Electric Service and Meter Installations
Electric Service and Meter Installations
Installations Manual
General ........................................................................................................................... 5
Availability and Classification of Service ......................................................................... 6
Line Extensions ............................................................................................................... 6
Temporary Service/Saw Service ..................................................................................... 7
Manufactured (Mobile Home) Service ............................................................................. 9
Number of Services and Meters ...................................................................................... 9
Application for Service................................................................................................... 10
Alterations and Additions............................................................................................... 10
Use of Service by Customer.......................................................................................... 10
Interruption of Service and Liability ............................................................................... 11
Grounding ..................................................................................................................... 11
Final Connections ......................................................................................................... 12
Inspections .................................................................................................................... 12
Meter Tampering, Seals and Fraudulent Use................................................................ 13
General ......................................................................................................................... 15
Service Conductors – Attachment Point ........................................................................ 15
Service Entrance General ............................................................................................. 15
Service Entrance Conductors........................................................................................ 16
General ......................................................................................................................... 19
Service Entrance Conductors........................................................................................ 19
Underground Service in Overhead Districts .................................................................. 20
Underground Services from Underground Distribution.................................................. 21
Underground Services in Underground Network Area .................................................. 21
Location......................................................................................................................... 32
Interrupting Capacity of Protection Devices .................................................................. 32
Single Phase Service Equipment .................................................................................. 32
Three Phase Service Equipment................................................................................... 33
You can reach our 24-hour Customer Service Center toll-free at 1-800-251-7234.
Definitions
1. "Application for Service" - a mail, phone or personal request by the customer to the
Company stating desire for electric service to be furnished at a certain location.
2. "Building" - a structure which stands alone or which is cut off from adjoining structures
by firewalls, as defined by the pertinent building codes, with all openings therein
protected by approved fire doors.
4. "Code" - the National Electrical Code (NEC) and the National Electrical Safety Code
or other electrical codes or regulations in effect in the area served.
5. "Company, our, we, us" - Dominion Energy South Carolina, Inc. (“Dominion Energy
South Carolina") (“DESC”).
6. "Cost" or "expense" - shall include all labor, material and other applicable charges,
plus overheads.
9. "Customer will provide" or "will install" or "will have installed" or "will furnish" and
similar references - the Company expects the customer to provide and install the
equipment in question. It is assumed that the customer will delegate this obligation to
10. "Developer" - the party entering into the agreement with the Company.
11. "Distribution Lines" - company lines located in or along streets, alleys, highways,
rear lot lines or elsewhere, and by easements, when used or intended for use for
general distribution of electric service to customers.
12. "Electrical installation" - the total electrical wiring and equipment installed on the
customer's premises.
13. "Firewall" - a four-hour fire-resistant wall having protected openings, which restrict the
spread of fire, and extend continuously from the foundation to three feet above the
roof unless the roof is of non-combustible material for the area within forty feet (40')
each side of the wall. In this case, the firewall need not extend above the roof.
14. "Fraudulent Use" - obtaining electric and/or gas service by unlawful means.
16. "Instrument Transformer" - transformers used for reducing the current or voltage to
quantities suitable for metering. There are indoor and outdoor types. Indoor types
must be installed in cabinets whether installed indoors or outdoors. Outdoors types
are usually installed without cabinets but may sometimes be put in cabinets.
17. "Instrument Transformer Cabinet" - a sealable metal box for housing instrument
transformers, i.e., CT enclosure.
18. "Line" - a system of poles, wires, and fixtures, or the equivalent ducts, conduits,
cables, etc. used for the distribution of electricity. It may be located in a street,
highway, alley, or on a private right-of- way.
19. "Line Extension" - any addition to the Company's existing distribution lines and
facilities which must be made to render electric service to a customer.
20. "Manufactured Home" - formerly known as a mobile home which has been
21. "Meter" - a device for measuring the electric power and energy supplied to a customer.
22. "Meter Enclosure" - a wood or metal cabinet, or metal socket, installed indoors or
outdoors, in which the Company's metering equipment is located.
23. "Meter Sockets" - a meter socket is the base portion of a socket type meter. There
are numerous kinds of meter sockets such as light duty, heavy duty, multi-terminal,
etc. all with various numbers and sizes of conduit openings. Each particular socket
has a preferred application although some are interchangeable.
24. "Meter Tampering" - any attempt to alter the registration of use on an electric or gas
meter.
26. "Modular Home" - any building including the necessary electrical, plumbing, heating,
ventilating and other service systems manufactured off site and transported to the
point of use for installation or erection with or without other specified components, as
a finished building and not designed for ready removal to another site. This must
qualify under the S.C. Modular Building Construction Act, Regulation #19-460.15. Any
home considered being a modular home will have a certification label. This label
verifies it is a modular home and must be shown to the service representative before
any electrical connection is made.
27. "Overhead Distribution Areas" - those areas in which the customer's premises abut
on company overhead distribution facilities.
28. "Point of Attachment" - the first point of contact on the customer's building or
structure at which the service drop is attached.
29. "Rate Schedule Classification" - the classification of the customer's electric service
for rate application as determined by the class of service, the amount of electric power
supplied and the purpose for which the electric service is to be used.
30. "Service" - the conductors and equipment for delivering energy from the Company's
line to the wiring system of the premises served.
C. "Service entrance" - that part of the wiring from the point of attachment or
termination of the service drop or service lateral to and including the service
equipment on the customer's premises.
31. "Service connection" - one service drop or service lateral and its associated service
entrance.
32. "Service entrance conductors" - the supply conductors, which extend from the point
of attachment or termination of the service drop or service lateral to the service
equipment on the premises being served.
33. "Service Entrance Equipment" - the service entrance conductors, raceway and
fittings or service entrance cable and fittings which are installed on the customer's
premises to connect the electric service to the wiring inside the building.
34. "Service Raceway" - the conduit containing the service entrance conductors.
36. "Temporary or seasonal service" - may be furnished under the appropriate General
Service Rate Schedule to any Customer. Temporary service shall include all
construction services and other services having a life expectancy of one year or less.
