with wall bracket

e) Hang the inverter over the bracket, move the inverter close to it, slightly lay
300mm down the inverter, and make sure the 3 mounting bars on the back are fixed
well with the 3 grooves on the bracket.
Table Available Space Size
Position Min.size
300mm 300mm Note: Please refer to the details from the Quick Installation Guide.
Left 300mm
Right 300mm
X1
Top 300mm
Bottom 300mm
Front 300mm

300mm

16 17
Installation Installation

5.5 Connections of the Inverter Note!


PV connection mode below is not allowed!
5.5.1 The Main Steps to Connect to the Inverter

Ø PV String Connection

The inverter has a couple of PV connectors which can be connected in series into 2-
strings PV modules. Please select PV modules with excellent function and reliable
quality. Open circuit voltage of module array connected should be <Max.DC (table as
x PV array
+
-

+
- -
+ + PV1
-
+ PV2
-
Inverter

follow) input voltage, and operating voltage should be within the MPPT voltage
range. Connection Steps
a) Turn off the DC switch.
Table 3 Max. DC Voltage Limitation b) Choose 12 AWG(4mm²) wire to connect the PV module.
X1-3.0-T-D
c) Trip 6mm of insulation from the wire end.
X1-3.3-T-D X1-3.6-T-D X1-4.2-T-D X1-4.6-T-D X1-5.0-T-D X1-5.3/5.98-T-D
Model d) Separate the DC connector as below.
X1-3.0-T-N X1-3.3-T-N X1-3.6-T-N X1-4.2-T-N X1-4.6-T-N X1-5.0-T-N X1-5.3/5.98-T-N
Max.DC Voltage
Inverter+BMU 6.0 mm
600V
12AWG
trip length
DANGER! d) Separate the DC connector as below.
Danger to life due to high voltages on DC conductors. plug pin contact cable nut
When exposed to sunlight,the PV array generates dangerous DC
voltage which is present in the DC conductors.Touching the DC
conductors can lead to lethal electric shocks.
Cover the PV modules.
Do not touch the DC conductors.

NOTE!
e) Insert striped cable into pin contact and ensure all conductor strand are
Please choose a suitable external DC switch if the model (X1-3.0-T-N,
captured in the pin contact.
X1-3.3-T-N,X1-3.6-T-N,X1-4.2-T-N,X1-4.6-T-N,X1-5.0-T-N,X1-5.3-T-N,
f ) Crimp pin contact by using a crimping pliers. Put the pin contact with striped
X1-5.98-T-N) is purchased.
cable into the corresponding crimping pliers and crimp the contact.(torque:1.2±
0.1Nm)
WARNING!
PV module voltage is very high which belongs to dangerous voltage
range, please comply with the electric safety rules when connecting.

WARNING! g) Insert pin contact through the cable nut to assemble into back of the male or
Please do not make PV positive or negative ground! female plug. When you feel or heard a “click” the pin contact assembly is seated
correctly.(torque:1.2±0.1Nm)

NOTE!
Please follow the requirements of PV modules as below:
Same type; Same quantity; Identical alignment; Identical tilt.
In order to save cable and reduce the DC loss, we suggest installing
the inverter near PV modules.
18 19
Installation Installation

Ø Grid Connection d) Separate the AC plug into three parts as below.


- Hold the middle part of the female insert, rotate the back shell to
X1 series inverter are designed for single phase grid. Voltage range is 220/230/240V, loose it, and datach it from female inset.
frequency is 50/60Hz. Other technical requests should comply with the requirement - Remove the cable nut (with rubber insert) from the back shell.
of the local public grid.
Table 4 Cable and Micro-breaker recommended
X1-3.0-T-D X1-3.3-T-D X1-3.6-T-D X1-4.2-T-D X1-4.6-T-D X1-5.0-T-D X1-5.3/5.98-T-D
Model
X1-3.0-T-N X1-3.3-T-N X1-3.6-T-N X1-4.2-T-N X1-4.6-T-N X1-5.0-T-N X1-5.3/5.98-T-N

Cable 4-5mm² 4-5mm² 4-5mm² 5mm²


Inverter+BMU
5mm² 5mm² 5mm²
e) Slide the cable nut and then back shell onto the cable.
Micro-breaker 20A 20A 20A 25A 32A 32A 32A

*The parameters have some differences because of different environment and material. Please
according to the local conditions to choose appropriate cable and micro-breaker.

