GF Signet Mag Flow Meter Insertion Type

The document describes the Signet 2551 Magmeter Flow Sensor. It is an insertion style magnetic flow sensor with no moving parts that can measure flow in pipes from 1/2 to 36 inches. It has various output options and is available in corrosion resistant materials like polypropylene and PVDF.

Uploaded by

Imran Ahmed Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
119 views6 pages

GF Signet Mag Flow Meter Insertion Type

The document describes the Signet 2551 Magmeter Flow Sensor. It is an insertion style magnetic flow sensor with no moving parts that can measure flow in pipes from 1/2 to 36 inches. It has various output options and is available in corrosion resistant materials like polypropylene and PVDF.

Uploaded by

Imran Ahmed Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Signet 2551 Magmeter Flow Sensor

Available in a variety of wetted materials and ideal


for pipe sizes up to DN900 (36 in.)
Features
• Test certificate included for -X0, -X1

• Patented Magmeter technology*

• No moving parts

• Bi-directional flow

• Empty pipe detection

• Installs into pipe sizes DN15 to DN900


(0.5 to 36 in.)

• Operating range 0.05 to 10 m/s (0.15 to 33 ft/s)

• Accurate measurement even in dirty liquids

• Polypropylene and PVDF retaining nuts


The Signet 2551 Magmeter is an insertion style standard, Valox optional
magnetic flow sensor that features no moving parts.
The patented* sensor design is available in corrosion- • 4 to 20 mA, digital (S3L), frequency,
resistant materials to provide long-term reliability with relay output (Display only)
minimal maintenance costs. Material options include
PP with stainless steel, PVDF with Hastelloy-C, or PVDF • No pressure drop
with Titanium. Utilizing the comprehensive line of Signet
installation fittings, sensor alignment and insertion depth • Corrosion resistant materials; PP or PVDF with SS,
is automatic. These versatile, simple-to-install sensors Hastelloy-C, or Titanium
deliver accurate flow measurement over a wide dynamic
range in pipe sizes ranging from DN15 to DN900 (½ to • Multi-language display menu available
36 inches), satisfying the requirements of many diverse
applications.

Signet 2551 Magmeters offer many output options


of frequency/digital (S3L) or 4 to 20 mA which are MEASURING EQUIPMENT

available on both the blind and display versions. The 77CJ

frequency or digital (S3L) sensor output can be used (3-2551-PX-XX


with Signet’s extensive line of flow instruments while version only)
the 4 to 20 mA output can be used for a direct input to
Applications
PLCs, chart recorders, etc. Both the 4 to 20 mA output
and digital (S3L) sensor interface is available for long • Chemical Processing
distance signal transmission. An additional benefit is the • Water and Wastewater Monitoring
empty pipe detection which features a zero flow output • Metal Recovery and Landfill Leachate
when the sensors are not completely wetted. Also, the • Commercial Pools, Spas, and Aquariums
frequency output is bi-directional while the 4 to 20 mA • HVAC
output can be set for uni- or bi-directional flow using the • Irrigation
display or the 3-0252 Configuration Tool which connects • Scrubber Control
to PCs for programming capabilities. • Neutralization Systems
• Industrial Water Distribution
In addition, the display version of the 2551 Magmeter
is available with relays and features permanent and
resettable totalizer values, which can be stored and seen
on the display. Also, the display contains multi-languages
with English, Spanish, German, French, Italian and
Portuguese menu options.

