CEM3 Manual
CEM3 Manual
CEM3
User Manual
Version 1.7.0
Al l ot h e r t ra d e ma rk s , b o t h ma r ke d a n d n o t m a r k e d , a r e t h e p r o pe r t y o f t h ei r r es p e c t iv e ow n er s .
E T C i n t e n d s t h i s d o c u m e n t , w h e t h er p r i n t e d o r e le c t r o n i c , t o b e p r o v i d e d i n i t s e n t i r e t y . T h i s
p r o d u c t i s i nt e n de d f o r p r o f e s s i o n a l u s e o n l y . R e a d t h i s e n t ir e do c u m e n t b e f o r e u s i n g t h i s p r od u c t .
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 1
Using this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Text Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Table of Contents i
Chapter 2 System Reference. . . . . . . . . . . . . . . . . . . . . 6
Important Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Advanced Features (AF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Dimmer Doubling (UL/ 120V 60Hz Systems Only). . . . . . . . . . .6
Latch-Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Panic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Patch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Preset Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Redundant Tracking (ESR and FDX Racks Only) . . . . . . . . . . .10
Variable Speed Fan (ESR Series Racks Only) . . . . . . . . . . . . . .11
UI Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Dimmer Property Definitions. . . . . . . . . . . . . . . . . . . .17
Rack Property Definitions . . . . . . . . . . . . . . . . . . . . . .20
Dimmer Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Linear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Modified Linear (Mod-Linear) . . . . . . . . . . . . . . . . . . . . . . . . .21
Square Law (Square). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Modified Square Law (Mod-Square) . . . . . . . . . . . . . . . . . . . .22
Sensor 2.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Stage 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Stage 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Fluro1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Fluro 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
ANDI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
VIP 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Custom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table of Contents v
Introduction
Welcome to your new CEM3 Power Control system.
This manual is designed to introduce you to the CEM3 user interface and the primary features
and functions available to you in the setup and use of your CEM3 power control system.
Using this Manual
The following graphics and conventions are used throughout this manual to convey
important information.
Note: Notes are helpful hints and information that is supplemental to the main text.
WARNING: A Warning statement indicates situations where damage may occur, people
may be harmed, or there are serious or dangerous consequences of an action.
WARNING: RISK OF ELECTRIC SHOCK! This warning statement indicates situations where
there is a risk of electric shock.
Text Conventions
• Bold is used to indicate something in the CEM3 user interface, such as a parameter or button.
• [Brackets] are used to indicate a tactile button on the face of the CEM3 (such as [Setup], [Test],
and [Enter]).
Please email comments about this manual to: [email protected].
Introduction 1
Help from ETC Technical Services
If you are having difficulties, your most convenient resources are the references given in this
user manual. To search more widely, try the ETC website at etcconnect.com or the Dimming
and Networking Systems page at community.etcconnect.com.
If none of these resources are sufficient, contact ETC Technical Services directly at one of the
offices identified below. Emergency service is available from all ETC offices outside of normal
business hours.
When calling for help, please have the following information handy:
• Product model and serial number (located on the bottom of the CEM3)
• Installation type
• Other components in your system (Unison®, other consoles, etc.)
Asi a German y
ETC Asia ETC GmbH
Technical Services Department Technical Services Department
Room 1801, 18/F Ohmstrasse 3
Tower 1, Phase 1 Enterprise Square 83607 Holzkirchen, Germany
9 Sheung Yuet Road +49 (80 24) 47 00-0
Kowloon Bay, Kowloon, Hong Kong [email protected]
+852 2799 1220
[email protected]
Navigation
Scroll Wheel
Use the scroll wheel and up/down arrows to move the selection cursor on any menu screen until the
desired item is highlighted. Menus that do not fit on one screen will have a scroll bar on the right side
of the display window, and additional menu options can be accessed with the scroll wheel. You can
also tap the top or bottom of the scroll wheel to move the display cursor up or down.
The scroll wheel also lets you scroll through number fields (such as circuit number) or through the
available options for a selected item (such as Module Type).
The center button of the scroll wheel functions as [Enter]. Press [Enter] to select the highlighted item on
the display window or to commit entered data.
Keypad
Use keypad to enter values for any value fields in the display window. When setting levels you can
select individual dimmers or ranges of dimmers using the [and] and [thru] buttons.
Both the center button of the scroll wheel and the bottom right keypad button function as [Enter].
Press [Enter] to select the highlighted item on the display window or to commit entered data.
Getting Started 3
Navigation Buttons
The navigation buttons ([Test], [About], [Setup]) and the [Back] button are used to navigate menus in
the display window (see Menu Structure on page 11). Press [Back] to return to the previous screen on
any menu.
Note: Prior to performing a Quick Setup, make sure that your rack DIP switch settings are
set appropriately for your rack type. See Setting Rack DIP Switches and Termination
on page 36.
CAUTION: Quick Setup will overwrite some of the data in your rack. Only perform a
Quick Setup when you want to reconfigure your system or are instructed to
do so by ETC Technical Services.
You can begin a Quick Setup by selecting Quick Setup from the main screen or by navigating to
[Setup]>Quick Setup>[Enter].
From this screen you can use the CEM3 interface to enter data in up to four screens to quickly establish
your rack configuration: Module, Circuit, Dimmer Double, and Patching (see below for screen
descriptions).
Once you have entered data in the screens, select OK and press [Enter] to save the setup changes.
Module
The current Rack Type is listed. To change the module type select Module. Select a module type and
model from the list, then select Next. The rack will be configured as filled with the selected module
type. If you don’t need to change the module types, leave the type as Unchanged.
Circuit
Set Numbering to either Renumbering or Unchanged to indicate whether to renumber the rack. If you
select Renumbering, set these two additional parameters:
• Set the Starting At value to the number for the first circuit in the rack. If this is your first or only
rack, this number is typically 1. If this rack is one of many in your system, this number typically
continues the numbering sequence from the previous rack. Default is 1.
• Set the Balance type: Straight, 1-Phase, or 3-Phase. The CEM3 processor defaults to the balance
type that is appropriate for the detected power source, but you can change this value if desired.
- Straight results in circuit numbering that will proceed sequentially straight through the entire
rack.
- 1-Phase or 3-Phase results in circuit numbering that distributes the circuits evenly across the
different power phases so that neighboring circuits do not place an uneven load on any phase.
Patch
Select an automatic patching method to patch the entire rack sequentially.
Note: Automatic patching is only available for racks with one space. For racks with more
than one assigned space, see Patching on page 34.
Getting Started 5
Chapter 2
System Reference
This chapter includes the general concepts behind the features of your CEM3, the general menu
structure of the software, definitions of all dimmer properties, and illustrations of the various dimmer
curves available in your system.
Important Concepts
This section introduces some of the primary concepts. Topics are listed alphabetically.
Circuit
A circuit is a user assignable number between 1 and 99999. The circuit is the reference number for that
dimmer in the rack. Circuit numbers must be unique per space; it is possible to have multiple circuits of
the same number, but they must be in different spaces.
Configuration
The rack configuration is a collection of all of the data stored about the rack and all of its circuits. The
configuration is stored automatically in the CEM3 whenever you make a change (for example,
changing a circuit from switched to dimmed).
The configuration of any rack is automatically stored on both the CEM3 module and the CEM3
backplane. Therefore, you can remove a CEM3, replace it with a new, unconfigured CEM3, and the
configuration from the backplane will be loaded to the new CEM3.
You can save and load rack configurations by connecting a USB removable media device to the USB
port on the front of the module, by connecting to a computer on the network (using the CEM3 web
interface), or by connecting to an FTP server. Saving and loading are performed from the File
Operations menu. See Saving or Uploading Files and Firmware on page 30.
Control Level
Latch-Lock off range
Latch-Lock on range
relay open
(circuit off)
Time
relay closes relay opens
(circuit turns on) (circuit turns off)
Lug
“Lug” refers to a physical position in the rack. Lugs are always numbered counting downwards from
the top of the rack, starting at 1. Some modules may take up multiple lug positions in the rack.