Payment is required in advance for the full cost of erecting and removing all lines,
transformers, and other service facilities necessary for the supply of such service.
202. This booklet is issued as a convenient general reference for customers, architects,
engineers and contractors planning or constructing buildings or installing, repairing
or renewing apparatus or equipment to be connected to the Company's distribution
system.
203. These practices are subject to additions and changes at any time as developments
and progress in the electrical industry may require. A copy of subsequent
approved changes will be furnished each holder of this manual upon request.
204. The information herein is supplementary to the National Electrical Code and the
National Electrical Safety Code, as approved by the American National Standards
Institute, and such state and municipal laws and ordinances as may be in force
within cities, towns or communities in which the Company furnishes electric
service. Should a conflict exist, the authority having jurisdiction will govern.
205. The Company is desirous of serving its customers promptly and satisfactorily. It
will endeavor to cooperate with contractors and customers to the fullest extent in
completing service connections with as little delay and inconvenience as possible
and will gladly give special attention to any particularly difficult situation confronting
a customer.
206. The Company will be willing to confer, upon request, with those desiring
information concerning rates, services, etc.
207. It is realized that the same or similar statements are repeated at various places in
this booklet, but is intentional for emphasis and also because reference may be
made to only a certain section for specific information and thus important factors
may be overlooked if they are not repeated.
208. The Company's nominal secondary service voltages are 120 volts single phase,
120/240 volts, 3 wire single phase, 240 volts 3 phase 3 wire, 120/240 3 phase 4
wire, 120/208 3 phase 4 wire, 277/480 volts 3 phase 4 wire. Service voltages
higher than 480 volts are available only by negotiation with the company. The size
and type of the customer’s load must warrant such an installation. It is unusual for
the Company to have more than one of these voltages available at any one
location, and it must not be assumed that any particular voltage is available at any
particular location. All of the above voltages are supplied at approximately 60
hertz. The customer must ascertain from the Company with absolute certainty,
well in advance of the date actual service connection is required, whether or not
the type of service required is available in the particular locality in question. If
required service is available, its exact character must be determined; that is, the
voltage, phase, etc. THESE CHARACTERISTICS MAY VARY IN DIFFERENT
LOCALITIES. The Company will supply this information, and it is advisable to
obtain it in writing so as to avoid possible misunderstandings. Do not rely on the
representations of unauthorized parties. It is desirable to know the names of the
Company representatives you deal with.
209. The information contained in this booklet refers primarily to service requirements
at the usual secondary distribution voltages for light and power installations.
Service requirements for installations requiring higher voltages are subject to
special negotiation between the customer and the Company.
210. The Company will, if requested, advise and assist its present or prospective
customers relative to problems associated with electrical equipment and facilities
and particularly in the application of motors to the loads that are to be served.
Line Extensions
211. In order to avoid delay, persons desiring service are advised to inquire of the
Company as to what type service may be provided, and to make necessary
arrangements prior to beginning wiring installation.
212. Developers of subdivisions or other real estate projects are urged to consult with
the Company as soon as preliminary plans are made, in order that the electric line
extensions may be developed for the best possible arrangement, and right-of-way
obtained before any lots are sold. The company can often suggest minor changes
in lot lines so that poles, guy wires, pad-mount transformers, switchgear, etc. might
213. When temporary service is desired, the prospective customer will make
arrangements for it directly with the Company at his local office, well in advance of
the required service date. Prospective customers will contact the Company to have
the service location spotted before construction is started. The Company reserves
the right to refuse to connect a service without modification if a spot has not been
requested.
214. Temporary installations requiring special service, meter or other work for
construction purposes, exhibits of short duration etc., are made at the expense of
the customer, with charges according to the material and work required for
installing and removing. In all such cases, an advance payment sufficient to cover
the estimated construction expense and energy used may be required. In those
areas where Underground Distribution is to be established, special conditions
relative to the establishment of temporary service will arise and must be worked
out with the Customer Service Engineering Department or District Manager of the
Company.
215. These services are usually overhead for construction purposes. They must be
given special consideration since they are not of a permanent nature. In residential
or commercial areas where underground distribution exists or is planned, special
construction techniques are required. The following are the general steps to be
taken by the customer in acquiring temporary or saw service.
STEP 2 - The customer shall make application for service at the Company's
In cases where the Company's facilities are not within 125 feet or
applicant is unable to determine whether or not the Company's
facilities are suitable, then he should call the Company's office and
request that an investigation be made as to the availability of
temporary service. The investigator will advise the applicant if the
service is readily available and where to install the "Temporary
Service Assembly". In the event that the service is not readily
available, a longer time may be required in order to make the
necessary line extensions. Once the customer has satisfied the
requirements of Step 1, he should proceed with Step 2.
Step 3 - The Company's service crews will come to the job site and make the
connections if the "Assembly" is properly located and erected. If the
"Assembly" is improperly installed, the applicant will be notified what
corrections are necessary, and Step 4 will then become applicable.
Step 4 - Applicant shall have the necessary corrections made then notify the
Company's nearest Customer Service office that the "Temporary
Assembly" is ready for the establishment of service. An additional
connection charge for the service crew's second call will be made.
This step, including the additional connection charge, will be repeated
for each trip the service crew makes and is unable to complete the
connection if due to improper location or installation of the "Temporary
Service Assembly".
216. The customer must provide a suitable support for the service drop wires, meter
and weatherproof housing for the service equipment. Service entrance wiring and
equipment will be supplied and installed by the customer and at the location
designated by the Company's representative. The temporary installation must
meet the above criteria and be able to support the weight of a ladder with a person
on it.
217. Owners of permanent or transient parking facilities should consult with the
Customer Service Engineering Department or District Manager of the Company to
find out how service will be provided. All installations shall be in accordance with
the latest approved National Electrical Code, Article 550, and latest Company
requirements. An electric meter can be attached to a manufactured (mobile) home
if the conditions below are met:
Company has the right to reject any service found to be unsafe. Services could
be declared unsafe due to electrical or structural issues. Structural issues occur
most often on overhead installations – the installation not providing adequate
support for the tension of the service conductors. The customer assumes all
responsibility for damages resulting from attachment of service to a manufactured
(mobile) home. Customer will be responsible for cost of lift pole if required to
reduce tension of service conductor.