Micro-breaker should be installed between inverter and grid, any loads should f ) Insert the tripped end of each three wires into the appropriate hole in the
not be connected with inverter directly. female insert, and then tight each screw (to tight each wire in place).(PH1
cross screwdriver .torque:0.8±0.1Nm)

X1

g) Screw down the threaded sleeve the pressure screw.

Incorrect Connection between Load and Inverter

Connection Steps
a) Check the grid voltage and compare with the permissive voltage range (refer to h) Screw down the pressure screw.(torque:3±0.3Nm)
technical data).
b) Disconnect the circuit-bricker from all the phases and secure against re-
connection.
c) Trip the wires:
- Trip all the wires to 52.5mm and the PE wire to 55mm.
- Use the crimping pliers to trip 6mm of insulation from Al wire ends as below. I) Connect the AC plug to the inverter.

6mm

20 21
Installation Installation

ØSelection of Fuses and Cables NOTE!


2
Main cable(AC line cable)shall be short circuit protected and thermal overload
protected.
Always fit the input cable with fuse. Normal gG(US:CC or T)fuses will protect the input
cable in short circuit situation. They will also prevent damage to adjoining equipment.
Dimension the fuses according to local safety regulations, appropriate input voltage
and the related current of the solar inverter.

AC output protected by external fuse(gG rated current 25A/250VAC for 3.0KW /3.3KW;
32A/250VAC for 3.6KW/4.2KW/4.6KW/5.0KW/5.3KW/5.98KW) provides in all live
connections to the AC supply.
Ø Earth Connection
The rated short circuit breaking capacity of the above protective device shall be at
least equal to the prospective fault current at the point of installation. See section
Screw the ground screw with allen wrench shown as follow. (φ4
technical data of this manual details. hexagon wrench.torque:1.5±0.2Nm)

AC output cable: Cu; L, N,PE: 3*4.0mm² for 3.0KW/3.3KW/3.6KW and 3*5mm² for
4.2KW/4.6KW/5.0KW/5.3KW/5.98KW @40℃ ambient temperature with a max length
of 5m, with operating time of the fuses is less than 5 seconds, installation method B2
according to EN60204-1:2006, annex D: cable in conduit cable trunking system,
number of loaded circuit only one. Use H07RNF(cord designation 60245 IEC66) for an
ambient temperature of 40℃ or less and use 90℃ wire for ambient temperature
between 40℃ and 60℃.

Note 1: For those different conditions mentioned above, dimension of the cables WARNING!
according to local safety regulations, appropriate input voltage and the load and the Be sure the ground wire must be connected!
load current of the unit.(You can choose a thicker cable but the fuses must rated
according to the cable.)
5.5.2 Communication interface
Note 2: Fuses must be approved by Notified Body.
This product has a series of communication interfaces: such as WiFi,
Inverter is not provided galvanic isolation from the mains to the PV array, feedback RS485/NFI, DRM and USB for upgrading for human and machine
current to the array is 25A/250VAC for 3.0KW and 3.3KW; 32A/250VAC for 3.6KW, communication. Operating information like output voltage, current,
4.2KW, 4.6KW, 5.0KW, 5.3KW and 5.98KW based on the fuse provided in the mains. frequency, faulty information, etc., can be delivered to PC or other
Also in the worst case the reverse current comprises the sum of the short-circuit monitoring equipment via these interfaces.
currents of all intact lines.
WiFi
Therefore the current-carrying capacity of the components and sub-assemblies This inverter provides a WiFi port which can collect information from inverter
provided in the end-use system(connectors, cables, junction box, switch ger, etc.) and including status, performance and updating information to monitoring website
the reverse current PV modules shall be considered based on the feedback current via connecting Pocket WiFi( purchase the product from supplier if needed)
and reverse current. The direct current(DC) circuit breaker or fuse between each solar
generator and inverter shall be provided based on solar inverter input ratings. Connection steps:
Select DC cables based in the above inverter back-feed current and ISC PV rating and 1.Plug the Pocket WiFi into “WiFi/LAN/GPRS” port at the bottom of inverter.
Vmax ratings. 2.Connect the WiFi with router.
3.Set the station account on the solaX web.(Please check the Pocket WiFi user
manual for more details) (torque:0.6±0.1Nm)