System Reference 7
Panic
CEM3 offers a panic capability that complies with the UL 924 standard.
When a properly connected and enabled CEM3 has a panic “look” stored, it will automatically play the
recorded look when it receives a signal over the panic circuit.
Panic can be enabled when a maintained (normally open or normally closed) contact closure is properly
wired to the backplane. For more information, see the data termination guide or installation guide that
was supplied with the rack.
For information on how to configure panic on your CEM3, see Setting Up Panic on page 32.
Note: To configure panic mode through an electrical override without using the CEM3
module software, order the Hardwired Panic Accessory (7140K1002). Contact your
local dealer for more information.
Patch
Patching governs the relationship between control input sources (DMX A, DMX B, and sACN) and the
control of circuits in the rack. This relationship can be edited to match the needs of your control
sources and rack constraints. For information on patching, see Patching on page 34.
When you activate a preset, this action is propagated across the Net3 network. For example, if you
activate a given preset for space 1, all CEM3 modules on the network will activate that preset for
space 1.
System Reference 9
Rig Check
In Sensor3 racks with Advanced Features (see Advanced Features (AF) on page 6) you can record a
special preset called Rig Check, which includes both circuit levels and the amount of load (current)
expected on each circuit.
Once recorded, the Rig Check can be played back, either from the CEM3 face panel or remotely, and
the CEM3 will post load high, load low, or no load messages based on how the load of the circuit has
changed since you recorded the Rig Check preset. These messages will be available on the CEM3
display or on a connected console that monitors AF feedback.
You can record, run, and clear a rig check on the Test menu (see Test on page 12).
Spaces
Spaces are logical divisions within a system (such as different rooms) that isolate station control (preset
and sequence control) to the defined group of controllable outputs in that division. CEM3 supports
separation of its controllable circuits into spaces.
Station Functions
Presets can be played back from preset stations in the system.
• Press a preset station button to activate a preset.
• Press it again to deactivate the preset.
• Stations can be configured with an Off button. This option is performed at the station and should
only be done by a qualified technician.
• The group of presets controlled by any station can be altered at the station. This should only be
done by a qualified technician.
For more information see the Echo Preset Station Installation Guide available at etcconnect.com.
Menu Structure
This section describes the menu structure of the software. Press the desired button to access the menu
items below. Use the standard navigation method to select and enter options in the menus (see
Navigation on page 3).
System Reference 11
Test
Field Description
Set levels for outputs from this rack only. This will present a table-style view
of the outputs in this rack and allow setting and releasing of levels. To set
levels:
• Select a circuit by numeric entry or scrolling with the wheel
• To select a range of circuits, use [thru] and [and].
- Press [Last/A] or [Next/B] on the keypad to set a level for the A or B
Set Local Levels
side of dimmer doubled circuits. See example below.
• Press [at].
• Use numeric entry or scroll to select a level. 0–100 is the valid range.
100 will display as "FL".
• Press [Enter]. The selected circuits will be set to the specified level or
released if you did not enter a level.
Set levels for chosen circuits in a space. See Example on the next page. If
necessary, double press [Back] to clear the command line during any of the
following steps.
1: Use the keypad to enter a circuit number between 1 and 99999.
2: Press [and] to enter multiple circuits or press [thru] to enter a range of
circuits.
• Press [Last/A] or [Next/B] on the keypad to set a level for the A or B
side of dimmer doubled circuits. See example below.
Set System Levels
3: Press [at] or [Enter]. The command line ends with "at".
4: Use the keypad or scroll wheel to enter a level if desired. 0–100 is the
valid range. 100 will display as "FL".
5: Press [Enter]. The selected circuits will be set to the specified level or
released if you did not enter a level. The command line ends with "*".
6: If you selected a single circuit, press [Next] or [Last] on the keypad to
increment or decrement the circuit number to set the level of another
circuit, if desired.
Quickly run through all lugs or all circuits in a space to test their output at a
Dimmer Check
given percentage.
Release Systm Lvls Release any active levels for a given space at once.
Presets Record or play back presets. See Recording and Playing Presets on page 27.
Record or play back sequences. See Recording and Playing Sequences on
Sequences
page 29.
Release all architectural control such as presets, sequences, and set zone
Release All Arch
levels.
Record a rig check preset to facilitate AF reporting. Rig Check features are
only available if the rack property AF Enabled is set to Yes. See Rig Check
Record Rig Check
on page 10, Advanced Features (AF) on page 6, and Rack Property
Definitions on page 20 for more information.
Run a rig check preset. You will be notified of any load inconsistencies
Run Rig Check
found during the rig check.
Clear Rig Check Clear the recorded rig check from all racks for a given space.
System Reference 13
About
Field Description
View all properties for any circuit in a space or in any rack on the network.
Dimmers
See Dimmer Property Definitions on page 17.
View all properties for the host Sensor rack. See Rack Property Definitions
on page 20.
Rack • Status: displays "Rack OK" or "Errors Exist"
• Panic State: displays "Ready" when not in a panic condition and
"Active" when in a panic condition.
View any current errors or other status messages. See Error Messages on
Errors
page 57.
View the current control source (Highest-Takes-Precedence or “HTP”) and
related output level being received by all dimmers in a space.
• "DMXA" is DMX Port A
• "DMXB" is DMX Port B
• "sACN" is Streaming sACN
• "AF" means Advanced Features is using the dimmer for load
recording
Source Info
• "SetLevels" means Set Levels or Dimmer Check is in use on
the dimmer
• "ACNDirect" is ACN Direct Control
• "Preset" followed by a number means a preset is running on
the dimmer
• "Panic" means the panic settings are in effect
• "--" means no control of the dimmer
Displays the current software version on your CEM3 processor. You can
About CEM3
also save a copy of the CEM3 User Guide to a USB drive.
Field Description
View and adjust the settings for any circuit in any rack connected to the
Dimmers
network. See Dimmer Property Definitions on page 17.
View and adjust the settings for the host Sensor3 rack. See Rack Property
Rack
Definitions on page 20.
Assign the space, circuit number, and module type for any circuit slot in the
rack. You can auto assign or manually edit the options for any circuit.
Circuit Assignment
For single and half-density modules such as the D20F, select Edit Circuit
Layout to adjust circuit numbering before you perform final patch updates.
Edit the patch and functionality for any port (DMX or sACN). See Patching
Patching
on page 34.
Set up and edit network properties for the CEM3. See Setting Up CEM3 on
Network
the Network on page 35.
Save configurations, load configurations, or upgrade CEM3 software using
File Operations either a USB memory device or an FTP server. See Saving or Uploading Files
and Firmware on page 30.
Record a panic look and set the specific details (such as fade and delay
Panic
times) for when a panic look is executed. See Setting Up Panic on page 32.
Set the rack’s time and date, or switch between automatic or manual time
Time/Date
setting.
Quickly set up the rack configuration. For more information see Performing
Quick Setup
a Quick Setup on page 4.
Adjust various settings regarding the user interface. See UI Preferences on
UI Preferences
page 16.
System Reference 15
UI Preferences
Adjust various settings regarding the user interface. Edit these settings in the UI Preferences Setup
screen [Setup]>UI Preferences.
Field Description
Adjust the settings of the backlight behind the display window. Choices are
Backlight Mode On, Off, and Auto. Auto will illuminate the window after a button press or
boot up for the time specified in Backlight Time. Default is Auto.
Appears only when Backlight Mode is set to Auto. Specify the time in
Backlight Time minutes and seconds (between 0:10 and 9:59) for the backlight to stay lit
after a reboot or button press. Default is 3:00.
Set the contrast of the display window. This can also be done from the
Contrast
home screen by holding the back arrow and using the scroll wheel.
