Structural Peer Review: General Information

The document outlines the requirements for structural peer review of buildings in the City of Miami. Structural peer review is required for buildings over 60 feet tall, over 250,000 square feet, in Structural Occupancy Category IV, or if requested by the Building Official. An independent licensed engineer selected by the owner conducts the review to verify the structural design complies with building codes. The reviewing engineer submits a report confirming code compliance. The structural engineer of record remains solely responsible for the design.

Uploaded by

Tan Ching
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
232 views2 pages

Structural Peer Review: General Information

The document outlines the requirements for structural peer review of buildings in the City of Miami. Structural peer review is required for buildings over 60 feet tall, over 250,000 square feet, in Structural Occupancy Category IV, or if requested by the Building Official. An independent licensed engineer selected by the owner conducts the review to verify the structural design complies with building codes. The reviewing engineer submits a report confirming code compliance. The structural engineer of record remains solely responsible for the design.

Uploaded by

Tan Ching
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

STRUCTURAL PEER REVIEW

General Information Rev. 02-20-2018

Structural Peer Review:


The purpose of the Structural Peer Review is to provide independent verification that the
structural design of the Structure* is in general conformance with the requirements of the Florida
Building Code, and all related structural codes and technical standards.
*STRUCTURE: The structural frame and the load supporting parts of floors, roofs, walls,
foundations, cladding, cladding framing, stairs, equipment supports, railings and other
secondary structural items are included in this definition of “Structure”.

Structural Peer Review is required for:


1) Buildings included in Structural Occupancy Category IV as defined in the Florida Building Code.
2) Buildings greater than 60 feet in height (measured from grade level to the average height of the highest
roof surface), or more than 250,000 square feet in gross floor area.
3) Buildings where a Structural Peer Review is specifically requested by the Building Official.

Selection of the Reviewing Engineer:


The Structural Peer Review shall be performed by a qualified independent structural engineer who
has been retained by, or on behalf of, the Owner of the property. This Reviewing Engineer shall
meet specific qualification requirements, including demonstrable experience in the structural
design and/or peer review of structures similar in scope and complexity. The Owner of the
property shall submit to the Building Official the names of up to three (3) Florida-licensed
engineers specializing in structural design.

The final selection will be made by mutual consent; after which, a meeting between the Building
Official and the Engineer must be scheduled prior to commencement of the Structural Peer
Review.

Extent of the Structural Peer Review:


Scope: The Reviewing Engineer shall review the plans and specifications submitted with the
original permit application, and all subsequent revisions thereto. Said review shall be for
compliance with the structural and foundation design provisions of the Florida Building Code and
all related structural codes and technical standards. The Reviewing Engineer shall perform the
following tasks, as a minimum:

1) Confirm that the design loads conform to the applicable codes.


2) Confirm that other structural design criteria and design assumptions conform to the applicable codes
and are in accordance with generally accepted engineering practice.
3) Review geotechnical and other engineering investigations that are related to the foundation and
structural design and confirm that the design properly incorporates the results and recommendations
of the investigations.
4) Confirm that the structure has a complete load path.
5) Perform independent calculations for a representative fraction of the systems, members and details to
check their adequacy. The number of representative systems, members and details verified shall be
sufficient to form a basis for the reviewer’s conclusions.
6) Confirm that the structural integrity provisions of the applicable codes are being followed.
7) Verify that performance-specified structural components (such as certain precast concrete elements)
have been appropriately specified and coordinated with the Primary Building Structure.

Page 1 of 2
8) Review the structural and architectural plans for the building. Confirm that the structural plans are in
general conformance with the architectural plans regarding loads and other conditions that may affect
the structural design.
9) Confirm that major mechanical items are accommodated in the structural plans.
10) Confirm that all items defined in Structure are in accordance with the Florida Building Code.
11) Attest to the general completeness of the structural plans and specifications.
Structural Calculations: The structural calculations prepared by the structural engineer of record
shall be submitted to the Reviewing Engineer, upon his/her request, for reference only. The
Reviewing Engineer shall not be obliged to review or check these calculations. If the design criteria
and design assumptions are not shown on the drawings or in the computations, the structural
engineer of record shall provide a statement of these criteria and assumptions for the reviewer.

Structural Peer Review Report, and Plans Processing:


General. The Reviewing Engineer shall submit a report to the department stating whether or not
the structural design shown on the plans and specifications generally conforms to the structural
and foundation requirements of the Florida Building Code.
Contents. The report shall demonstrate, at a minimum, compliance with items 1 through 11 of
“Extent of the Structural Peer Review” above. Additionally, the report shall also include:

1) The codes and standards used in the structural design of the project.
2) The structural design criteria, including loads and performance requirements.
3) The basis for design criteria that are not specified directly in applicable codes and standards. This
should include reports by specialty consultants such as wind tunnel study reports and geotechnical
reports. Generally, the report should confirm that existing conditions at the site have been investigated
as appropriate and that the design of the proposed structure is in general conformance with these
conditions.

Phased submission. If an application is submitted for a permit for the construction of foundations
or any other part of a building before the construction documents for the whole building have
been submitted, then the Structural Peer Review and report shall be phased. The Reviewing
Engineer shall be provided with sufficient information upon which to perform a Structural Peer
Review for the phased submission.

Approval Stamps: Upon the approval of the plans, the reviewing engineer shall sign, date and
stamp each drawing page with the language “PEER REVIEWED in accordance with City of Miami
requirements for Structural Peer Review, and verified for Code Compliance”.

Responsibility:
Structural Engineer of Record. The Structural Engineer of Record shall retain sole responsibility for
the structural design. The activities and reports of the Reviewing Engineer shall not relieve the
Structural Engineer of Record of this responsibility.
Reviewing Engineer. The Reviewing Engineer’s report states his or her opinion regarding the
design by the engineer of record. The standard of care to which the Reviewing Engineer shall be
held in the performance of the Structural Peer Review and report is that the level of skill and care
are consistent with Structural Peer Review services performed by professional engineers licensed
in the State of Florida for similar types of projects.