22 23
Installation Installation

RS 485/NFI/DRM Ø RS 485 Connection Steps:


a. RS 485 1) Firstly unscrew the screw from the 485 port.(PH1 cross screwdriver
.torque:0.8±0.1Nm)
RS 485 is one standard communication interface which can transmit the real data
2) Prepare a communication cable and trip the insulation from it.
from inverter to PC or other monitoring equipments.
3) Let the communication cable pass though the waterproof connector, then
insert it into the connector following the PIN definition rule.
Hand tighten. torque:1.2±0.1Nm

X1

4) Crimp the connector with the crimping plier.


5) Insert the cable into the 485 port of the inverter, and tighten the
waterproof connector.
b. NFI(optional)

The NFI, energy controller, is integrated with meter, control MCU and RS485 to
communicate with the inverter. It can control the power of inverter to assure that
the redundant power will not feed into Grid.

X1 series inverter Ø NFI Connection Steps:


Please see the Quick Guide and User Manual for X1-NFI Installation for details.
Electrical X1

grid Load DRM

DRM function (for AS4777) is provided to support several demand response


modes by giving control signals as below. The user should short circuit between
NFI 1 and 2 and cooperate with external equipment when using it.

8
The PIN de nitions of RS 485/NFI interface are as below.
PIN 1 2 3 4 5 6 7 8
1
Definition RefGen Com/DRM0 GND_COM X X X X X

8
DRM shares the terminal block with RS485/NFI communications.
The connection steps of the DRM, user can refer to the above (b) RS485
PIN 1 2 3 4 5 6 7 8 connections.
NFI_A/ NFI_B/
Definition RefGen Com/DRM0 GND_COM E_Stop GND_COM X
485_A 485_B Note: Only DRM0 is available now, and other functions are being developed.

24 25
Installation Installation

4 Upgrade *The inverter with LCD:

3) Then insert U-disk into the USB port on the bottom of the inverter. Then
NOTE! turn on DC switch or connect the PV connector, the LCD will show the main
According to the X1 series with LCD or not, please select the pictures as below.
corresponding upgrade method.

ARM Cancel Update(ARM)


User can update the inverter system through the U-disk.
DSP OK Updating----25%
WARNING!
Make sure the input voltage is more than 150V (in good illumination
condition), or it may result in failing during updating. U-disk

Ø Upgrade Steps:
1) Please contact our service support to get the update file, and extract it 4) Press up and down to select the one that you want to update and long
into your U-disk as the following file path: press down to confirm.

5) After the upgrade is complete, please remember to turn off the DC switch
“update\ARM\618.00207.00_X1_BOOST3.0_MINI2.0_AIR2.0_ARM_Vx.xx_xxxxxxxx.usb”;
“update\DSP\618.00205.00_X1_BOOST3.0_MINI2.0_AIR2.0_DSP_Vx.xx_xxxxxxxx.usb or disconnect the PV connector, then pull off the U-disk, screw the
”. waterproof lid.
Note: Vx.xx is version number, xxxxxxxx is file completion date.

WARNING! WARNING!
• Make sure the directory is in accordance with above form strictly! During updating, please don’t turn off the DC switch or
• Do not modify the program file name ! Or it may cause the inverter disconnect the PV connector. If failed, please repeat the above
not work anymore ! operation again.

2) Make sure the DC switch is off and the AC is disconnected with grid.
Unscrew the waterproof lid of Upgrade port by straight screwdriver as below.

Straight screwdriver

Waterproof lid

torque:1.5±0.2Nm
26 27
Installation Installation

**The inverter without LCD: 5.6 Run the Inverter


(1) and (2) steps are the same. Ø Start inverter after checking all below steps:
(3) Turn on DC switch or connect the PV connector, blue light “a” and red
a) Check that device is xed well on the wall.
light “b” flash alternately for 10 times. Indicator light “1”, “2”, “3”, “4” are unlit.
b) Make sure all the DC breakers and AC breakers are disconnected.
c) AC cable is connected to grid correctly.
d) All PV panels are connected to inverter correctly, DC connectors which are
not used should be sealed by cover.
e) Turn on the external AC and DC connectors.
f ) Turn on the DC switch to the “ON”position.
a b
1 2 3 4 1 2 3 4 1 2 3 4
Ø Start the inverter
L1 L2 L3 L4

X1 X1 X1 Inverter will start automatically when PV panels generate enough energy.