Language Set the display language for the display window. Default is English.
Set the units used for the temperature display, Celsius (C) or Fahrenheit (F).
Temp Locale
Default is F.
Set the method of displaying sACN addresses: Universe/Channel (Uni/Ch) or
sACN
absolute address (Abs). Default is Uni/Ch.
System Reference 17
Dimmer Setup Submenu
Definition
screen (if applicable)
The current operating curve for the dimmer. Options are: Square,
Mod-Square, Linear, Mod-Linear, and more. See Dimmer Curves
Curve
on page 21 for a complete listing of curves and their
descriptions.
In switched mode the threshold value defines the control
percentage at which the output turns on. In dimmed mode, the
Threshold% threshold defines the level at which preheat is applied. See
Dimmer Output Diagram on page 26 for an illustration of how
threshold works with other dimmer properties.
Latch-Lock only. The control level range (as percentage) that
Control Settings On Level% causes the On Time to start counting down. Ranges available in
10% increments. Default is 41–50%. See Latch-Lock on page 7.
Latch-Lock only. The control level range (as percentage) that
Off Level% causes the Off Time to start counting down. Ranges available in
10% increments. Default is 81–90%. See Latch-Lock on page 7.
Latch-Lock only. The time that a level must be maintained before
On Time (sec) a circuit is switched on. Available range is 1–360 seconds.
Default is 5 seconds. See Latch-Lock on page 7.
Latch-Lock only. The time that a level must be maintained before
Off Time (sec) a circuit is switched off. Available range is 1–360 seconds.
Default is 5 seconds. See Latch-Lock on page 7.
DMX A The DMXA channel to which the circuit is patched.
Control whether the circuit receives 16-bit data from DMX A.
DMX A 16-Bit
Options are Yes or No (Default = No).
DMX B The DMXB channel to which the circuit is patched.
Control whether the circuit receives 16-bit data from DMX B.
Patching DMX B 16-Bit
Options are Yes or No (Default = No).
The sACN channel to which the circuit is patched. Displayed as
sACN either universe/channel or absolute, based on UI Preference
settings (see UI Preferences on page 16).
Control whether the circuit receives 16-bit data from sACN.
sACN 16-Bit
Options are Yes or No (Default = No).
System Reference 19
Rack Property Definitions
Each rack has specific properties that dictate how the rack is identified and functions. Edit these
properties in the Rack Setup screen ([Setup]>Rack).
Linear
The linear curve matches the control input percentage to Root Mean Squared (RMS) voltage output.
Each percent increase in control level increases dimmer voltage output by the same amount.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
System Reference 21
Square Law (Square)
At low control levels, much of a traditional incandescent fixture’s light output is in the invisible infrared
spectrum. This results in poor visible response to low control levels. A square law curve applies a
multiple derived from the square root of the control level (with full output equal to 1.00) to increase
voltage response at low control levels to compensate for the infrared loss.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
Stage 1
This curve matches the stage curve of the Transtechnik PM90 dimming system.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
System Reference 23
Stage 2
This is a traditional German stage lighting curve.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
Fluro1
This curve is specifically for Nesys fluorescent devices.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
Fluro 2
This curve is tuned to work with common 3-wire fluorescent ballasts.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
VIP 90
VIP90 is a curve specifically tuned to produce good dimming performance with the VIP-90 fluorescent
ballast from SE Light management AG, commonly used in European theatrical fluorescent luminaires.
100
80
60
Dimmer Output (%)
40
20
0
0 20 40 60 80 100
Control Input (%)
Custom
You can use ETC’s Concert software to configure up to five custom curves.
System Reference 25
Dimmer Output Diagram
This diagram illustrates the relationship between min scale, max scale, curve, threshold, and preheat
for the dimmer output from a CEM3 channel.
Threshold(%)
100%
Output Voltage Max Scale Voltage
Control Level
Configuration Selection
When a CEM3 processor that contains an existing configuration is moved to a different rack, the CEM3
will detect that it has been moved and prompt you to select the rack configuration to use. A timer
counts down from 15 seconds before defaulting to [Use the Rack Config]. Within 15 seconds you can
choose to [Abort] the operation.
• If the rack type is suited to work with the backplane configuration or the CEM3 configuration,
you can choose to use either configuration.
• If the rack type is not suited to work with the backplane configuration, you will be given an option
to select the backplane configuration or to clear the configuration and generate a new
configuration.
Incorrect Version
When switching CEM3 processors, the software version of the backplane may not match the software
version of the CEM3. This results in a backplane version mismatch. You can either [Generate New
Config] or [Use CEM3 Config].
When switching CEM3 processors, the rack type configuration may not match the configuration set on
the backplane switches. If this occurs the CEM3 processor will display a rack mismatch. Select
[Generate New Config] to generate a new default configuration.
Common Tasks 27
Preset Menu
Presets are recorded by taking a snapshot of the current levels for all circuits assigned to the space that
are set to be included in presets (see Allow in Preset on page 19). If a circuit is not set to be included
in presets, any level it is currently using will be withheld from the record action.
Sequence Menu
Sequences are recorded by taking a snapshot of the current levels for all circuits assigned to the space
that are set to be included in a step. If a circuit is not set to be included in a step, any level it is currently
using will be withheld from the record action.
Common Tasks 29
Saving or Uploading Files and Firmware
CEM3 allows you to save configurations to USB removable media, a computer connected to the
network (using the CEM3 web interface), or an FTP server on the network. Before you can use an FTP
server, you must configure it on the CEM module. See Working with Net3 Conductor Over FTP on page
36.
You can also upload a configuration or update the CEM3 software using the same methods.
Saving Configurations
To USB Media
1: Navigate to [Setup]>File Operations>Save to USB. The Save As screen will appear.
2: If desired, edit the name of the configuration using the scroll wheel and keypad.
a: Select the file name using the scroll wheel and press [Enter]. The first character of the rack
name will be highlighted.
b: Use the keypad to alter the selected character. Keypad numbers have standard keypad text
input letters. Multiple presses of any key will cycle through the number, lowercase letters, and
then uppercase letters for that key.
c: When the desired character is displayed, use the scroll wheel to move to the next character
in the rack name. If you want the name to be longer, press [Next] to add another character.
d: Repeat steps b–c until the desired rack name is displayed.
e: When the rack name is correct, press [Enter].
3: Select OK and press [Enter]. The configuration will be saved to the device.
To a Computer
To save a configuration to a computer on the system network, see Using the CEM3 Web Interface on
page 42.
To an FTP Server
Navigate to [Setup]>File Operations>Save to Server. You can edit the file name prior to saving using
the scroll wheel and the keypad to enter letters.
Loading Configurations
From USB Media
1: Navigate to [Setup]>File Operations>Load from USB. The Load File screen will appear.
2: Use the scroll wheel to navigate the file structure to the desired configuration file (the file name
will end in “.etc”) and press [Enter]. The configuration will load.
From a Computer
To load a configuration from a computer on the system network, see Using the CEM3 Web Interface
on page 42.
From a Computer
To load a configuration from a computer on the system network, see Using the CEM3 Web Interface
on page 42.
You can also use ETC UpdaterAtor software to upgrade your CEM3. UpdaterAtor can be downloaded
from the ETC website at etcconnect.com.
Common Tasks 31
Setting Up Panic
To fully enable panic functionality for your CEM3, the following criteria must be met:
• A maintained contact closure from a UL924-Listed triggering device has been wired to the panic
circuit on the CEM3 backplane (for more information, see the Sensor3 CEM3 Data Terminations
Guide that ships with the Sensor3 rack).
• The Emergency Contact switch on the CEM3 backplane is the correct position for the contact
closure type, either normally open (NO) or normally closed (NC).
• A snapshot of the desired panic look has been recorded in the CEM3 software.
Note: A panic look can be recorded regardless of whether you have a wired panic circuit.