218. The Company will install only one set of service conductors (one voltage) to a
building or structure. If one customer occupies the building, only one watt-hour
meter will be installed. If occupied by several different families or businesses each
one will become a customer of the Company, and a meter for his service must be
installed.
220. The Company will receive application in person or by telephone for original or
additional service at any local office. Full information concerning such application
will be furnished. A security deposit may be required.
222. It is necessary that applications show street numbers, lot and block number or
other means of locating the customer's premises and a corresponding
identification system be visibly installed at the customer's premises to aid the
Company in finding the proper location.
223. When the Company connects a customer's facilities to its supply lines,
arrangements are made for meters, transformers and other equipment to match
the installation as it is at that time. It is essential that the customer or contractor
give notice to the Company of any large additions in load. It is desirable for them
to consult with the Company before adding such loads so that the Company's
equipment of the proper size will be provided. If the customer wishes to make any
alterations in his service or desires the relocation of any Company equipment or
facilities at any time following the establishment of his service, the customer must
notify the Company, obtain its approval and bear the entire cost of such changes.
224. To safeguard both the property of the customer and that of the Company, the
customer is cautioned against over sizing either the main fuses or those of branch
circuits by installing fuses or circuit breakers larger than approved by the National
225. The customer's wiring and equipment are to be maintained by him in the condition
required by the insurance and governmental authorities having jurisdiction. The
customer will use the equipment and service in such a manner as not to disturb
the Company's service to other customers.
226. For reliable, quality service it is necessary that the wiring on all single phase three
wire installations be balanced so that the current will be, as nearly as possible, the
same in each load wire with the neutral wire carrying a minimum of current. In
installations, especially of a commercial type, where the single phase load is the
majority factor it is recommended that careful consideration be given to the use of
four wire WYE service, if available. Complete details of the advantages of this type
of service where applicable, can be obtained from the Company.
227. It is also necessary, for good service, that the customer must take action to
properly balance the load on each phase of all three-phase circuits.
228. The Company will endeavor to furnish continuous service but does not guarantee
uninterrupted service; is not liable for any damage which the customer may sustain
by reason of the loss of energy, or the loss of one or more phases; nor is the
Company liable for any damage due to reversal of phases; unless such reversal
occurs as a result of Company work; nor is the Company liable for damage that
may be incurred by the use of any service wiring, connections, instruments,
services or electrical appliances installed by or for the customer; nor is the
Company liable for damages that may be incurred due to the presence of the
Company's property on the customer's premises. If the customer requires three-
phase service, the installation and maintenance of adequate relays and circuit
breakers to protect against single-phase conditions, and phase reversal is
advisable and the installation and maintenance is the responsibility of the
customer. Further, the Company strongly recommends that ALL MOTORS
(INCLUDING SINGLE PHASE) BE PROVIDED OVERLOAD PROTECTIVE
DEVICES.
Grounding
229. Ground wires and ground rods installed in accordance with the requirements and
specifications of the latest approved edition of the National Electrical Code, or in
230. Minimum code grounding requirements are based on national average conditions.
Our service area experiences a higher than average level of lightning activity and
the customer’s equipment is subject to more probability of damage from this cause.
Although there is no known positive protection from the higher magnitude lightning
surges, the best grounding possible, within economic reason, as close to the
equipment as possible is the best protection.
231. An approved ground system and ground electrode system as specified in the latest
approved edition of the National Electrical Code shall be supplemented by
requirements of the Company and other authorities having jurisdiction. The
Company requires the customer to install a 5/8" by eight foot solid ground rod or
3/4" by eight foot galvanized iron pipe as a grounding electrode with a grounding
electrode conductor from the ground rod to the ground connection in the meter
base. The Company requires that the ground electrode system be electrically
bonded to other systems used as grounding electrode systems such as house
water system, underground piping system well casing, etc. The Company only
accepts copper grounding conductors in the meter bases. The Company suggests
that contractors advise customers of these requirements in order that they know
their importance.
232. The Company cannot allow the installation of foreign grounding conductors within
its pad-mounted switchgear and transformers or the attachment of foreign
grounding conductors to its grounds. Exception: bonding of above ground metallic
supply and communication enclosures that are separated by a distance of six feet
or less from our pad-mounted switchgear and transformers is acceptable.
Final Connections
233. THE COMPANY WILL MAKE ALL FINAL CONNECTIONS BETWEEN THE
COMPANY’S MAINS AND THE CUSTOMER’S WIRING AND IT WILL NOT
PERMIT UNAUTHORIZED CONNECTIONS.
Inspections
234. The wiring and appliances of the customer should be installed and maintained in
accordance with and should conform to the requirements of the latest approved
editions of the National Electrical Code and to such state, county and municipal
235. Where law requires inspection, the customer must have the wiring inspected and
approved by an authorized electrical inspector and have the installation released
for connection before the Company can make connection to its system. The
Company is prohibited by law from making service connections until a favorable
release is received.
236. In those areas served by the Company where an authorized electrical inspector's
final report is not mandatory by law, the Company shall have the right, but shall
not be obligated, to inspect any installation on the customer's premises before
electrical energy is supplied or at any later time, and reserves the right to reject
any wiring or appliance not installed in accordance with the Company's standard
requirements. Such inspection, or failure to inspect, or to reject, shall not render
the Company liable or responsible for any loss or damage resulting from defects
in the installation, wiring, or appliances or from violation of the Company's rules,
or from accidents which may occur upon the premises of consumer directly or
indirectly as the result of the connection of the electrical source. In case of
disagreement, the Company reserves the right to have such an inspection made
at its expense by a certified electrical inspector and favorable report rendered by
him before electrical service will be established.
238. After the customer has applied for and/or received service from the electrical utility,
he shall make every reasonable effort to prevent tampering with the meter and
service drop/service lateral serving his premises. A customer shall notify the
Company as soon as possible, of any tampering with, damage to, or removal of
any equipment.