* U.S. Patent No: 7,055,396 B1

www.gfsignet.com
Specifications
General
Operating Range 0.05 to 10 m/s 0.15 to 33 ft/s
Pipe Size Range DN15 to DN900 ½ in. to 36 in.
Linearity ± 1% reading plus 0.1% of full scale
Repeatability ±0.5% of reading @ 25 °C (77 °F)
Minimum Conductivity 20 μS/cm
Wetted Materials
Sensor Body/Electrodes -P0, -P1, -P2: PP/316L SS
and Grounding Ring -T0, -T1, -T2: PVDF/Titanium
-V0, -V1, -V2: PVDF/Hastelloy-C
O-rings FKM (standard)
EPR (EPDM), FFKM (optional)
Case PBT
Display Window Polyamide (transparent nylon)
Protection Rating NEMA 4X/IP65
Electrical
Power Requirements 4 to 20 mA 24 VDC ±10%, regulated, 22.1 mA max.
Frequency 5 to 24 VDC ±10%, regulated, 15 mA max.
Digital (S3L) 5 to 6.5 VDC, 15 mA max.
Auxiliary (only required for units with relays) 9 to 24 VDC, 0.4 A max.
Reverse Polarity and Short Circuit Protected
Current Output 4 to 20 mA Loop Accuracy 32 μA max. error (25 °C @ 24 VDC)
Isolation Low voltage < 48 VAC/DC from electrodes and auxiliary power
Maximum Cable 300 m (1000 ft)
Error condition 22.1 mA
Max. Loop Resistance 300 Ω
Compatible with PLC, PC or similar equipment
4 to 20 mA load needed
Frequency Output Output Modes Freq., or Mirror Relay (display version only)
Max. Pull-up Voltage 30 VDC
Max. Current Sink 50 mA, current limited
Maximum Cable 300 m (1000 ft)
Compatible with Signet Model 8550, 8900, 9900, 9900-1BC, 9950
Digital (S3L) Output Serial ASCII, TTL level 9600 bps
Compatible with Model Signet 8900 controller, 9900, 9950, 0486 Profibus Concentrator
Relay Specifications
#1, #2 Type Mechanical SPDT
Rating 5 A @ 30 VDC max., 5 A @ 250 VDC max.
#3 Type Solid State
50 mA @ 30 VDC, 50 mA @ 42 VAC
Hysteresis User adjustable for exiting alarm condition
Alarm On Trigger Delay Adjustable (0 to 9999.9 sec.)
Relay Modes Off, Low, High, Window, and Proportional Pulse
Relay Source Flow Rate, Resettable Totalizer
Error Condition Selectable; Fail Open or Closed
Display
Characters 2 x 16
Contrast User-set in four levels
Backlighting (only on relay versions) Requires external 9-24 VDC, 0.4 mA max.
Max. Temperature/Pressure Rating
Storage Temperature -20 °C to 70 °C -4 °F to 158 °F
Relative Humidity 0 to 95% (non-condensing)
Operating Temperature Ambient -10 °C to 70 °C 14 °F to 158 °F
Media 0 °C to 85 °C 32 °F to 185 °F
Maximum Operating Pressure 10.3 bar @ 25 °C 150 psi @ 77 °F
1.4 bar @ 85 °C 20 psi @ 185 °F
Shipping Weight
0.680 kg 1.50 lb
Standards and Approvals
CE, FCC, UL, CUL, NSF (3-2551-PX-XX version only)
RoHS compliant, China RoHS
NEMA 4X / IP65 Enclosure (with cap installed)
Manufactured under ISO 9001 for Quality and ISO 14001 for Environmental Management and
OHSAS 18001 for Occupational Health and Safety
See Temperature and Pressure graphs for more information.

www.gfsignet.com
Dimensions
Blind version Display version
95.3 mm
(3.75 in.)
94 mm
(3.7 in.)

Pipe Range
1/2 to 4 in. -X0 = 58 mm (2.3 in.) 79.25 mm
(3.12 in.) 116.8 mm
5 to 8 in. -X1 = 91 mm (3.6 in.) (4.6 in.)
10 to 36 in. -X2 = 167 mm (6.6 in.)

-X0
X = Sensor Body P, T, or V -X0
-X1
-X1
-X2
-X2

Stand-Alone Panel Mount Pipe, Tank, Wall Mount 4 to 20 Output Automation System

Signet Signet Instruments Signet Instruments Customer Supplied Chart Recorder, 0486 Profibus Concentrator
Model 2551 8900 9900 9900 with 3-8050 Universal Mount Kit Programmable Logic Controller, or and Customer Supplied
Magmeter 9950 9900-1BC 9900-1P 9900-1BC with Rear Enclosure Programmable Automation Controller Programmable Logic Controller or
Programmable Automation Controller
System Overview

N/C

L OUT-

L OUT+

N/C

L IN-

L IN+

GND

DATA

+5V OUT

L IN-

L IN+

GND

DATA

+5V OUT

L IN-

L IN+
ENTER
OR + OR
OR
PLC
Address

Power
Profibus

24 VDC
0.40A Max
USB

S3L
Signet 3-0486 Profibus Concentrator

Channel 1
Freq
Out
Channel 7
Valve

Channel 2
S3 L
In

Freq
S3 L
Channel 6

Channel 3
S3L
Loop

Freq
S3L
Channel 5

Channel 4
S3L Freq
Loop

+ PLC

+5V OUT

+5V OUT

+5V OUT

+5V OUT
Freq IN

Freq IN

Freq IN

Freq IN
PWR+

PWR+

PWR+

PWR-

PWR-

PWR-

DATA

DATA

DATA

DATA
GND

GND

GND

GND
Signet 2551
Magmeter

Signet Fittings

All sold separately

Temperature/Pressure Graphs (psi) (bar)