Note: To configure panic mode through an electrical override without using the CEM3
module software, order the Hardwired Panic Accessory (7140K1002). Contact your
local dealer for more information.
WARNING: Power must be turned OFF when you perform this procedure. Before
removing dimmer or control modules for service, de-energize main feed to
dimmer rack and follow appropriate Lockout/Tagout procedures as described
in NFPA Standard 70E. It is important to note that electrical equipment such
as dimmer racks can present an arc flash safety hazard if improperly serviced.
This is due to available large short circuit currents on the feeders of the
equipment. Any work on energized equipment must comply with OSHA
Electrical Safe Working Practices.
Off
Time
Panic Panic
Activated Deactivated
Common Tasks 33
Patching
Patching governs the relationship between control sources (DMX A, DMX B, and sACN) and the rack’s
circuits, and is editable from the CEM3 face panel. Typically, repatching is used in portable rack
situations where the dimmer rack must adapt to different control sources and lighting systems. For
permanent rack installs, repatching is rarely needed.
You can patch racks that have only one assigned space using one of two methods: manual or
automatic. Racks with multiple assigned spaces can only be edited manually. For racks edited using an
automatic method, circuits will be numbered sequentially from the specified starting address following
the designated Balance setting (Straight, 1-Phrase, or 3-Phase) in Quick Setup. See Performing a Quick
Setup on page 4.
Any circuit set to a patch of 0 cannot be controlled from the data source specified.
Automatic Patching
Automatic patching is the final step in the Quick Setup utility. See Performing a Quick Setup on page 4.
Manual Patching
Note: Module density can affect patching. Prior to patching, make sure you set up the
module type in [Setup]>Circuit Assignment.
Manual patching allows you to patch on a circuit-by-circuit basis. There are two independent options
for manual patching: DMX and sACN. Both can be set individually for your needs.
1: Navigate to [Setup]>[Patching], and then select either Edit DMX Patch or Edit sACN Patch.
2: Press [Enter]. The Select Space screen will appear (if multiple spaces exist).
3: Select the desired space (if applicable) and then select OK. The Patch Table will open.
4: Use the scroll wheel or keypad to select the DMX port (A or B) or sACN universe and channel for
the desired circuit.
5: Press [Enter]. The field will become editable.
6: Scroll to or enter the desired channel from the keypad.
7: Press [Enter].
8: Repeat steps 4–7 for all desired circuits in the space.
9: Press [Back] when done. A confirmation dialog will open.
10: Select the appropriate option:
• [Yes/Save]: Save the changes
• [No/Cancel]: Cancel the changes
• [Continue Editing]: Edit additional circuits
11: Repeat steps 2–10 for any additional spaces.
Link Local
Choose Link Local if you work in a touring system where equipment changes frequently.
Link Local automatically assigns a randomly generated IP address within a given range.
DHCP
Choose DHCP if your system includes a DHCP server (for example, an Eos console).
This setting will attempt to acquire an IP address from a DHCP server. If the request fails, CEM3 will
acquire its address through Link Local (see above) for this boot cycle only. If rebooted, the rack will
attempt a DHCP request again.
Custom
With this method you can set the IP address (IP), Subnet (SN), and Gateway (GW) using the keypad. The
ETC convention for IP addressing is 10.101.xxx.yy (“x” varies by ETC product line, “y” is an incremental
value for products of the same type).
Common Tasks 35
Network Setup for Redundant Tracking Racks
The Redundant Tracking option is only available for ESR and FDX systems.
In a redundant tracking system, each processor has a separate network connection to which a separate
IP address may be assigned. When working in a redundant tracking system CEM3 will prompt you to
select the processor (A or B) for which you want to change the IP settings.
WARNING: To avoid the possibility of electric shock, power must be turned OFF when you
perform this procedure. Before removing dimmer or control modules, de-
energize main feed to dimmer rack and follow appropriate Lockout/Tagout
procedures as described in NFPA Standard 70E. It is important to note that
electrical equipment such as dimmer racks can present an arc flash safety
hazard if improperly serviced. This is due to available large short circuit
currents on the feeders of the equipment. Any work on energized equipment
must comply with OSHA Electrical Safe Working Practices.
On the CEM3 backplane, located in the rack behind the CEM3 control module, there is a small bank of
8 DIP switches. These switches were set when your system was commissioned by an ETC technician to
match the specific size, features, and desired behavior of your dimmer rack. Generally, you will not
need to alter these settings after commissioning. However, in the event that you must replace your
CEM3 control module or backplane, you will need to ensure these settings match the previous
controller.
Use this section to determine the required settings for your dimmer rack. There is also a label on the
underside of the CEM3 that explains the function of each switch.
When setting the DIP switches, you may also need to check the DMX A and DMX B termination
settings for the rack. See the backplane label to determine the appropriate position of the termination
switch.
DIP 1 : DBM
This switch disables the backplane memory so that the configuration is not stored on the rack itself.
Default is Off.
DIP 2 : AF
This switch should be set to On if your rack has Advanced Features (see Advanced Features (AF) on
page 6).
Note: For JSR dimmer racks intended for use with 100 VAC power feeds, both DIP 3 and
DIP 4 should be set to On.
DIP 5 : ND
This switch should be set to On if your rack includes a neutral disconnect.
DIPs 6–8
These DIP switches are used together to determine the number of module slots in your rack. Refer to
the table below to find the desired settings for your rack size.
DIP Number
Rack size
6 7 8
6 module slots Off On On
12 module slots Off On Off
24 module slots Off Off On
36 module slots On Off Off
48 module slots Off Off Off
Common Tasks 37
Maintaining and Cleaning the Rack
Proper air flow is necessary for your Sensor3 rack to function properly and consistently. Perform the
following procedures regularly to keep dust and foreign debris from impeding the proper function of
your rack.
Note: Sensor3 48-module racks have two filters, one stacked on top of the other with a
retention bar in the middle of the rack. Remove the top filter screen before removing
the bottom one.
2: Slide the filter upwards approximately 0.5 in. (1.25 cm) until the base of the filter clears the top
of the metal lip.
3: Pull the bottom of the air filter out and
away from the door far enough to clear the
retaining lip and slide the filter downwards
and out of the door frame.
4: In an area away from your dimmer rack
and other dust-sensitive equipment,
remove all dust or debris from the filter
using either compressed air or a vacuum.
5: Slide the top of the filter up into the slot at the top of the door until the base clears the metal
retaining lip at the bottom.
6: Ease the filter back into the door frame and carefully let it drop back into place.
Note: For Sensor3 48-module racks, install the bottom filter first. The top filter rests on the
top edge of the bottom filter.
WARNING: To avoid the possibility of electric shock, power must be turned OFF when you
perform this procedure. Before vacuuming dimmer or control modules de-
energize main feed to dimmer rack.and follow appropriate Lockout/Tagout
procedures as described in NFPA Standard 70E. It is important to note that
electrical equipment such as dimmer racks can present an arc flash safety
hazard if improperly serviced. This is due to available large short circuit
currents on the feeders of the equipment. Any work on energized equipment
must comply with OSHA Electrical Safe Working Practices.
Do not remove dimmer modules when vacuuming. Phase voltages inside the
rack can be deadly, and therefore only qualified technicians should be
allowed to remove modules and expose the inside of the dimmer rack.
CAUTION: Be careful not to push any foreign matter into the module.
5
OFF
6
OFF
11
OFF
12
OFF
Common Tasks 39
Replacing AF Cards
AF cards are located on the right side of the dimmer module slot between the copper neutral busses
and the dimming circuitry cards.
WARNING: To avoid the possibility of electric shock, power must be turned OFF when you
perform this procedure. Before removing modules or AF cards de-energize
main feed to dimmer rack and follow appropriate Lockout/Tagout
procedures as described in NFPA Standard 70E. It is important to note that
electrical equipment such as dimmer racks can present an arc flash safety
hazard if improperly serviced. This is due to available large short circuit
currents on the feeders of the equipment. Any work on energized equipment
must comply with OSHA Electrical Safe Working Practices.