239. Any form of meter tampering and/or fraudulent use may be cause to take one or
more of the following actions against the customer:
301. An "Overhead Service" is the complete wiring system from the Company's
overhead distribution lines to a building including the customer's service entrance
wiring and service equipment. The "service conductor" is the overhead conductors
from the Company's distribution lines to the building. The "service entrance
conductors" are those conductors installed by and at the expense of the customer
between the point of attachment of the "service conductors" to the customer's
building and the customer's "service equipment" within or on the building.
303. In order to avoid errors, the customer, architect, or contractor must obtain from the
Company the location of the point of attachment on the building of the Company's
service conductors. Upon inquiry by the customer, the Company will as far as
practicable designate a location for service conductors and their point of
attachment to the building that is mutually acceptable. The Company will assume
no responsibility to change the location of its service conductor attachments if an
improper location is chosen without consultation with the Company or if the
mutually accepted location is not utilized. If in the opinion of the Company there
is a reasonable appropriate location on a building where the Company's service
conductors can be attached by running them from an existing pole, and the
customer wants another pole set for his convenience or desire, the customer shall
pay the cost thereof and such extra facilities will become the property of the
Company.
304. The point of attachment should not be more than 30 feet above ground unless a
greater height is required to obtain the proper clearance. WHERE THE DESIGN
OF THE BUILDING WILL NOT PERMIT THE ABOVE-MENTIONED
CLEARANCES, SOME TYPE OF SERVICE STRUCTURE SATISFACTORY TO
THE COMPANY MUST BE PROVIDED BY THE CUSTOMER TO OBTAIN
305. The point selected for the attachment of the overhead service conductors shall be
located so that it is not necessary to install more than one set of wire attachments
on the customer's building. The attachment point shall not be closer than three
feet to the side of any window, awning, porch, fire escape or other parts of the
building, which are readily accessible to persons. The point of the attachment
should not be located above uncovered porches, platforms, oil tanks or other
elevated projections unless a clearance of 10 feet above such projections is
maintained (for voltages of not more than 150 volts to ground). In all cases,
clearances shall comply with latest approved edition of the National Electrical
Safety Code.
306. Safe and adequate anchoring structures for the Company's service conductors are
required of the customer, and in no case will the Company be responsible for the
condition of any customer's building or structure to which service wires are
attached or have been attached. Where mast services are required for attaching
service conductors, rigid galvanized iron conduit must be used and fastened with
a minimum of two - two hole straps attached with toggle bolts. Couplings are not
allowed above the top strap. (Other types of conduit are not acceptable).
307. The Company will furnish and the customer will install service drop attachment
fittings on all buildings requiring overhead service. The point of attachment shall
be suitable to hold the strain of the attachment secondary conductors. Where
anchor bolts are required they shall be 5/8 inch galvanized. These bolts must be
installed in a structural member of the building. A washer not less than 1/8 inch
thick and two inches square must be installed under the head of each bolt. The
threaded portions of the bolts are to project at least two inches beyond the outer
surface of the building wall. Secondary conductors to be a maximum 125' in
length. Service attachment points shall be able to support 1,000 pounds of
tension.
308. The service entrance conductors may consist of continuous lengths of multi-
conductor cable approved for the purpose or of individual conductors installed in
309. In order to prevent moisture from entering the raceway of service entrance
conductors or service cables, it is advisable to terminate them on an outside
building wall at a point approximately six inches above the point of attachment of
the highest service conductor so that the individual service entrance conductors
will extend downward to the points where connections are made to the service
conductors. These features make advisable the use of an approved fitting
(weather head) at the outer end of the service conductors, which permits the
conductors to extend downward only. When it is impossible to locate the
termination of service entrance conductors or service cable above the point of
attachments of the service conductors, a drip loop must be formed with the service
entrance conductors as they are connected to the service conductors. For
complete details see latest approved edition of National Electrical Code.
310. The location of the service entrance weather head shall be close enough to the
point of attachment of the overhead service conductors so that wires extending out
of the weather head can be connected to the overhead service conductors without
splicing. The side clearances shall be the same as those required for the overhead
service conductors.
311. Each conductor of the service entrance shall extend no less than two feet beyond
the weather head for wires smaller than 1/0 and not less than three feet for wires
of number 1/0 and larger to provide sufficient length for connection to the overhead
service conductors. Where drip loops are required these conductors shall be
further extended sufficiently to permit the bottom of the loops to project at least
eight inches below the weather head.
312. To protect the service entrance conductors and prevent the entrance of moisture,
all conduit and fittings used in the service entrance raceway are to be made rain-
tight. Also, rain-tight fittings shall be used on service entrance cable at all points
of connection between cable and meter sockets or other outdoor service
313. Where conduit is used, fittings with removable covers in the service conduit ahead
of the meter are prohibited except in very special cases and then only with prior
approval of the Company. If they are permitted, they cannot be concealed and
approved lockable or sealable cover types must be used.
314. In general, where no accessible common meter location is available for buildings,
such as duplex houses, apartment buildings, etc., separate sets of service
entrance conductors must be brought out to a common point on the building wall
to be connected to a single service drop.
315. Wires carrying metered energy are not to be located in the same raceway with
wires carrying un-metered energy.
316. All service entrance conductors must be of sufficient size to conform to the rated
ampacity of the service entrance equipment and also of sufficient size to provide
for reasonable future load increases.
317. Refer to the latest edition of the NEC to determine the correct service entrance
size and allowable number of conductors in conduit. The Company strongly
recommends that service entrance conductors smaller than #2 copper or #1
aluminum not be used. Further, the Company recommends that all single-phase
service be a minimum of three wire 100 amperes.
318. It is required that the neutral conductor of the service entrance wiring be plainly
identified. Bare or substantially white insulated wires are sufficient identification.
It is further required that on a 4 wire three phase Delta service the conductor having
the highest voltage to ground (high-leg) be connected to the center position (B
phase) of the customer's main line switch and to the line and load terminals on the
right hand side of the meter socket (Note: Prior to 1975 the NEC did not specify
the location of the "high-leg"; therefore, the customer should take all necessary
precautions to properly identify the "high-leg by marking its location orange"). This
conductor is to be identified at all connection points including weather head, meter
socket, and main switch.