180 12.4
170 11.7
160 11.0
Note:
150 10.3
The pressure/temperature graphs are specifically 140 9.7
for the Signet sensor. During system design the 130 9.0
specifications of all components must be considered. 120 8.3
In the case of a metal piping system, a plastic sensor 110 7.6

will reduce the system specification. When using a 100 6.9


90 6.2
PVDF sensor in a PVC piping system, the fitting will
80 5.5
reduce the system specification.
70 4.8
60 4.1
50 3.4
40 2.8
30 2.1
20 1.4
Application Tips 10 .7
• Note minimum process liquid conductivity 0
°C -20 0 20 40 60 80 100 120
requirement is 20 μs/cm
°F -4 32 68 104 140 176 212 248
• Install sensor using standard Signet installation
fittings for best results.
• Sensor is capable of retrofitting into existing 515
and 2536 fittings.

Please refer to Wiring, Installation, and Accessories sections for more information.
www.gfsignet.com
Ordering Information

Pipe Size Mfr. Part No. Code Sensor Body


Frequency or Digital (S3L) output
Programmable open collector for use with any Signet Flow Instrument or the 8900 or
9900 Instruments**
DN15 to DN100 (½ to 4 in.)
No Display
3-2551-P0-11 159 001 105 Polypropylene and 316L SS
3-2551-T0-11 159 001 108 PVDF and Titanium
3-2551-V0-11 159 001 257 PVDF and Hastelloy-C
with Display, two SPDT relays, one solid state relay
3-2551-P0-21 159 001 267 Polypropylene and 316L SS
3-2551-T0-21 159 001 436 PVDF and Titanium
3-2551-V0-21 159 001 269 PVDF and Hastelloy-C
with display
3-2551-P0-41 159 001 261 Polypropylene and 316L SS
3-2551-T0-41 159 001 433 PVDF and Titanium
3-2551-V0-41 159 001 263 PVDF and Hastelloy-C
DN125 to DN200 (5 to 8 in.)
No Display
3-2551-P1-11 159 001 106 Polypropylene and 316L SS
3-2551-T1-11 159 001 109 PVDF and Titanium
3-2551-V1-11 159 001 258 PVDF and Hastelloy-C
with Display, two SPDT relays, one solid state relay
3-2551-P1-21 159 001 268 Polypropylene and 316L SS
3-2551-T1-21 159 001 437 PVDF and Titanium
3-2551-V1-21 159 001 270 PVDF and Hastelloy-C
with Display
3-2551-P1-41 159 001 262 Polypropylene and 316L SS
3-2551-T1-41 159 001 434 PVDF and Titanium
3-2551-V1-41 159 001 264 PVDF and Hastelloy-C
DN250 to DN900 (10 to 36 in.)
No Display
3-2551-P2-11 159 001 107 Polypropylene and 316L SS
3-2551-T2-11 159 001 448 PVDF and Titanium
3-2551-V2-11 159 001 450 PVDF and Hastelloy-C
with Display, two SPDT relays, one solid state relay
3-2551-P2-21 159 001 435 Polypropylene and 316L SS
3-2551-T2-21 159 001 454 PVDF and Titanium
3-2551-V2-21 159 001 456 PVDF and Hastelloy-C
with Display
3-2551-P2-41 159 001 432 Polypropylene and 316L SS
3-2551-T2-41 159 001 460 PVDF and Titanium
3-2551-V2-41 159 001 462 PVDF and Hastelloy-C

**This option is a programmable open collector output that is available with display versions only.

www.gfsignet.com
Ordering Information (continued)