Phase voltages inside the rack can be deadly, and therefore only qualified
technicians should be allowed to remove modules and expose the inside of
the dimmer rack.
S S S S S S S S
1 SR3-6 W W W W W W W W
(E)SR3-12 1 2 3 4 5 6 7 8
Card 1 0 0 00 0 0 0 1 ON
2 (E)SR3-24
0 OFF
Card 2 0 1000 0 0 0
1 0000 0 0 0
3 ESR3-36
Card 3
4 (E)SR3-48
Card 4 1 1000 0 0 0
CAUTION: Restoring rack defaults will erase all rack data. Do not perform this procedure
unless you absolutely intend to restore the rack back to its original factory
settings.
Common Tasks 41
Chapter 4
Web Access and Mobile App
This chapter describes the CEM3 web interface and the Sensor3 ThruPower System Reporter.
This page displays the software and power information for the rack, as well as any currently active error
messages.
Dimmers
This page allows you to view the current status of all circuits in the rack.
Setup
This page allows you to alter the Control Mode or Curve for any circuit in the rack. Click Apply Changes
when you have completed all the desired changes.
Presets Page
Note:
Rack#1
Rack Change Detected
- CEM3 Rack Rack #1 - Selection
Config CEM3 Rack
System
The OK
configuration in Systemyou
Would OK like to use
this CEM3 does not the configuration of Shown if rack type in
match the rack. the CEM3 or of the backplane and CEM3
Note: configuration files match.
DMX A: Offto DMX
Switching the B: Off
rack DMX rack
A: Off DMX B: Off
backplane? Select [Backplane Config] or
sACN:config
1/1 in 5s sACN: 1/1 [CEM3 Config].
[Use Rack Config] [Backplane Config]
[Quick Setup]
[Abort] [Info] [Quick Setup]
[CEM3 [Info]
Config]
Config
Rack #1 - Selection
CEM3 Rack
Systemyou
Would OK like to use Shown if rack type in
the configuration of backplane and config
do not match. Select
the CEM3 or of the Note: [Clear Configuration] to
DMX rack
A: Off DMX B: Off
backplane? generate a new default config
sACN: 1/1 or select
[Backplane Config].
[Backplane Config]
[Quick
[ClearSetup] [Info]
Configuration]
System OK displays “System OK” if no error state exits. If error states exits, the system status display will scroll through errors.
Highlight an error and press [Enter] to clear it.
Presets Active
10.101.101.101
displays the first DMX A and DMX B patched values by lug or “OFF”
DMX A: Off DMX B:
B: Off
Off
displays the current sACN address in universe/channel or absolute format depending on configuration setting
sACN: 1/1
1/1 (see UI Preferences) or “OFF”
[Quick Setup]
[Quick Setup] [Info]
[Info] [Quick Setup] is shown if the rack property “Setup at Home” is set to Yes. See Rack in the Setup menu flow chart.
Highlight [Quick Setup] and press [Enter] to access the Quick Setup menu (see the Quick Setup menu flow chart).
Highlight [Info] and press [Enter] to access View/Clear Errors (see the Info menu flow chart below the
Quick Setup menu flow chart).
Panic
Rack #1 - CEM3 Rack Rack #1 - CEM3 Rack
System OK System OK Panic operation:
Presets Active Presets Active If Out Delay is set to Manual,
10.101.101.101 Panic is active. following clearing of the
Note: See Setup menu flow chart 10.101.101.101 electrical panic select
DMX A: Off DMX B: Off Note:
for Panic settings. DMX A: Off DMX B: Off [Restore Control] to clear
sACN: 1/1
1/1 sACN: 1/1
1/1 the panic look.
Panic Active! Panic Ended!
[Quick Setup] [Info]
[Info] [Quick Setup]
[Restore [Info]
Control]
AF Card Upgrade
Rack #1 - CEM3 Rack
System OK AF Card #1
Upgrading
Presets Active
10.101.101.101 AF Card is being upgraded.
Note:
DMX A: Off DMX B: Off
sACN: 1/1
1/1
Redundant Tracking
Rack CEM3
#1 - Control
CEM3 Rack Rack #1 - CEM3 Rack
System OK System OK
Redundant Tracking: Presets Active Redundant Tracking:
Backup Ready the home screen of 10.101.101.101 the home screen of
Note: processor B when Note: processor B when
DMX A: Off DMX B: Off processor A is in control. DMX A: Off DMX B: Off processor B is in control.
sACN: 1/1 sACN: 1/1
1/1
Rack #1 - CEM3 Rack Quick Setup: Module Select Module Type Select Module
System OK [Dimmer] [D15]
Presets Active [Relay] [D15AF] Module Types and Modules
10.101.101.101 Rack Type: SR48 [Relay (ND)] [D20J] displayed vary by rack type.
DMX A: Off DMX B: Off Module: [Unchanged] [Thru Relay] [D20AF] Note: Modules with no configurable
sACN: 1/1
1/1 [Fluorescent] [D20AFN] settings (AFM, CC)
are not displayed.
[Low Wattage] [D20AFNJ]
[Quick Setup] [Info]
[Info] [Abort] [Next] [Generic]
About Dimmer 1 [D20AFG]
Numbering:[Unchanged]
Quick Setup: DimDbl
[Abort] [Next]
Patch: [Independent]
DMXA: [Off]
DMXB: [Off]
sACN Universe: [1]
sACN Address: [1]
[Abort] [Next]
Patch: [UniverseSplit]
DMXA:Ckt1 @ [Off]
Note: Patch mode Universe Split
DMXB:Ckt - @ Off is not available when
sACN Universe: [1] dimmer doubling.
sACN Address: [1]
[Abort] [Next]
Rack #1 Set/Override
Dimmer - CEM3 Rack Select Space Set Levels Release Set Levels
System
[Set OK Levels]
Local 1: -- 2: --
[Set System Levels] Space: [1] 3: -- 4: -- Release Set Levels? Set Levels in
[Dimmer Check] Space1 5: -- 6: -- Space 1
DMX A: Off
[Release DMXLvls]
Systm B: Off 7: -- 8: -- Yes have been released
sACN: 1/1
[Presets] 9: -- 10: -- No
[Sequences] 11: -- 12: --
[Quick Setup]
[Release [Info]
All Arch] [Cancel] [OK] 13: -- Dimmer14: 1--
About About Dimmer 1 About Dimmer 1
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check]
Note: Set Levels
Yes
This screen is not shown No
if lugs in the rack are
configured to one space.
About Dimmer 1
Rack
Dimmer
#1 Set/Override
- CEM3 Rack Select Space Set Circuits Set Levels Release Set Levels
System
[Set OK Levels]
Local Enter circuit numbers
[Set System Levels] Space: [1] to set levels Release Set Levels? Set Levels in
[Dimmer Check] Space1 Space 1
DMX A: Off
[Release DMXLvls]
Systm B: Off > Yes have been released
sACN: 1/1
[Presets] No
[Sequences]
[Quick Setup]
[Release [Info]
All Arch] [Cancel] [OK] About Dimmer 1 About Dimmer 1 About Dimmer 1
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check]
Set Levels
Note:
Release Set Levels?
Yes
This screen is not shown No
if lugs in the rack are
configured to one space.
