Application Guide Loop Testing Techniques PDF
Application Guide Loop Testing Techniques PDF
Application note 49
5, Test leads
Test currents The contact resistance of test leads, particularly on
High loop test currents develop large signals that contaminated surfaces, and fused leads also add
are easier and more accurate to measure. They also additional resistance to the measurement.
can cause large touch voltages on the installation
under test that should be monitored to prevent In all cases it is recommended to make more than
danger. one measurement to check that any changes in load
Lower test currents are less likely to operate or switching on the supply have not interfered with
protection and touch voltages are reduced. the results.
3-wire high/dc High current L- Faster than 2- Can be inaccurate on Neutral not
or low N, dc L-E for up wire test TT systems always
frequency AC to 30 s Supply must have N-E accessible
current connection so cannot
be used on 110 V
centre-tapped supplies
2 wire low Low energy test Repeatable May trips some RCDs
energy up to 30 s results, 2 wire or RCBOs,
connection Measurement accuracy
Less susceptible depends on system
to leakage characteristics
currents
CERTIFICATION ISO
UK UNITED STATES OTHER TECHNICAL SALES OFFICES
Registered to ISO 9001:2008 Cert. no. Q 09250
Archcliffe Road Dover 4271 Bronze Way Valley Forge USA, College Station USA, Sydney Registered to ISO 14001-2004 Cert. no. EMS 61597
CT17 9EN England Dallas TX 75237-1019 USA AUSTRALIA, Täby SWEDEN, Ontario CANADA,
T +44 (0) 1304 502101 T 800 723 2861 (USA only) Trappes FRANCE, Oberursel GERMANY, Aargau Loop_AN_en_V01
F +44 (0) 1304 207342 T +1 214 333 3201 SWITZERLAND, Kingdom of BAHRAIN, Mumbai www.megger.com
[email protected] F +1 214 331 7399 INDIA, Johannesburg SOUTH AFRICA, Chonburi
Megger is a registered trademark
UNITED STATES [email protected] THAILAND