Open and Short Circuit Switches Fault Detection of Voltage Source Inverter Using Spectrogram
Open and Short Circuit Switches Fault Detection of Voltage Source Inverter Using Spectrogram
net/publication/273635142
Open and Short Circuit Switches Fault Detection of Voltage Source Inverter
Using Spectrogram
CITATIONS READS
4 513
3 authors:
16 PUBLICATIONS 120 CITATIONS
Technical University of Malaysia Malacca
155 PUBLICATIONS 555 CITATIONS
SEE PROFILE
SEE PROFILE
Norhazilina Bahari
Technical University of Malaysia Malacca
18 PUBLICATIONS 65 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
PROTON EXCHANGE MEMBRANE FUEL CELL (PEMFC) PARAMETERS ESTIMATION USING TIME-FREQUENCY ANALYSIS TECHNIQUE View project
All content following this page was uploaded by Abdul Rahim Abdullah on 17 March 2015.
Abstract –In the last years, fault problem in power electronics has been more and more
investigated both from theoretical and practical point of view. The fault problem can cause
equipment failure, data and economical losses. And the analyze system require to ensure fault
problem and also rectify failures. The current errors on these faults are applied for identified type
of faults. This paper presents technique to detection and identification faults in three-phase voltage
source inverter (VSI) by using time-frequency distribution (TFD). TFD capable represent time
frequency representation (TFR) in temporal and spectral information. Based on TFR, signal
parameters are calculated such as instantaneous average current, instantaneous root mean square
current, instantaneous fundamental root mean square current and, instantaneous total current
waveform distortion. From on results, the detection of VSI faults could be determined based on
characteristic of parameter estimation. And also concluded that the fault detection is capable of
identifying the type of inverter fault and can reduce cost maintenance.
representation (TFR). Based on TFR, parameters of VSI Commonly, intersective method is simplest way to
current signal are estimated and used to identify open and generate a PWM signal, which requires a triangle waveform
short circuit switches fault based on current pattern then and a comparator. When the value of the references signal
characteristic of VSI are calculated. is more than the modulation waveform, the PWM signal is
in the high state, otherwise it is in low state. Besides that,
2. Voltage Source Inverter System the module of fault generation that used for give pulse at
switching gate signal means give disturbance at gate signal
Voltage source inverter (VSI) is an electronic device
which concern direct current (DC) to Alternating current The switches fault VSI for open circuit fault condition,
(AC). VSI has advantages like higher efficiencies, IGBT falls in the off state and remains in this situation
minimizing installation timing, elimination interconnect regardless of the gate voltage value. Open circuit fault
power cabling costs and reducing building floor space. generally do not cause system shutdown, but degrade its
Fig.1 (a) shows the diagram of general system for this performance. Fig. 2 show the model of circuit when VSI
research and Fig.1 (b) shows the modeling of three-phase switches open circuit fault.
VSI with the fault generation. In the model S11 to S32 are
Insulated Gate Bipolar Transistors (IGBTs) which can be on
or off pulse width modulation (PWM) is a common IM
technique for controlling the switches.
Inverter Motor
Load
Collect
Data Fig. 2. The model of Voltage Source Inverter when
Switches Open Circuit Fault
IM IM
component of the phase leg. The switching status represent Fourier Transform (STFT) and can be expressed as below.
in term of “1” when the switch is closed and “0’ when open. Where h(t ) is the input signal while w(t) is the window
The cause of fault in VSI for this paper depends on pulse function. This technique depends on window size since it
width modulation (PWM). Such the fault is open circuit results better time resolution and lower frequency
fault upper, open circuit fault lower, short circuit fault upper resolution by using smaller window size and vice versa[12,
and short circuit fault lower [9-11]. 13, 15, 16].
2
h( )w( t )e
j 2 f
Sjp
1
S x (t , f ) d (1)
1 4. Parameter Estimation
Sjn
Parameters of the faults signal are estimated from the
Fig. 4. Gating signals of the inverter in an ideal case TFR to identify the characteristics of VSI faults.
The gate switching fault is one of cause open circuit and 4.1 Instantaneous Average Current
short circuit VSI. Based on Fig.5 and 6, gate pulse
switching is one of causes fault VSI. Open circuit fault 1
T
T 0
causes by gate pulse switching “0” then short circuit fault I I rms (t )dt (2)
rms, ave
causes by gate pulse switching “1”.