About Dimmer 1
Rack
Dimmer
#1 Set/Override
- CEM3 Rack RackDimmer Check
#1 - CEM3 Rack
System
[Set OK Levels]
Local Systemby:
Check OK [Lug]
[Set System Levels] Lug: [1]
[Dimmer Check] Level (%): [100]
DMX A: Off
[Release DMXLvls]
Systm B: Off DMX A: Off DMX B: Off
sACN: 1/1
[Presets] sACN: 1/1
[Sequences]
[Quick Setup]
[Release [Info]
All Arch] [Quick
<<< Setup] [Next>>>
Prev] [Info]
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check] RackDimmer
#1 - CEM3
Check
Rack
Systemby:
Check OK [Circuit]
Ckt: [1]
Level (%): [100]
DMX A: Off DMX B: [1]
Space: Off
sACN: 1/1
[Quick
<<< Setup] [Next>>>
Prev] [Info]
Rack
Dimmer
#1 Set/Override
- CEM3 Rack Select Space Release Set Levels
System
[Set OK Levels]
Local
[Set System Levels] Space: [All Spaces] Set Levels in
[Dimmer Check] All Spaces All Spaces
DMX A: Off
[Release DMXLvls]
Systm B: Off have been released
sACN: 1/1
[Presets]
[Sequences]
[Quick Setup]
[Release [Info]
All Arch] [Cancel] [OK] About Dimmer 1
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check]
Note:
Rack #1 Set/Override
Dimmer - CEM3 Rack
System
[Set OK Levels]
Local
Select Space Sequence Sequence
[Set System Levels]
Space Space1 Space Space1
[Dimmer Check] Space: [1] Sequence Inactive Sequence Active
DMX A: Off
[Release DMXLvls]
Systm B: Off Space1 [Activate] [Deactivate]
sACN: 1/1
[Presets]
[Edit Steps] [Edit Steps]
[Sequences]
[Auto Setup] [Auto Setup]
[Quick Setup]
[Release [Info]
All Arch]
[Record Rig Check] [Cancel] [OK]
[Run Rig Check]
[Clear Rig Check]
Rack
Dimmer
#1 Set/Override
- CEM3 Rack Release All Arch
System
[Set OK Levels]
Local
[Set System Levels]
[Dimmer Check] All Arch levels
DMX A: Off
[Release DMXLvls]
Systm B: Off have been released
sACN: 1/1
[Presets]
[Sequences]
[Quick Setup]
[Release [Info]
All Arch] About Dimmer 1
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check]
Rack
Dimmer
#1 Set/Override
- CEM3 Rack Select Space Record Rig Check
System
[Set OK Levels]
Local
[Set System Levels] Space: [1] Recording Rig Check The seconds displayed will General Note: Rig Check
[Dimmer Check] Space1 in 5s count down from the property options are only available
Note: AF Reaction Time set in in racks with AF enabled
DMX A: Off
[Release DMXLvls]
Systm B: Off Setup/Dimmers/Advanced Feat and are not available in
sACN: 1/1
[Presets] toward zero before non-AF and FDX racks.
[Sequences] recording a rig check
look.
[Quick Setup]
[Release [Info]
All Arch] [Cancel] [OK] <back to abort>
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check]
Note:
Rack
Dimmer
#1 Set/Override
- CEM3 Rack Select Space Run Rig Check Run Rig Check These screens are displayed
System
[Set OK Levels]
Local if a rig check look has been
recorded. The seconds displayed
[Set System Levels] Space: [1] Running Rig Check Running Rig Check will count down from the property
[Dimmer Check] Space1 Please Wait... Please Wait... AF Reaction Time (set in
DMX A: Off DMXLvls]
B: Off Note: Setup/Dimmers/Advanced Features)
[Release Systm toward zero as the look fades up,
sACN: 1/1
[Presets] and the seconds will count down
[Sequences] Fading Look Up: 5s Measuring Loads: 5s again as the loads are measured
while the look is held. Select [Back]
[Quick Setup]
[Release [Info]
All Arch] [Cancel] [OK] <back to abort> <back to abort> to return to the DimmerSet/Override
[Record Rig Check] screen.
[Run Rig Check]
[Clear Rig Check] Note:
Run Rig Check
Rack
Dimmer
#1 Set/Override
- CEM3 Rack Select Space Clear Rig Check
System
[Set OK Levels]
Local
[Set System Levels] Space: [1] Rig Check Look
[Dimmer Check] Space1 Cleared
DMX A: Off
[Release DMXLvls]
Systm B: Off
sACN: 1/1
[Presets]
[Sequences]
[Quick Setup]
[Release [Info]
All Arch] [Cancel] [OK]
[Record Rig Check]
[Run Rig Check]
[Clear Rig Check]
Rack #1 About
- CEM3 Rack Select Space About Dimmer
System OK
[Dimmers] Circuit: [1]
[Rack] Space: [1] Space 1: Space1 Recorded Load and
Actual Load are only shown
[Errors] Space1 Rack 1: CEM3 Rack for dimmers with Advanced
DMX A: Off
[Source Info]DMX B: Off Lug: 1 Features. See Setup/Dimmers/
Note: Advanced Features. Recorded
sACN: 1/1
[About CEM3] Level: 0% Load and Actual Load are only
Control Src: sACN shown if the dimmer is in the
[Quick Setup] [Info] [Cancel] [OK] Ctrl Mode: Dimmable local rack; they are not shown
Recorded Load: 0.0A if the dimmer is in a network-
connected rack.
Actual Load: 12.0A
Note:
Rack #1 About
- CEM3 Rack About Rack 1
System OK
[Dimmers] Name: CEM3 Rack
[Rack] Rack Type: SR48
[Errors] CPU Temp: 97°F
DMX A: Off
[Source Info]DMX B: Off Temp 1: 34C
sACN: 1/1
[About CEM3] Temp 2: 22C
Status: Errors Exist
[Quick Setup] [Info] SW Ver: 1.7.0.9.0.XX Temp 1 and Temp 2
Note: are only shown in FDX racks.
Frequency: 60Hz See Setup/UI Preferences/
X:118 Y:117 Z:118 Temp Locale.
Patch:
DMXA: 1 ~ 96
DMXB: 1 ~ 96
sACN: 1/1 ~
1/96
Panic State: Ready
Rack #1 About
- CEM3 Rack Rack
View/Clear
#1 - CEM3
Errors
Rack
System OK
[Dimmers] System OK
Fan Fail
[Rack] Select an error
[Errors] Note: and press [Enter] to clear
DMX A: Off
[Source Info]DMX B: Off DMX A: Off DMX B: Off it. If the error cannot
be cleared, it will stay
sACN: 1/1
[About CEM3] sACN: 1/1 in the list .
Rack #1 About
- CEM3 Rack Select Space Source Information
System OK
[Dimmers] Space: Space1
[Rack] Space: [1] Ckt HTPSource Lvl
[Errors] Space1 1 Preset 33 33% Space name is not shown
DMX A: Off
[Source Info]DMX B: Off 2 sACN FL% Note: if the system has only one
sACN: 1/1
[About CEM3] space.
3 SetLevels 55%
4 ACNDirect FL%
[Quick Setup] [Info] [Cancel] [OK] 5 sACN 45%
Note:
Rack #1 About
- CEM3 Rack About
Rack #1 CEM3
- CEM3 Rack
System OK
[Dimmers] System
ETC OK
CEM3 v1.7.0
[Rack] To save a copy of the [Save Manual] saves a
[Errors] user manual, insert copy of the CEM3 User Manual
Note: to the root of the USB key
DMX A: Off
[Source Info]DMX B: Off DMX A: key
a USB Off and
DMXpress
B: Off with file name
sACN: 1/1
[About CEM3] sACN: 1/1
enter. CEM3_Manual.pdf.
