ADVC 207A FV Loop Automation
ADVC 207A FV Loop Automation
● Rule E:
- The Tie ACR trips when power flow
reduces by 50%, or
- Power flow direction reversal
● Rule E:
- The Tie ACR trips when power flow
reduces by 50%, or
- Power flow direction reversal
Tie ACR
Feeder ACR
● Rule E:
- The Tie ACR trips when power flow
reduces by 50%, or
- Power flow direction reversal
Tie ACR
Feeder ACR
● Disadvantage
MID-POINT RECLOSER
LA TIME CHANGE SETTINGS
TIE RECLOSER
LA TIME CLOSE
ADJACENT
FEEDER TIE TIMEOUT
● Pickup
- Block Trigger causes Loop Automation
to ignore any loss of supply events
while in pickup.
- Allow Trigger should be used if the
Fault Reset Time is longer than the
Supply Timeout setting.
● Activation Delay
- 3 – 1800 seconds
● Pickup
- Blocks Trigger or Allows Trigger
● Auto Restore
- Available/Not Available
- On/Off
ENGINEERING MENU
Protection menu
Configuration menu
↕
Power quality
Telemetry menu
Automation menu
Measurements menu
TELEMETRY MENU
Current
Voltage
↕
Configure Ports
Configure Comms
↕ Frequency
CONFIGURATION MENU Power
System settings
Feature selection
↕ Energy
Demand
Radio
Maintenance
IOEX Status
AUTOMATION
Loop Auto Available
Schneider Electric – < AUTHOR > – <DATE> 25
Loop Automation Configuration on the Panel
ENGINEERING MENU
Protection menu
Configuration menu
↕
Power quality
Telemetry menu
Automation menu
Measurements menu
TELEMETRY MENU
Current
Voltage
↕
Configure Ports
Configure Comms
↕ Frequency
CONFIGURATION MENU Power
System settings
Feature selection
↕ Energy
Demand
Radio
Maintenance
IOEX Status
ENGINEERING MENU
Protection menu
Configuration menu
↕
Power quality
Telemetry menu
Automation menu
Measurements menu
AUTOMATION
AUTOMATION MENU AUTOMATION MENU
Loop Auto On/Off
Loop Auto Status
↕
Loop Auto On Tie/Midpoint/Feeder ACR Delay Time 30s
Tie Restore One/Both way
Delay Time
AUTOMATION MENU LOP/Loop Linked/Unlinked
AUTOMATION MENU
Auto Restore Avail/Not Av
Loop Automation Normal Auto Restore On/Off
LOP/Loop Unlinked
AUTOMATION MENU
AutoRestore OFF
Schneider Electric – < AUTHOR > – <DATE> 27
Loop Automation - Review
● What are the three types of ACR in a Loop Automation scheme?
Feeder, Mid-Point and Tie
● What would ACRs used in an Auto Changeover scheme be designated?
- Feeder – Preferred Supply
- Tie – Alternate Supply
● What does an ‘End of Sequence’ event indicate?
- An auto reclose sequence has gone through to what would normally be
‘Lockout’, but Loop Automation is on, and a close could occur
automatically.
● In order to ensure that Loop Automation only comes into effect when there
is no possibility of the supply being restored by an auto reclose, the Loop
Automation time should be set longer than:
- The longest possible Auto Reclose time
(minus the supply timeout, plus a safety margin)
● What state must an ACR be in to be designated a Tie ACR?
- Open.