402. For all underground services the Company, as far as practicable, will designate a
location for the service point to the building or in some cases a service point remote
from the building to which the customer must bring his service conductors. The
Company will assume no responsibility for changing the location of the service
conductor if an improper location is chosen without consultation with the Company
or if the previously designated location is not utilized.
404. In general where no accessible common meter location is available for buildings
such as duplex houses, apartment buildings, etc. separate sets of service entrance
conductors must be brought out to a common point on the building wall to be
connected to a single service lateral.
405. Wires carrying metered energy are not to be located in the same raceway with
wires carrying un-metered energy.
406. All service entrance conductors must be of sufficient size to conform to the rated
ampacity of the service entrance equipment and also of sufficient size to provide
407. It is required that the neutral conductor of the service entrance wires be plainly
identified. Bare or substantially white insulated wires are sufficient identification.
408. Company supplies standard overhead service to the customer. When underground
service is desired, customers should contact the local Company office and obtain
information as to what type of service is available or can be supplied.
409. The following rules apply for residential underground services fed from overhead
supply hereafter referred to as “hybrid services”.
c. For new hybrid services - The customer will pay in advance the difference
between the estimated cost of the hybrid and the estimated cost of a new
overhead service of the same current carrying capacity.
d. For conversion from overhead to hybrid - The customer will pay for the cost of
removing the overhead service and all costs associated with the installation of
the hybrid service.
412. As previously explained, the details of service from underground distribution are
more fully explained in the Company's Residential and Commercial Underground
Booklets. These booklets specifically and individually provide details for single-
family dwellings, apartments, condominiums, mobile homes, and commercial
customers.
415. In some cases it is impossible for the Company to determine in advance the exact
location at which service entrance conductors will enter a building on account of
possible interference from obstacles in the street. Because of this uncertainty, the
installation of the customer's service entrance equipment should not be made until
after the Company has completed the layout of the service entrance raceway into
the building, or until definite arrangements have been made with the Company.
501. Many types of metering installations are required to adequately register the sale of
electricity to customers. Factors such as voltage, load, rates, phase connectors,
and location are involved. THE COMPANY MUST, THEREFORE, RESERVE
FOR ITSELF THE ENTIRE DECISION AS TO HOW, WHERE, AND WHAT TYPE
OF EQUIPMENT IS TO BE INSTALLED. The Company will, as far as practicable,
cooperate with contractors and customers as to the location and feasibility of
installations in accordance with the desires of the customer.
502. Some types of installations are so familiar to contractors that customers may
depend on them to make installations which meet Company requirements without
consultation with the Company, but if this is done it in no way obligates the
Company to relinquish any of the decisions reserved for itself in these
specifications.
503. In general, all meters and metering equipment at secondary voltages must be
installed on the source side of customer's service entrance and/or service entrance
equipment, i.e., main disconnect, unless otherwise instructed by the Company or
the Company gives permission. On all new or existing installations that are to be
rearranged in any way that affects the customer's service entrance and/or service
entrance equipment, i.e., meter disconnect, standard meter socket and/or
instrument transformer cabinet shall be installed.
504. In Section 9 there are drawings and pictures that may be used as a guide for the
installation of typical jobs, after proper consultation with, and approval of the
Company. All of the rules in the text of this section, however, are to be considered
as supplementing them and considered a part thereof.
506. A guide listing the most common items involved in metering is shown in the
following table. This table also shows who is responsible for furnishing, installing
and maintaining the equipment. The Company reserves the right to determine
120/208V 4W WYE 201 - 600 amps - OH - Bolt-In, Form 9K K-7T bolt-in Customer
120/208V 4W WYE 201 - 600 amps - UG - Bolt-In, Form 9K K-7SW bolt-in Customer
120/208V 4W WYE 601+ amps < 150 KVA OH 2 ea. 600MCM, or 3 ea. 350MCM Bolt-In, Form 9K K-7T bolt-in Company
120/208V 4W WYE 601+ amps < 150 KVA UG 2 ea. 600MCM, or 3 ea. 350MCM Bolt-In, Form 9K K-7SW bolt-in Company
OH or
120/208V 4W WYE 601+ amps > 150 KVA - CT Meter, Form 9S A-Base Company
UG
120/208V V-phase OH or
0 - 200 amps - - Form 12S 5 jaw socket Customer
(Network) UG
120/208V V-phase OH or
201 - 600 amps - - Bolt-In, Form 12K K-5T bolt-in Customer
(Network) UG
120/208V V-phase OH or
601+ amps < 100 KVA 2 ea. 600MCM, or 3 ea. 350MCM Bolt-In, Form 12K K-5T bolt-in Company
(Network) UG
120/208V V-phase OH or
601+ amps > 100 KVA - CT Meter, Form 5S A-Base Company
(Network) UG
OH or
120/240V 3W 1PH 0 - 200 amps - - Form 2S 4 jaw socket Customer
UG
OH or
120/240V 3W 1PH 201 - 600 amps - - Form 2K K-4UT bolt-in Customer
UG
OH or
120/240V 3W 1PH 601+ amps < 100 KVA 2 ea. 500MCM, or 4 ea. 350MCM Form 2K K-4UT bolt-in Company
UG
OH or
120/240V 3W 1PH 601+ amps > 100 KVA - CT Meter, Form 5S A-Base Company
UG
OH or
120/240V 4W Delta 0 - 200 amps - - Form 16S 7 jaw socket Customer
UG
120/240V 4W Delta 201 - 600 amps - OH - Bolt-In, Form 9K K-7T bolt-in Customer
120/240V 4W Delta 201 - 600 amps - UG - Bolt-In, Form 9K K-7SW bolt-in Customer
120/240V 4W Delta 601+ amps < 150 KVA OH 2 ea. 600MCM, or 3 ea. 350MCM Bolt-In, Form 9K K-7T bolt-in Company
120/240V 4W Delta 601+ amps < 150 KVA UG 2 ea. 600MCM, or 3 ea. 350MCM Bolt-In, Form 9K K-7SW bolt-in Company
OH or
120/240V 4W Delta 601+ amps > 150 KVA - CT Meter, Form 9S A-Base Company
UG
OH or Integrated
277/480V 4W WYE 0 - 225 amps < 150 KVA 1 ea. 350MCM Form 16S Company
UG disconnect
OH or
277/480V 4W WYE 225+ amps > 150 KVA - CT Meter, Form 9S A-Base Company
UG
Metering Selection Guide.xls (2013)
507. The preferred location for meters is outdoors. This is a definite requirement for all
residences and small commercial buildings. (See paragraph 522 on Grouped
Installations). When any customer, falling in the above category, who has his
meter installation indoors, makes any change involving his service entrance
equipment or meter installation, he must make the necessary revision in his wiring
to provide for the meter to be moved outdoors.