Check the status of LED indication and LCD screen, the LED indication should be
(A) (B1) (B2) blue and the LCD screen should display the main interface.
If the LED indication is not blue, please check the below:
- All the connections are right.
c) About 10 seconds later, the system will be updated automatically. During - All the external disconnect switches are closed.
this period, blue light “a” is always been on and red light “b” is unlit. Indicator - The DC switch of the inverter is in the “ON” position.
light “1”, “2”, “3”, “4” show the progress of system updating. Refer to figure (B1), it
shows that the updating process is half-finished. Once finished completely, it
shows as figure (B2).
Ø Below is the three status when operating, which means inverter starting
up successfully. And there are difference between having LCD and not having
Note: The updating process for ARM needs about 10 seconds and DSP needs the LCD.
about 1 minutes.
*The inverter with LCD can refer to the following:
WARNING! Waiting: Inverter is waiting to checking when DC input voltage from panels is
During updating, please don’t turn off the DC switch or greater than 110V (lowest start-up voltage) but less than 150V (lowest operating
disconnect the PV connector. If failed, please repeat the above voltage).
operation. Checking: Inverter will check DC input environment automatically when DC
input voltage from the PV panels exceeds 150V and PV panels have enough
energy to start inverter.
Normal: Inverter begins to operate normally with blue light on. Meanwhile
5 Earth Fault Alarm feedback energy to grid, LCD displays present output power.

The earth fault alarm installed into the inverter, is the standard configuration, Enter the setting interface to follow the instructions when it is rst time to start
as required by AS 4777.2 and AS/NZS 5033, it will give an alarm once the earth up.
impedance of the PV arrays is less than 100KΩ .

28 29
Installation Operation Method

**Below is three different states of the inverter without LCD when operating, 6. Operation Method
which means inverter starting up successfully.
Waiting: Inverter is waiting to checking when output DC voltage from PV panels
6.1 Control panel
is greater than 110V (lowest start-up voltage) but less than 150V (lowest
operating voltage). Under this mode, the blue light “a” is flickering, shown as
figure (A).
Checking: Inverter will check output environment automatically when DC LCD LED
output voltage of PV panels. Under this mode, the blue light “a” is flickering,
shown as figure (A).
Normal: Inverter begins to operate normally with blue light “a” on. Inverter will
work in MPPT mode when PV voltage is in the MPPT voltage range, inverter will A
stop feedback to grid when PV power is not enough.
Under this mode, the blue light “a” is always on, light ”1,2,3,4” represent the E F 1 2 3 4

X1 X1
output power. As shown in figure (B), the output power is 0%~25%".

B C
B C D

a b a b
1 2 3 4 1 2 3 4 Object Name Description

X1 X1 A LCD Screen Display the information of the inverter.

(A) (B) B Light in blue: The inverter is in normal status.


Waiting/Checking Normal
Indicator Flash in blue: The inverter is in waiting status.
LED
C Light in red: The inverter is in fault status.
WARNING!
Power to the unit must be turned on only after installation work D Up/ESC button: Move cursor to upside or increase value.
Function Return from current interface or function
has been completed. All electrical connections must be carried Button Move cursor to downside or decrease value.
out by quali ed personnel in accordance with legislation in E
Down/Enter button: Con rm and change the parameters.
force in the country concerned.
Indicator
F Light in blue: The fault types or output power of the inverter.
LED
NOTE !
Please set the inverter if it is the first time to start up.
Above steps are for the regular start of the inverter. If it is the first Note: When the inverter with LCD and LED are in “Waiting” and “Checking”
time to start up the inverter, you need to setup the inverter. status, the blue light “B” is flickering; when in “Normal” status, the blue light “B” is
always on.
ENERGY CONTROL
Equipment only to be used for the purpose outlined by SolaX.