Pipe Size Mfr. Part No. Code Sensor Body

4 to 20 mA output for use with PLC, PC or similar equipment


DN15 to DN100 (½ to 4 in.)
No Display
3-2551-P0-12 159 001 110 Polypropylene and 316L SS
3-2551-T0-12 159 001 113 PVDF and Titanium
3-2551-V0-12 159 001 259 PVDF and Hastelloy-C
with Display, two SPDT relays, one solid state relay
3-2551-P0-22 159 001 273 Polypropylene and 316L SS
3-2551-T0-22 159 001 439 PVDF and Titanium
3-2551-V0-22 159 001 275 PVDF and Hastelloy-C
with Display
3-2551-P0-42 159 001 279 Polypropylene and 316L SS
3-2551-T0-42 159 001 442 PVDF and Titanium
3-2551-V0-42 159 001 281 PVDF and Hastelloy-C
DN125 to DN200 (5 to 8 in.)
No Display
3-2551-P1-12 159 001 111 Polypropylene and 316L SS
3-2551-T1-12 159 001 114 PVDF and Titanium
3-2551-V1-12 159 001 260 PVDF and Hastelloy-C
with Display, two SPDT relays, one solid state relay
3-2551-P1-22 159 001 274 Polypropylene and 316L SS
3-2551-T1-22 159 001 440 PVDF and Titanium
3-2551-V1-22 159 001 276 PVDF and Hastelloy-C
with Display
3-2551-P1-42 159 001 280 Polypropylene and 316L SS
3-2551-T1-42 159 001 443 PVDF and Titanium
3-2551-V1-42 159 001 282 PVDF and Hastelloy-C
DN250 to DN900 (10 to 36 in.)
No Display
3-2551-P2-12 159 001 112 Polypropylene and 316L SS
3-2551-T2-12 159 001 449 PVDF and Titanium
3-2551-V2-12 159 001 451 PVDF and Hastelloy-C
with Display, two SPDT relays, one solid state relay
3-2551-P2-22 159 001 438 Polypropylene and 316L SS
3-2551-T2-22 159 001 455 PVDF and Titanium
3-2551-V2-22 159 001 457 PVDF and Hastelloy-C
with Display
3-2551-P2-42 159 001 441 Polypropylene and 316L SS
3-2551-T2-42 159 001 461 PVDF and Titanium
3-2551-V2-42 159 001 463 PVDF and Hastelloy-C

www.gfsignet.com
Accessories and Replacement Parts

Mfr. Part No. Code Description

O-rings
1220-0021 198 801 000 O-ring, FKM (2 required per sensor)
1224-0021 198 820 006 O-ring, EPR (EPDM) (2 required per sensor)
1228-0021 198 820 007 O-ring, FFKM (2 required per sensor)
Replacement Transducers
3-2551-P0 159 001 211 PP/316L SS, DN15 to DN100 (½ to 4 in.) pipe
3-2551-P1 159 001 212 PP/316L SS, DN125 to DN200 (5 to 8 in.) pipe
3-2551-P2 159 001 444 PP/316L SS, DN250 to DN900 (10 to 36 in.) pipe
3-2551-T0 159 001 213 PVDF/Titanium, DN15 to DN100 (½ to 4 in.) pipe
3-2551-T1 159 001 214 PVDF/Titanium, DN125 to DN200 (5 to 8 in.) pipe
3-2551-T2 159 001 445 PVDF/Titanium, DN250 to DN900 (10 to 36 in.) pipe
3-2551-V0 159 001 376 PVDF/Hastelloy-C, DN15 to DN100 (½ to 4 in.) pipe
3-2551-V1 159 001 377 PVDF/Hastelloy-C, DN125 to DN200 (5 to 8 in.) pipe
3-2551-V2 159 001 446 PVDF/Hastelloy-C, DN250 to DN900 (10 to 36 in.) pipe
Replacement Electronics Module
3-2551-11 159 001 215 Magmeter electronics, frequency or digital (S3L) output
3-2551-12 159 001 216 Magmeter electronics, 4 to 20 mA output
3-2551-21 159 001 372 Magmeter display electronics, frequency or digital (S3L) output, with relays
3-2551-22 159 001 373 Magmeter display electronics, 4 to 20 mA output w/relays
3-2551-41 159 001 374 Magmeter display electronics, frequency or digital (S3L) output
3-2551-42 159 001 375 Magmeter display electronics, 4 to 20 mA output
Other
P31536 198 840 201 Sensor plug, Polypropylene
7310-1024 159 873 004 24 VDC Power Supply, 10W, 0.42 A
7310-2024 159 873 005 24 VDC Power Supply, 24W, 1.0 A
7310-4024 159 873 006 24 VDC Power Supply, 40W, 1.7 A
7310-6024 159 873 007 24 VDC Power Supply, 60W, 2.5 A
7310-7024 159 873 008 24 VDC Power Supply, 96W, 4.0 A
3-8050.390-1 159 001 702 Retaining nut replacement kit, NPT, Valox
3-8050.390-3 159 310 116 Retaining nut replacement kit, NPT, PP
3-8050.390-4 159 310 117 Retaining nut replacement kit, NPT, PVDF
3-8551.521 159 001 378 Clear plastic cap for display
1222-0042 159 001 379 O-ring for clear plastic cap, EPR (EPDM)
3-0252 159 001 808 Configuration Tool (Blind version only)
3-9900.392-1 159 000 839 Liquid tight connector kit, NPT (1 pc.)
3-8050.396 159 000 617 RC filter kit (for relay use), 2 per kit

3-2551.099 Rev K (06/18)


© Georg Fischer Signet LLC
3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057 • www.gfsignet.com • e-mail: signet.ps@georgfischer.com
Specifications subject to change without notice. All rights reserved. All corporate names and trademarks stated herein are the property of their respective companies.

www.gfsignet.com