508. Meters for large commercial customers or others in congested areas may be
indoors or outdoors as specified by the Company.
509. If, after the Company's portion of the work involved in a meter installation is
completed, the customer desires the meter to be relocated for his convenience and
the Company approves the relocation, the customer will bear all costs involved.
511. Meters shall not have any type structure, plant or other encumbrance within a
three-foot radius of the meter face. Meters shall not be installed where the
Company's meter readers or service people may inadvertently damage flower
beds or shrubbery or where it will be necessary for them to climb over fences or
other obstructions to read or service the meters, or in locations where they may be
accidentally damaged such as on buildings where they will extend unguarded into
stairways, alleys, walkways, or driveways. They shall not be installed on walls or
in areas subject to severe vibration, nor on porches, carports, breezeways, or any
location likely to be enclosed in the future. They shall not be installed over or under
fuel oil drums, nor close enough to such drums as to prohibit free access to the
meters. They shall not be installed under roof valleys of buildings with eaves less
than 12 inches in width. Meters must be installed on the building where there is
sufficient structural integrity to provide a mounting for the metering equipment. The
customer may be required to provide additional structural integrity if deemed
necessary by the Company.
512. The Company will not install meters indoors except in unusual circumstances. In
the event no outdoor location is feasible, the details for the location of the indoor
meters must be pre-approved by the Company.
513. Each meter located in an individual area in multiple occupancy buildings must be
served by a separate set of conductors in a separate raceway from the point on
the outside of the building where the service drop is attached. Meters located in a
common area serving two or more occupants of the same building may be served
by a single set of service entrance conductors.
514. Meters should preferably be located on the first floor of multi-story buildings, but
may be located in basements or other floors provided all other requirements of
these rules and the rules for mounting and group installations are met. Meters
shall be located in basements only when the ceilings are normal room height and
it is provided with a regular stairway, which is opened or closed with a standard
doorway.
515. Meters shall not have any type structure, plant or other encumbrance within a
three-foot radius of the meter face. Meters must be located in areas where they
will be readily accessible to Company personnel for installation, maintenance,
reading, testing, inspection or removal.
516. Meters must not be located in areas enclosed by trap doors or panels, or on lattices
or in coal or wood bins, in sheds, attics, bedrooms, bathrooms, toilet rooms,
restaurant kitchens, stairways, ventilating or elevator shafts. They must not be
located in areas where there is excessive vibration or dampness. They shall not
be installed in furnace or boiler rooms except by special permission of the
Company. Meters must not be installed near belts or other moving machinery that
would endanger the safety of those doing work near or on the meter. Meters
should not be installed in any place where unnecessary inconvenience will be
caused to either the customer or the Company in the performance of its regular
duties on customer's premises.
517. Rooms allocated for use of meters should not be used for any other purpose. At
least three feet of clear space must be maintained in front of meter installations
518. Outdoor meters shall be mounted so that the center of the meter shall be not more
than 72 inches and not less than 54 inches (42 inches for ganged) above finished
grade level. Ganged meters installed in meter rooms shall be mounted so that the
center of the meter shall be not more than 72 inches and not less than 42 inches
above floor level.
519. It is necessary that the socket be carefully and rigidly mounted so that the plane of
the front of the socket will be vertical and so that the meters when mounted on the
sockets will be in a true vertical position.
520. For fastening equipment and fittings to buildings with wood outside finish, use only
screws made of non-corrosive material of adequate strength. For brick, tile or
other types of masonry buildings, use only expansion shields, lead anchors or
inserts equipped with galvanized steel machine screws.
521. Some typical layouts are included in Section 9 of this booklet, but the company
should always be consulted for details on any particular job.
Grouped Meters
522. Grouped installations at the Customer's option may be made by using "pre-
bussed" multi- position units in which the service entrance conductors are
connected in the wiring compartment (see appendix). Grouped installations shall
be “ringless” in design. In selecting the appropriate method, the requirements of
the local authority enforcing code requirements must be considered.
523. Grouped installations of meters are special situations generally requiring special
methods and equipment. Prior approval with the Company is required before any
layouts are made or equipment is specified for job.
524. It is required that each meter socket in grouped installations be plainly and
permanently marked (on the inside of the meter socket and outside on the meter
socket cover) to indicate the area served by each. This rule applies whether meters
are installed indoors or outdoors, and whether or not the meters are ganged or
individually served from a common service entrance raceway.
This rule also applies to duplex residences or single residences converted into two
or more apartments, or a combination of residence and/or stores or offices. When
any occupancy is so marked the customer desiring service in such space must
provide this information when applying for service.
Meter Wiring
525. There are two basic types of meter wiring regardless of whether the installation is
single or three phase. One type is where the customer's service entrance
conductors are connected to the meter socket terminals, and is known as a self-
contained metering installation. With the other type the customer's service
entrance conductors pass through or are connected to instrument transformers,
and only the secondary wires from the instrument transformers are connected to
the meter socket terminals. This is known as an instrument transformer metering
installation. All service conductors (including the neutral) shall be terminated in
the self-contained meter socket. All service conductors (including the neutral) shall
pass through the instrument transformer cabinet.
526. When Company furnishes and installs residential underground service in approved
underground areas, the Company will make connections on the line side of the
meter socket and the customer will make connections on the load side of the meter
socket.