Rack #1 -Setup
CEM3 Rack Select Space Setup Space1 Select Module Type Select Module
System OK
[Dimmers] Ckt [1] [AFM] [D15]
[Rack] Space: [1] Module: [D20AF] [Constant Current] [D15AF]
[Circuit Assignment] Space1 Control: [Dimmable] [Dimmer] [D20J]
DMX A: Off DMX B: Off
[Patching] Firing: [Normal] [Relay] [D20AF]
sACN: 1/1
[Network] Control Settings [Relay (ND)] [D20AFN]
[File Operations] Patching [Thru Relay] [D20AFNJ]
[Quick Setup]
[Panic] [Info] [Cancel] [OK] Dimming Settings [Fluorescent]
About Dimmer 1 [D20AFG]
[Time/Date] Panic/Arch Settings [Low Wattage] [D20AFJ]
[Quick Setup] Advanced Features [Generic] [D20HR]
[UI Preferences]
Note:
Rack #1 - CEM3
Rack SetupRack Rack
Data#1Loss
- CEM3
Behavior
Rack
System
Rack OK
Number: [1] System OK[Crossfade]
DMXA:
System Number: [1] Fade Time: [2]
Data Ports: Wait Time: [180]
DMX
DMX A:
A:Off[Disabled]
DMX B: Off DMX A: Off
Preset DMX B:
Space: Off
[1]
sACN:
DMX B:1/1 [Disabled] sACN:
Preset1/1Number: [16]
sACN: [Enabled] DMXB: [Wait & Fade]
[Quick
Arch Setup] [100]
Priority: [Info] [Quick Setup]
Fade Time: [Info]
[2]
Off as Release:[Yes] Wait Time: [180]
Fan: [30] sACN: [Wait & Fade]
AF Enabled: [Yes] Fade Time: [2]
Presets on Boot: [N] Wait Time: [180]
Setup at Home: [Yes]
Volt High Warn:[Yes]
Temp High Warn:[Yes]
Station Power: [Off]
Remote Record: [No]
[Data Loss Behavior]
Rack #1 -Setup
CEM3 Rack Circuit Assignment Auto Ckt Assignment Confirmation
System OK
[Dimmers] [Auto Assign...] You have selected to
[Rack] [Edit Circuit Layout] Numbering: [Straight] renumber all dimmers
[Circuit Assignment] First Circuit: [1] in the rack.
DMX A: Off DMX B: Off
[Patching] Space: [1] Are you sure you
sACN: 1/1
[Network] want to do this?
[File Operations]
[Quick Setup]
[Panic] [Info] [Cancel] [Renumber] [No!] [Yes/Renumber]
[Time/Date]
[Quick Setup]
[UI Preferences]
Confirmation
You have selected to
renumber all dimmers
in the rack.
Are you sure you
Auto Ckt Assignment want to do this?
[Cancel] [Renumber]
Note: A T T E N T I O N !
[No/Cancel]
[Yes/Save]
Module choices vary by
rack type. [Continue Editing]
A T T E N T I O N !
Note:
A T T E N T I O N !
Rack #1Patch
- CEM3
Table
Rack A T T E N T I O N !
Note: System OK
Ckt sACN
1 [ 7] Save Patch Table
2 [ 8] Changes Before
DMX A:3Off[ DMX B: Off
13] Exiting?
sACN: 1/1
4 [ 13] [No/Cancel]
This screen is not shown
if the system has only one 5 [ 19] [Yes/Save]
space. [Quick 6Setup]
[ [Info]
20] [Continue Editing]
Note: A T T E N T I O N !
Rack #1 -Setup
CEM3 Rack Select Processor Network Setup
System OK
[Dimmers] [Main(A) Processor] Type: [Custom]
[Rack] [Backup(B) Processor] IP: [ 10.101.101.101]
[Circuit Assignment] SN: [ 255.255.0.0]
DMX A: Off DMX B: Off
[Patching] GW: [ 10.101.1.11]
sACN: 1/1
[Network]
[File Operations]
[Quick Setup]
[Panic] [Info] [Cancel] [OK] [Abort] [Commit]
[Time/Date]
[Quick Setup]
[UI Preferences] Network Setup
Note: Type: [DHCP]
IP: [ 10.101.101.101]
SN: [ 255.255.0.0]
GW: [ 10.101.1.11]
This screen is only
shown if the CEM3 is in
a tracking backplane. [Abort] [Commit]
Network Setup A T T E N T I O N !
Type: [Link Local]
IP: [ 10.101.101.101] Save Network Settings
Before Exiting?
[No/Cancel]
[Yes/Save]
[Abort] [Commit] [Continue Editing]
A T T E N T I O N !
[No/Cancel]
[Yes/Save]
[Continue Editing]
A T T E N T I O N !
[No/Cancel]
[Yes/Save]
[Continue Editing]
File Operations
[Save to USB] [Cancel] [OK]
[Load from USB]
[Upgrade from USB]
[Save to Server]
[Load from Server]
[Upgrade from Server]
[Set up Server]
File Operations
[Save to USB]
[Load from USB]
[Upgrade from USB]
[Save to Server]
[Load from Server]
[Upgrade from Server]
[Set up Server] Load cfg file
Rack001.etc
File Operations
[Save to USB]
[Load from USB] [Cancel] [OK]
[Upgrade from USB]
[Save to Server]
[Load from Server]
[Upgrade from Server]
[Set up Server]
File Operations
[Save to USB]
[Load from USB]
[Upgrade from USB]
[Save to Server]
[Load from Server]
[Upgrade from Server]
[Set up Server] Software Upgrade Software Upgrade
cem3_v1_6_0.bld Are you sure you
want to upgrade the
operating software to
file:
cem3_v1_7_0.bld ?
File Operations
[Save to USB]
[Load from USB] [No] [Yes]
[Upgrade from USB]
[Save to Server]
[Load from Server] Software Upgrade
[Upgrade from Server] Are you sure you
[Set up Server] want to upgrade the
operating software to
file:
cem3_v1_7_0.bld ?
[No] [Yes]
[No/Cancel]
[Yes/Save]
Rack #1 -Setup
CEM3 Rack Set Time/Date
System OK
[Dimmers] Mode: [Manual]
[Rack] Time Hour: [10]
[Circuit Assignment] Time Minutes: [08]
DMX A: Off DMX B: Off
[Patching] Year: [2017]
sACN: 1/1
[Network] Month: [Jun]
[File Operations] Day: [20]
[Quick Setup]
[Panic] [Info]
[Time/Date]
[Quick Setup]
[UI Preferences] Set Time/Date
Mode: [Automatic]
Offset from UTC: [0]
Time Service: Found
Current Time:
20 Jun 2017 15:08
Rack #1 -Setup
CEM3 Rack
System OK
[Dimmers]
[Rack]
[Circuit Assignment]
DMX A: Off DMX B: Off
[Patching]
sACN: 1/1
[Network] Note: See Quick Setup menu
[File Operations] flow chart.
[Quick Setup]
[Panic] [Info]
[Time/Date]
[Quick Setup]
[UI Preferences]
Rack #1 -Setup
CEM3 Rack UI Preferences
System OK
[Dimmers] Backlight Mode: [Auto]
[Rack] Backlight Time: [05:00]
[Circuit Assignment] Contrast: [29] Backlight Time will
DMX A: Off DMX B: Off
[Patching] Language: [English] Note: only appear if
Backlight Mode is set
sACN: 1/1
[Network] Temp Locale: [F] to Auto.
[File Operations] sACN: [Uni/Ch]
[Quick Setup]
[Panic] [Info]
[Time/Date]
[Quick Setup]
[UI Preferences]
WARNING: To avoid the possibility of electric shock, power must be turned OFF before
removing dimmer or control modules. Prior to any action that involves
removing any module, de-energize main feed to dimmer rack and follow
appropriate Lockout/Tagout procedures as described in NFPA Standard 70E.
It is important to note that electrical equipment such as dimmer racks can
present an arc flash safety hazard if improperly serviced. This is due to
available large short circuit currents on the feeders of the equipment. Any
work on energized equipment must comply with OSHA Electrical Safe
Working Practices.
Phase voltages inside the rack can be deadly, therefore only qualified
technicians should be allowed to remove modules and expose the inside of
the dimmer rack.
Error Messages 57
Message Cause Possible Corrective Action
The power on phase B is above the
Phase B Volts Check the incoming power supply to the rack.
volts high warning level (in
High Contact a qualified electrician.