30 31
Operation Method Operation Method

6.2 LCD Structure 6.3 LCD Operation


Please refer to the inverter for the most updated structure
• Setting function is used for setting the inverter for Safety, Grid, Power Factor and
so on.
• Since this function will change the inverter's parameter, the end user with the
*User can also see the U,I & P
user password as”0000” has the limited authority to change the setting. We need
1 level 2 level 3 level of the PV. (Usolar,Isolar,Psolar) installer password to do most of the professional setting.
Power 0W Enter Enter Ugrid 0.0V Down Igrid 0.0A
Normal >Status Pout 0W *
F 0.00Hz Up
Back
**Previous page
Up Down Up Down

Today 0.0KWh Enter


Enter
>Language >English
Normal Back German Enter
>Safety Country
Up Down Up Down ** Grid >AS4777<
Enter ↓ Enter >Safety Back
Down Total 0.0KWh Enter >Setting Grid ** Up Down
0 0 0 0
Normal Back Back Enter
>Vac Upper
Enter

Up Down **Go to next page >Grid
Enter
0.0 Back
> 220.0 <
1:xxYxxxDxxH Back
>Error Logs ***Only six latest errors were kept Up Down
Back Error1 Enter Enter Enter
*** Mode Select >Upper Limit ↓
Up Down >Power Factor >Pf(P)< > 273.0 <
Back Back 0.0 Back
>Product SN:
>About Up Down
X1xxx Enter
Mode Select
>P(U) Function
Up Down >Enable<
Back
Back Up Down
>Machine Type:
Enter Enter
xx-S > Proportion ↓
>Power Limit 1.00 > 0.80 <
Up Down Back Back
Up Down
Back Enter
>Master: Mode Select
>NFI Function
xxx >Disable<
Back
Up Down
Up Down Enter
Mode Select
Back >DRM Function
>Manager: >Enable<
xxx Back
Up Down
Enter

>New Password
0000
Back
Up Down
Note: Enter
Reset
Key Operation Description >Reset Errorlog
>No<
˅ Long Press Go to the next menu or confirm to change parameters Back
Enter/Down Up Down
Short Press Look at the next parameter or increase the value Enter
˄ Long Press Return the previous menu or confirm the parameters >Reset Energy
Reset
Back/Up Short Press Look at the previous parameter or decrease the value >No<
Back

32 33
Operation Method Operation Method

Ø LCD Display (3) Power Factor: ( For speci c country if required by the local grid.)
•1 level There are 6 modes for selecting: Off , Under-Excited, Over-Excited, PF(p), Q( u ).
a) The first line displays the parameters(Power, Today and Total) and the values. All parameters are shown below.
b) The second line shows the running status. Mode Comment
Namely, “Power” means the timely output power; Off -
“Today” means the power generated within the day.
Under-Excited PF value
“Normal” means the status of the inverter.
Over-Excited PF value
Upper limit
•2 level
Lower limit
Long press any first-level parameter can enter the sencond-level “Status” PF(p)
parameter interface. Power Upper
The user can also see other parameters, such as the Language( without password ), Power Lower
Setting ( need password ), Error Logs of the inverter, and About ( the user can watch QuVupRate
( EN50438_NL )
the information of the inverter).
QuVlowRate
Q( u ) ( EN50438_NL )
•3 level QUrangeV1 ( AS4777.2 )
Long press the sencond-level parameter can enter the corresponding third-level QUrangeV4 ( AS4777.2 )
parameter interface.
Fixed Q Power Q Power( for some local grids )

a) Status: The user can see the U/I/P parameters of the grid and the PV, such as the For VDE ARN 4105, curve cos φ = f(P) should refer to curve A. default values of setting are as
Ugrid, Igrid, P and F of the grid, and the Usolar, Isolar and Psolar of the PV. shown in curve A.
For E 8001, curve cos φ = f(P) should refer to curve B. default values of setting are as shown in
b) Language: This inverter provides several languages for customer to choose. curve B.

cos φ
c) Setting: Entering the installer password, the information of the LCD interface is leading Upper limit
0.9/0.95* 0.9
as the previous page shown.