529. Meter sockets are also required for instrument transformer installations. Sockets
for instrument transformer meters will be mounted by the customer, except on
pole-mounted and pad-mounted transformer installations.
533. All service entrance equipment, including wiring troughs, pedestals, and/or
raceways, containing un-metered wires shall be of the sealable type.
534. It is required that the high voltage leg and neutral of four wire delta service entrance
conductors be identified in each box, cabinet, switch or trough through which they
pass. They shall be identified at the entrance weather head. Neutral or grounding
conductors of any system must be readily identifiable. Gray or white wire is
sufficient identification for neutral conductor. Bare, green or green with yellow
stripe is sufficient for grounding conductor. Orange will be used to identify the
"high leg".
535. The line side high voltage leg of a delta system should always be attached to the
top right terminal in meter sockets. The load side high voltage leg of a delta system
should be connected to the bottom right terminal in meter sockets.
536. In instrument transformer installations where it is not practical to use window type
transformers or instrument transformer cabinets, the transformers may be
mounted in a bus structure provided they are readily accessible to authorized
Company representatives for checking, testing, and replacement. However,
before such installation is made, the Company should be consulted regarding the
location of the meter and facilities required.
Freestanding Switchboards
537. Where the customer's installation is of the switchboard type, and the Company
desires it, meters and metering devices of the switchboard type will be used and
mounted on an approved panel furnished by the consumer. This panel or panels
will be reserved exclusively for the metering equipment.
538. The Company will supply necessary information to the customer for the fabrication
of switchgear in which instrument transformers are to be installed. The Company
will furnish the instrument transformers for the customer to install. The Company
will install the instrument transformer secondary wiring after all service entrance
equipment is installed.
539. Freestanding panels provided for meter installations are to have at least three feet
clear space in the back and front from any permanently installed obstruction.
542. Service at high voltages, above 480 volts, is subject to special negotiations
between the customer and the Company. Because the meter and service
installation for such service requires special engineering considerations, it is
always essential to consult the Company well in advance of the time such service
will be required. This will allow necessary time for the customer's and the
Company's design and construction to be properly coordinated and equipment
obtained.
601. Customer service equipment locations are to be in accordance with the latest
approved edition of the National Electrical Code (local codes and other authorities
having jurisdiction) and should always be located in a readily accessible place as
close as practicable to the electrical load center and in a place not likely to become
obstructed by future alterations or cause inconvenience to the customers when it
becomes necessary to operate the equipment or renew fuses.
602. Consideration should be given to the location of branch circuit protection devices
on the same floor served by the circuits. The use of such sub-distribution centers
fed by suitable feeder circuits will result in short branch circuits and improved
service
603. The Company will, upon request, supply necessary information concerning
available fault current to enable the customer to determine the required interrupting
capacity of protective devices which are to be installed at any definite location on
the system. (This is of particular importance in network areas, or where the size
of the service is large.) While the Company will endeavor where possible to
anticipate system changes which may affect these values, it does not assume
responsibility or liability with respect to such protective devices, nor does the
Company guarantee their continuing adequacy against increased fault current
interrupting requirements resulting from system growth and changes.
604. The protective equipment installed, regardless of type, should be of such capacity
as to permit the full utilization of the capacity of the service entrance conductors
installed at the time of original installation and vice versa. This will tend to minimize
expensive reinstallation of service conductors or equipment as the load increases.
Automatic circuit breaker type service equipment is preferable in all cases and its
use is strongly recommended. It provides a means by which service may be
readily restored immediately and conveniently when interior trouble causes them
to operate.
605. Size of service entrance conductors and equipment shall have sufficient ampacity
606. Service entrance conductors shall be without splice except at the meter enclosure
where an approved bolted connection for copper wire and approved compression
connection for aluminum is permitted.
607. Unless otherwise required by local authority, a main disconnecting means is not
required for six circuits or less. If more than six circuits are needed, a main switch
must be provided, or the circuits grouped on sub-mains so that the total number of
disconnect mains to all circuits shall be six or less and located at the same place
608. Although fuse type equipment is acceptable, automatic circuit breakers are
preferred for this class of service because of the convenience in immediately
restoring service and the automatic interruption of all three phases supplying
power to the equipment when the circuit protection operates.
609. Three-phase service is usually required for industrial and large commercial
customers and requires special design considerations. The Company is available
for consultation for such services; however the customer should contact his
architect, engineer or electrical contractor as soon as possible.
701. This section is intended to cover only the major considerations of a highly
specialized type of service. This type of service is usually confined to serving one
large customer of commercial or industrial character and each installation will
present individual problems, which will have to be resolved by close coordination
between the customer, his representatives and the Company.
702. Transformer vaults shall contain only the supply transformers and associated
equipment, and UNDER NO CONDITIONS are any meters or customer's
secondary fuses, switches, or other customer's equipment to be installed therein.
Secondary devices and meters, however, should be installed as near the
transformer vault as practicable.
703. The National Electrical Code provides specific design limitations for transformer
vaults in buildings. Always consult appropriate inspection authorities concerned
before planning or building transformer vaults. Building regulations are not
necessarily uniform.
704. Underground Primary Services are to be considered special in all cases and
permission for such installations shall be obtained from the Company in advance.
705. Underground primary service will be provided only when overhead service is not
feasible, or when it is mutually advantageous to the Company and customer.
Customers Vault
707. For customers who provide vaults or Company owned transformers that serve no
other customers and who receive service at secondary voltages (whether primary
metered or not) the Company will:
(1) Where the vault is adjacent to the street property line, furnish, install and
maintain the primary service entrance facilities.
(2) Where the vault is installed some distance from the street property line for the
customer's convenience or to reduce his secondary wiring costs, the Company
will furnish, install and maintain the primary raceway to the property line and
the customer shall furnish, install and maintain the primary raceway from the
street property line to the vault.
801. The following requirements apply to all motors connected to the DISTRIBUTION
SYSTEMS of the Company.
802. The National Electrical Code provides that some motors less than one horsepower
and that all motors one horsepower and above be equipped with suitable starting
switches having overload protection.