[Setup]>Rack)
The power on phase C is above the
Phase C Volts Check the incoming power supply to the rack.
volts high warning level (in
High Contact a qualified electrician.
[Setup]>Rack)
Phase A Volts The voltage on phase A is below the Check the incoming power supply to the rack.
Low minimum required value for the CEM3 Contact a qualified electrician.
The voltage on phase B is below the Check the incoming power supply to the rack.
Phase B Volts Low
minimum required value for the CEM3 Contact a qualified electrician.
Phase C Volts The voltage on phase C is below the Check the incoming power supply to the rack.
Low minimum required value for the CEM3 Contact a qualified electrician.
The voltage on phase A is above the Check the incoming power supply to the rack.
Phase A Overvolts
maximum value for the CEM3 Contact a qualified electrician.
The voltage on phase B is above the Check the incoming power supply to the rack.
Phase B Overvolts
maximum value for the CEM3 Contact a qualified electrician.
The voltage on phase C is above the Check the incoming power supply to the rack.
Phase C Overvolts
maximum value for the CEM3 Contact a qualified electrician.
The CEM3 is unable to communicate
Rack Memory Check the CEM3 is seated correctly; Replace
with the memory chip on the
Error backplane
backplane
The CEM3 is unable to detect the rack
Check the CEM3 is seated correctly; Replace the
Rack Detect Error type from the DIP switches on the
backplane
backplane
The CEM3 detects that the rack fan is
Fan Fail drawing current outside the expected Check the rack fan and fan fuse.
value
A config was loaded that contained Regenerate configuration; contact ETC Technical
Config Rejected
invalid data or values Services
Check the AF cards and CEM3 are seated
The CEM3 is unable to communicate
AF Card Error 1 correctly; Check rack hardware for damage.
with AF card 1
Check DIP switch settings.
Check the AF cards and CEM3 are seated
The CEM3 is unable to communicate
AF Card Error 2 correctly; Check rack hardware for damage.
with AF card 2
Check DIP switch settings.
Check the AF cards and CEM3 are seated
The CEM3 is unable to communicate
AF Card Error 3 correctly; Check rack hardware for damage.
with AF card 3
Check DIP switch settings.
Check the AF cards and CEM3 are seated
The CEM3 is unable to communicate
AF Card Error 4 correctly; Check rack hardware for damage.
with AF card 4
Check DIP switch settings.
AF Card 1
AF card 1 is loading software Wait until software load has completed
Loading
AF Card 2
AF card 2 is loading software Wait until software load has completed
Loading
AF Card 3
AF card 3 is loading software Wait until software load has completed
Loading
AF Card 4
AF card 4 is loading software Wait until software load has completed
Loading
Error Messages 59
Appendix C
Redundant Tracking Systems
CEM3 features the ability to support dual redundant controllers in ESR24, ESR36 and ESR48 rack types,
as well as in the FDX3000 rack.
Redundant controllers provide extra security in the event of system failure, allowing a secondary
processor to immediately take control of the rack.
abc def at
Reset
Test ghi jkl mno and
Controller B
Enter
About Back pqrs tuv wxyz thru
Controller A
Redundant
Tracking Switch
Controller B
Automatic Control
Typically, in a redundant tracking system, the switch should be left in the auto position. When the
switch is set to auto, the A processor will have control by default. Control will switch to B when any of
the following events occur.
Loss of DMX
If DMX is lost by one processor but not the other, control will switch to the one still able to receive DMX
(note that the DMX data line is interconnected between both, so this would only occur in the event of
the failure of a DMX transceiver on the processor itself).
Power errors
If one processor experiences power errors but the other does not, control will switch to the one that
does not. Again, note that the same power is connected to both processors so this would only occur
in the event of an internal failure in the processor.
Display Status
When tracking is active and the A processor is in control, the displays will show as follows:
[Info]
CEM3 Control
Processor B
Backup Ready
CEM3 Control
[Info]
The switchover from A to B for dimming happens instantaneously, so that control of lights is not lost.
However, the switchover of the user interface has built in hysteresis to eliminate bounce in certain
circumstances (for example, when DMX is lost, both processors may not see and account for the DMX
loss at exactly the same time). For this reason it may sometimes appear to take a long time for the user
interface of the backup unit to start up; however, bear in mind that despite this apparent delay,
dimming control always transfers near-instantaneously.
Hardware
Front Panel
The FDX3000 carrier contains two CEM3 modules in a dual redundant configuration.
PSU Indicators
Redundant
Tracking
switch
PSU Indicators
The PSU indicators show the status of the two internal power supplies that supply the 15 VDC required
by FDX dimmer modules.
The two indicators should be lit at all times. If either is not lit, this could indicate a failure of the internal
power supply. If you see this condition, contact ETC Technical Services (see page 2).
DIMMER OUTPUTS
A B C D E F G H
DMX A DMX B
POWER
Panic Return
Panic Send
NET A NET B
Panic Out
Station +
Station -
+24VDC
Beacon
Grid
FEEDBACK
EXT
FUSES
15VDC
Option Connector
Dimmer Outputs
The dimmer outputs connect from the FDX3000 processor to the dimmer module trays. They should
generally be preconfigured from the factory. They are grouped in blocks of 12 dimmers, from A (1–12)
through H (85–96).
Feedback
The feedback connections allow the FDX3000 to determine the status of voltage and current for
modules that support sensing. The two feedback connections should be made from the factory.
15 VDC
The 15 VDC connection provides 15 V power to the FDX dimmer modules.
Option Connector
The option connector allows field connection of the rack options such as panic (see page 32), stations
(see page 10), and a remote beacon. For information on these connections, see the termination
markings on the rear of the FDX3000 carrier.
DMX Connections
The FDX3000 processor features DMX In and Thru connections on two industry-standard 5-pin
XLR connectors. The two DMX ports, A and B, are fed to both of the redundant processors.
Ethernet Connections
Two Ethernet connections are provided using Neutrik® etherCON® connectors, which may be either
connected to a Neutrik etherCON jack or a standard RJ45 connector. Net A connects to the A (upper)
CEM3, and Net B connects to the lower. The CEM3s feature an internal switch allowing use of the rear
and front panel Ethernet connections at the same time.
Power Input
The power input connector is a three phase supply, fed from the supply in the rack. The FDX3000
processor will function regardless of any phase loss; as long as at least one phase is still active the
processor will still dim any dimmers which still have power.
Regulatory Information
The FDX3000 rack is certified to the following CE standards:
• Safety: EN61439-1 (Low voltage Switchgear and Controlgear assemblies)
• Electromagnetic Immunity: EN61547 (EMC Immunity for Lighting Systems)
Initial Setup
Module Count
The FDX3000 controller supports between 1 and 96 dimmers. The number of dimmers is configured
using DIP switches on the backplane of the controller.
64 32 16 8 4 2 1
For example, to set up the rack for 96 modules, set DIP switches 32 and 64 to ON.
4: Reinstall the CEM3 modules.
5: Power up the rack.
Module Types
The following module types are supported in FDX:
• Blank : Used where a blank plate is fitted; gives no control and no feedback
• NoV-Nol : A dimmer module with no current or voltage feedback
• V-Nol : A dimmer module with voltage feedback but no current feedback
• NoV-I : A dimmer module with current feedback but no voltage feedback
• V-I : A dimmer module with voltage and current feedback
FDX 3000
Rack
NEUTRAL Load
Because the dimmer is at a low level, the roasting short does not draw enough current to trip the circuit
breaker. However, a roasting short is still a dangerous condition as currents can flow at a high enough
amperage to cause heat or, in extreme circumstances, fire.
The FDX3000 rack has the capability to detect this condition. When a roasting short is detected by a
module set to V/I mode, the dimmer is automatically driven to full, allowing the high current of the
short circuit to trip the circuit breaker.
This utility is automatically enabled on any modules set to V/I mode.