over-excited

inductive
(1) Safety: The user can set the right safety standard here.
(2) Grid: Usually end user do not need to set the grid parameters. All default value Power Upper
have been set before leaving factory according to safety rules. 1
0.7 0.8
0.2 0.5 1.0 0.2 0.3

under-excited
If need to reset, any changes should according to the requirement of local grid. p/pEmax f (P)

capactive
Power Lower

Parameter Comment
0.9/0.95* 0.9
Normally lagging Lower limit
Vac upper Voltage high protect curve A curve B
Vac lower Voltage low protect
Vac upper slow Voltage high slow protect Reactive power control, Reactive standard curve Q= f(V)
Vac lower slow Voltage low slow protect
Fac upper Frequency high protect Q V2s=1.10Vn
Fac lower Frequency low protect Qmax V1s=1.08Vn=QuVlowRate
Fac upper slow Frequency high slow protect V2i=0.90Vn
Fac lower slow Frequency low slow protect V2i=0.92Vn=QuVlowRate
V1s V2s
Vac 10m avg 10 min voltage high protect
V2i V1i V
Apply to EN50438_NL.
FreqSetPoint Frequency set point
FreqDropRate Frequency droop rate -Qmax
34 35
Operation Method Operation Method

→The way to operate the value : 6.4 Indicator Information


a) Just watch the parameter of the mode by short pressing (Λ) and (V) .
b) If you change other mode by short pressing (Λ) and (V) , you need return the Power Factor Ø Normal working
interface by long pressing the (V). Then short press (V) to confirm and enter the Upper Limit. This
time you can modify the value by long pressing (Λ) ; If you only change the parameter of the Blue light “a” keeps on. Light “1,2,3,4” are unlit:
mode(default), you just long press the (Λ) to modify the value.
c) After setting, long press the (V) key to confirm and return the previous directly.
Indicator Description

>Power Factor →Enter Mode Select


>PF(p)< → Enter >Upper Limit
0.0 → Enter ↓
> 273.0 <
1 2 3 4
Output power range : 0% ~ 25%

(3) P(u) Function: The device is suitable for Australia if the “Enable” is chosen.

(4) Power limits: User can set the power limit value of the inverter, and the default is Output power range : 25% ~ 50%
1. If you want to change, please refer to the method bellow. (the same operation to 1 2 3 4

other setting value)


> Proportion
1.00 → ↓
> 0.80 <
Output power range : 50% ~ 75%
1 2 3 4

→The way to set value :


a) Long press the key (V) to enter the interface, and long press again to modify .
b) Short Press (Λ) or (V) to increase or decrease the value you needed.
c) After setting, long press the (V) key to confirm the parameters or you can long press the (Λ) to
confirm and return the previous directly.
Output power range : 75% ~ 100%
1 2 3 4

(5) NFI Function: When selecting NFI, the user should set the NFI function “Enable”,
otherwise the inverter will not work.

(6) DRM Function: User can choose whether using the DRM function or not.

(7) New Password: Installer can set the new password here.
→The way to set password:
a) Long press the key (V) to enter the interface, and long press again to modify .
b) Short Press (Λ) or (V) to increase or decrease the value you needed.
c) After setting, long press the (V) key to confirm the parameters.
d) Long press (Λ) to enter next level.

(8) Reset Errorlog: The user can clear the errorlogs by this function.

(9) Reset Energy: The user can clear the power energy by this function.

(10) About: This interface shows information of the inverter, include product serial
number, machine type, master, slave and manager.

36 37
Operation Method Operation Method

Ø Working faults
Red light “b” keeps on, light “1, 2, 3, 4” are unlit :

Indicator Fault Description Indicator Fault Description

PV Volt Fault PV Over Voltage Fault Relay Fault Relay Fault


1 2 3 4 1 2 3 4

Inv EEprom Error


Isolation Fault Isolation Fault EEPROM Fault
1 2 3 4 1 2 3 4
Mgr Eeprom Fault

Temp Over Fault Over Temperature Fault Comms Lost Include SPI,SCI Faults
1 2 3 4 1 2 3 4

DCI Device Fault


DCI Fault Bus High Bus Volt Fault
1 2 3 4
DCI OCP Fault 1 2 3 4

Tz Protect Fault
RCD Fault RCD Fault TZ Fault
1 2 3 4 1 2 3 4 SW OCP Fault

Other Device Fault


Mains Lost Grid Lost Fault Other Device Fault
1 2 3 4 1 2 3 4 PLL Lost Fault

Grid Volt Fault Grid Volt Fault AC10Min Volt Fault AC10Min Volt Fault
1 2 3 4 1 2 3 4