Sjp
4.2 Instantaneous Root Mean Square [17]
The equation below from, Sx(t,f) is the distribution and
1
Sjn fmax is the maximum frequency of interest.
f max
Fig. 5. Gating signals of the inverter in an open-circuit
fault Irms t S x (t , f )df (3)
0
1
Sjp
0
4.3 Instantaneous RMS Fundamental Current
1
Sjn The instantaneous RMS fundamental current is as the RMS
0
current at power system frequency [12, 15, 18] can be
Fig. 6. Gating signals of the inverter in short-circuit
calculated as
fault
f hi
3. Result Time-Frequency Distribution
I1rms (t ) 2 S x (t , f )df
flo (4)
Spectrogram is one of the time-frequency
representations (TFR) that represents a three-dimensional f f
f hi f1 , f lo f1
of the signal energy with respect to time and frequency. 2 2
Time-frequency representations are used to analyze or
characterize signals whose energy distribution varies in
time and frequency. They map the one-dimensional time- 4.4 Instantaneous Total Waveform Distortion
domain signal into a two-dimensional function of time and
frequency [12-14]. A time-frequency representation The total waveform distortion consists of harmonic and
presents the variation of spectral energy over time [8-10]. In non-harmonic distortion. The TWD can be defined
this paper, time-frequency analysis technique which is
spectrogram is used to analyze the faults signal. Vrms (t )2 V1rms (t )2
Spectrogram is the squared magnitude of the Short Time
TWD(t) (5)
V1rms (t )
N. S. Ahmad , A. R. Abdullah and N. Bahari 193
Phase A
2
1
multiples of the fundamental frequency [1212, 14, 19]. For 0
Current, A
-1
example, the fundamental frequency given 60 Hz, the -2
Phase B
3
-3
interharmonic will be 70 Hz, 85 Hz. 20 0.1 0.2 0.3 0.4 0.5 0.6
1
0
-1
-2
-3
3
0 0.1 0.2 0.3 0.4 0.5 0.6
Phase C
2
V (t )rms h 0 Vh,rms (t )
2 H 2 1
0
TnHD(t) (7) -1
-2
V1rms (t ) -3
0 0.1 0.2 0.3 0.4 0.5 0.6
Time (s)
(a)
5. Results
Frequency, %
Instantaneous Average Current, Iave(t) 5.2 Open Circuit Switches Fault in VSI (Lower Fault)
1
Fig. 9(a) shows the three-phase VSI for fault at lower
0.5 switches. We can see, observation from the open-circuit
Current, A
Amplitude
Phase B & C
fault lower signal where current phase A higher than phase
0
B and C. The current phase A increase starting from 0.2 –
-0.5 Phase A 0.3 s but phase B and C respectively.
Open-Circuit Faults of the Lower Switch Signal
-1 3
Phase A
0 0.1 0.2 0.3 0.4 0.5 0.6 2
Time (sec)
Time (s)
1
0
-1
(a) -2
-3
30 0.1 0.2 0.3 0.4 0.5 0.6
Current, A
Phase B
2
Instantaneous RMS Current, Irms(t) 1
1.1 0
-1
-2
1.05 Phase C -3
3
Phase C
Current, A
Phase B -2
0.95 -3
0 0.1 0.2 0.3 0.4 0.5 0.6
1 0 Hz 60 Hz
0.9
Phase B
0.8 Phase A
0.7
0 0.1 0.2 0.3 0.4 0.5 0.6
Time (s)
Time (s) (b)
(c)
Instantaneous Total Waveform Distortion, TWD(t) Fig. 9. (a) Signal of Open-Circuit Fault Lower
1.5 (b) Spectrogram Open-Circuit Fault Lower
Percentage, %
Instantaneous Average Current, Iave(t) 5.3 Short Circuit Switches Fault in VSI (Upper Fault)
1
Fig. 11(a) shows signal short circuit switches fault
Phase A where three-phase current indicate the fault also occur at
Current, A
0.5
Amplitude
1.1 2
Current, A
Phase A
0
-1
1.05 Phase C -2
3
-3
0 0.1 0.2 0.3 0.4 0.5 0.6
Current, A
2
1 1
Phase B
0
0.95 Phase A Phase B -1
-2
0.9 -3
3
0 0.1 0.2 0.3 0.4 0.5 0.6
0 0.1 0.2 0.3 0.4 0.5 0.6 2
1
Phase C
Time (s) 0
-1
(b) -2
-3
Instantaneous RMS Fundamental Current, Irms(t) 0 0.1 0.2 0.3 0.4 0.5 0.6
1.1
Time (s)
Current, A
Phase C (a)
1
Time Frequency Representation
0.9 Phase B
0.8 Phase A
Frequency, Hz
0.7
0 0.1 0.2 0.3 0.4 0.5 0.6
Time (s)
0 Hz 60 Hz
(c)
Instantaneous Total Waveform Distortion, TWD(t)
3
Percentage, %
Instantaneous Average Current, Iave(t) 5.4 Short Circuit Switches Fault in VSI (Lower Fault)
1
Fig. 13(a) shows the signal short-circuit faults of the
Phase A lower switch where switch at phase A fault at 0.2-0.3s. The
Current, A
0.5
Current(A)
Phase A
2
1
1.6 0
-1
Current, A
-2
Amplitude(pu)
Current, A
1.4 Phase A 3
-3
0 0.1 0.2 0.3 0.4 0.5 0.6
Phase B
2
1
0
1.2 Phase B -1
Phase C -2
3
-3
0 0.1 0.2 0.3 0.4 0.5 0.6
2
1
Phase C
1
0
-1
-2
0.8 -3
0 0.1 0.2 0.3 0.4 0.5 0.6 0 0.1 0.2 0.3 0.4 0.5 0.6
1.1
Current, A
Frequency, Hz
1
Phase B & C
0.9 Phase A
0 Hz 60 Hz
0.8
0 0.1 0.2 0.3 0.4 0.5 0.6
Time (s)
(c)
Instantaneous Total Waveform Distortion, TWD(t)
1.5
Time (s)
Percentages, %
(b)
Phase A
1
Fig.13. (a) Signal of Short-Circuit Fault Lower (b)
Phase B Phase C Spectrogram Short-Circuit Fault Lower
0.5
The parameter that estimated from TFR with the
0 instantaneous average current for phase A is lower than
0 0.1 0.2 0.3 0.4 0.5 0.6
Time (s) phase B and C as shows Fig. 14(a). But for the RMS
(d) current value, phase A is higher while phase B and C is
Fig.12. Parameter Estimation for short-circuit fault lower, respectively as Fig. 14(b). For the instantaneous
Upper RMS fundamental current on Fig. 14(c), phase A is lower
(a) Instantaneous Average Current, Iave(t) than phase B and C. Besides that, instantaneous waveform
(b) Instantaneous RMS Current, Irms(t)
distortion as shows in Fig. 10(d), where faults signal occur
(c) Instantaneous RMS Fundamental Current,
Irms(t) at DC component, there TWD gives 1.42 percent but phase
(d) Instantaneous Total Waveform Distortion, B and C is below then 1 percent.
TWD(t)
N. S. Ahmad , A. R. Abdullah and N. Bahari 197
Phase C
Current(A)
1.4
Phase A Analysis results were made based on current parameter
1.2 estimation from spectrogram. Table 1 shows general of
Phase C
Phase B current error during fault detected. Next, Table 2 shows
1 overall observation of current error from parameter
estimation. From the observation of average current, that
0.8
0 0.1 0.2 0.3 0.4 0.5 0.6 found the value of IB is equal IC but less than 0.5 and other
Time (s) of current is IB equal with IC. Both of current is greater than
(b)
Instantaneous RMS Fundamental Current, Irms(t) 0.5 and less than zero. Next, the open-circuit lower can be
1.2 detect with IA below than 1, respectively is greater than
zero. For this condition IA is greater than 1 but IA less than
1.1 zero. higher than zero for open circuit fault upper. Besides
Current, A
Table 2. Characteristic for each fault detection estimation. So, the detection faults can be early and
based on parameter estimation fault in VSI will be decrease.
Parameter Type of fault Observation
Average Open Upper ( IB = IC) < 0.5
Current Others ( IB = IC) > 0.5
( IB = IC) < 0 Acknowledgment
Open Lower IA< 1 but IA >0
Others IA> 1 & IA< 0
Short Upper IA >1
Faculty of Electrical Engineering, Universiti Teknikal
Others IA< 1 Malaysia Melaka
Short Lower IA < -1
Others IA > -1
RMS Open ( IA = IC)
References
Current Other ( IA = IC)
Short Upper ( IB > IC) [1] Trabelsi, M., et al. An improved diagnosis technique
Other ( IB = IC) for IGBTs open-circuit fault in PWM-VSI-fed
Short Lower ( IC >IB)
Other ( IC =IB) induction motor drive. in Industrial Electronics (ISIE),
RMS Open IA > ( IB = IC) 2011 IEEE International Symposium on. 2011.
Current
Short IA > IC > IB [2] Bin, L. and S. Sharma. A Literature Review of IGBT
Fault Diagnostic and Protection Methods for Power
Inverters. in Industry Applications Society Annual
Meeting, 2008. IAS '08. IEEE. 2008.
[3] Fuchs, F.W. Some diagnosis methods for voltage
6. Conclusion source inverters in variable speed drives with induction
machines - a survey. in Industrial Electronics Society,
The analysis and detection system of type VSI faults is 2003. IECON '03. The 29th Annual Conference of the
presented using TFD. From the parameter calculation, IEEE. 2003.
the TFR is estimated to identify fault signal parameter [4] Bojoi, R., M.G. Neacsu, and A. Tenconi. Analysis and
and then, from the parameters, fault signal survey of multi-phase power electronic converter
characteristic can be calculated. Next, the characteristic topologies for the more electric aircraft applications. in
for each fault detection can be identifying based on Power Electronics, Electrical Drives, Automation and
current error. The performance of the faults system is Motion (SPEEDAM), 2012 International Symposium
verified by the value current error which is average on. 2012.
[5] B. Raison, G.R.a.J.P.R., Towards a Global Monitoring
current and fundamental current. It shows the VSI
Scheme for Induction Motor Drives. Proc. Int. Power
faults can be identified depends on value parameter
Electron. Conf.2000, 2000: p. pp. 1183-1188.
N. S. Ahmad , A. R. Abdullah and N. Bahari 199