Grid Freq Fault Grid Freq Fault


1 2 3 4

Consistant Fault Sample Fault


1 2 3 4

38 39
Troubleshooting Troubleshooting

7 Troubleshooting
7.1 Troubleshooting

This section contains information and procedures for solving possible problems
with X1 series inverters, and provides you with troubleshooting tips to identify
and solve most problems that could occur with the X1 series inverters.
This section will help you narrow down the source of any problems you may
encounter. Please read the following troubleshooting steps.
Check warnings or fault messages on System Control Panel or Fault codes on
the inverter information panel. If a message is displayed, record it before doing
anything further.
Attempt the solution indicated in troubleshooting lists.

● If your inverter's information panel is not displaying a Fault light, check the
following list to make sure that the present state of the installation allows proper
operation of the unit.
— Is the inverter located in a clean, dry, adequately ventilated place?
— Have the DC input breakers been opened?
— Are the cables adequately sized and short enough?
— Are the input and output connections and wiring in good condition?
— Are the configurations settings correct for your particular installation?
— Are the display panel and the communications cable properly
connected and undamaged?

Contact SolaX Customer Service for further assistance. Please be prepared to


describe details of your system installation and provide model and serial number
of the unit.

40 41
Troubleshooting Troubleshooting

7.2 Routine Maintenance

Inverters do not need any maintenance or correction in most condition,but if the


inverter often loses power due to overheating,this can be the following reason:
● The cooling fins on the rear of house are coverd by dirts.
Clean the cooling fins with a soft dry cloth or brush if necessary.
Only trained and authorized professional personnel who are familiar with the
requirements of safety was allowed to perform servicing and maintenance work.

► Safety checks
Safety checks should be performed at least every 12 months by manufacturer's
qualified person who has adequate training,kownledge,and practical experience
to perform these tests.The data should be recorded in an equipment log.If the
device is not functioning properly or fails any of test,the device has to be
repaired.For safety check details ,refer to this manual,section 2 Safety instruction
and EC Directives.

►Maintain periodically
Only qualified person may perform the following works.
During the process of using the inverter,the manage person shall examine and
maintain the machine regularly.The concrete operations are follow.
1) Check that if the cooling fins on the rear of house are covered by dirts,
and the machine should be cleaned and absorbed dust when necessary.
This work shall be check time to time.
2) Check that if the indicators of the inverter are in normal state,check if the
keys of the inverter are in normal state,check if the display of the inverter is
normal.This check should be performed at least every 6 months.
3) Check that if the input and output wires are damaged or aged.This check
should be performed at least every 6 months.
4) You should get the inverter panels cleaned and their security checked at
least every 6 months.

AC10Minute overvoltage Fault


AC10M Volt Fault System will reconnect if the utility is back to normal.
Or seek help from us.

NFI Fault
NFI Fault Check the the NFI connection with the inverter.
Or seek help from us.

42 43
Decommissioning

8 Decommissioning
8.1 Dismantling the Inverter

Disconnect the inverter from DC Input and AC output.


Wait for 5 minutes for de-energizing.
Disconnect communication and optional connection wirings.
Remove the inverter from the bracket.
Remove the bracket if necessary.

WARNING!
Before dismantling the inverter, please be sure to
disconnect the DC switch, and then unplug the PV and AC
cables, otherwise it will lead to an electric shock hazard.

8.2 Packaging

If possible, please pack the inverter with the original packaging.


If it is no longer available, you can also use an equivalent carton that meets the
following requirements.
Suitable for loads more than 30 kg.
With handle.
Can be fully closed.

8.3 Storage and Transportation


Store the inverter in dry place where ambient temperatures are always between
-25 °C - +60 °C. Take care of the inverter during the storage and transportation,
keep less than 4 cartons in one stack.

When the inverter or other related components need to be disposed. Have it


carried out according to local waste handling regulations. Please be sure to
deliver wasted inverters and packing materials to certain site, which can assist
relevant department to dispose and recycle.

44

You might also like