803. Phase reversal, low voltage, high voltage, or loss of one or more phases can
damage motors. To protect motors from these conditions, it is recommended that
protective relays or devices be used to automatically disconnect motors from the
voltage supply. Such devices are installed and owned by the customer and are
his responsibility.
804. The use of automatic time-delay circuit breakers for circuit protection in all cases
is strongly recommended. Where fuses are used, they should always be of the
time-delayed type. The time-delayed will, in many instances, prevent unnecessary
shutdowns due to the tripping of an instantaneous type circuit breaker, or blowing
of ordinary short time fuses by larger currents resulting from motor starting,
temporary overloads or temporary low voltage conditions. These devices are
installed and owned by the customer and are his responsibility.
805. The Company reserves the right to specify voltage characteristics and starting
limitations of all motors in order to limit voltage fluctuation and disturbances to its
customers. The Company further reserves the right to specify whether it shall
supply single phase or three phase service to a customer in accordance with
service limitations as set forth in the Company's General Terms and Conditions,
and as in the following paragraphs.
806. Motors up to and including 1/2 horsepower may be operated at 120 volts or 240
volts but should be single phase, unless the customer already has three phase
service or municipality constraints require three-phase service.
808. Motors above five horsepower must be operated at a minimum voltage level of 208
volts. The Company reserves the right to require these motors to be three-phase.
809. All motors up to and including 20 hp may be started across the line provided such
motors do not cause voltage fluctuations and disturbances to other customers.
811. The Company does not assume the responsibility for satisfactory operation of 220
to 250 volt three-phase classes of equipment on 120/208-volt WYE services. The
Company does not assume responsibility for satisfactory operation of 208 volt
WYE three-phase class of equipment used on 240 volt three phase services.
813. The Company is prepared to furnish to its customer’s assistance and advice where
new loads are to be added to the Company's lines. Before any motors are
installed, it is necessary to consult the Company in order to determine the
character and adequacy of the available service and the starting KVA limitations.
Existing customers who plan to add motors should also check with the Company.
814. Full voltage starting is the simplest and lowest cost method of starting. Other types
of starting that reduce the starting KVA are more expensive, but may be required
by the Company to prevent disturbances to other customers connected to the
distribution system. Also, for his benefit the customer may want to install reduced
KVA starting equipment to eliminate mechanical shock to the motor as well as
prevent disturbances to his other equipment.
816. As outlined in paragraph 814, motors may or may not need reduced KVA starting
equipment and BEFORE PURCHASING A MOTOR, the customer must:
(2) Consult the motor manufacturer so that the best motor and starter suited for
the job is purchased.
817. The following are guidelines that the Company will use in determining the
acceptability of large motors.
(2) Generally motors 50 through 100 horsepower will be required to have reduced
KVA starting equipment that will limit inrush current to 33 and one-third percent
of locked rotor current.
(3) Motors must reach at least 85 percent synchronous speed before switching to
"run" position.
NOTE: Locked rotor current is generally defined as six times full load current.
818. Reduced KVA starting equipment is usually required and all cases shall be
submitted to the Company for approval prior to purchasing.
819. There are many different types of starting equipment and it is important that the
customer contact the manufacturer so that motor and starter are properly matched,
Comparison Table #1
To aid in the selection of the type of starting best suited for the limitation involved.
1. Low torque
1. Smooth acceleration – motor
efficiency.
voltage increases, with speed.
2. Resistor gives off
2. High power factor during start,
heat.
requires expensive resistor.
3. Starting time in
3. Closed transition starting.
Primary Resistor 70 70 49 excess of 5
4. Less expensive than
seconds.
autotransformer starter in lower HP
4. Starting voltage
ratings.
difficult to adjust to
5. Available with as many as 7
meet varying
accelerating points.
conditions.
1. Requires special
motor design.
1. Moderate cost – less than primary
2. Starting torque is
resistor or autotransformer.
low.
Wye-Delta 100 33-1/3 33-1/3 2. Suitable for high inertia, long
3. Inherently open
acceleration, loads.
transition – closed
3. High torque efficiency.
transition available
at added cost
820. Starting equipment other than the types listed in Tables 1 and 2 may meet the
Company's starting requirements but the customer must establish proof of this
before the Company will give its approval. Customers are advised that it is very
difficult to establish such proof unless the motor supplier is the same as the driven
equipment supplier. Customers who purchase motors from one source and driven
equipment from another source quite often encounter difficulties in placing
responsibility for any problems that might arise. Therefore, it is again advised that
before purchasing a motor the customer should check carefully with the
manufacturer to insure that the best motor and starter for the job is purchased and
the torque requirements of the load are matched with the motor torque output.
Eighty-five percent synchronous speed should be obtained prior to switching from
"start" to "run". This will minimize "bump" in current during the transition from
"start" to "run" and will lengthen the life of the motor and starting equipment.
821. On many applications, motors will have to be started unloaded in order to meet the
starting requirements imposed by the Company. For example: LARGE
REFRIGERATION EQUIPMENT must be brought to rated speed unloaded.
HAMMER MILLS under no circumstances shall be loaded during starting. Even
when unloaded, hammer mills require excessive starting power and should be
given extra considerations.
823. THE GUIDES SHOWN HEREIN FOR LARGE MOTORS ARE GENERAL FOR
THE AVERAGE COMMERCIAL AREA. SPARSELY SETTLED AREAS,
RESIDENTIAL SECTIONS, AND AREAS ADJACENT TO HOSPITALS,
COMPUTER CENTERS, RADIO STATIONS, AND OTHER CUSTOMERS WITH
CRITICAL VOLTAGE EQUIPMENT, MAY REQUIRE MORE STRINGENT
RULES.
824. Industrial customers with their own substations or other customers in concentrated
industrial areas may be permitted to waive these rules upon approval by the
Company.
Special Equipment
825. The customer should maintain his power factor as near unity as possible. A good
power factor could result in a reduction of monthly billing and may permit the
reduction of conductor and equipment sizes. Where large capacity motors are to
be installed, consideration should be given to the use of synchronous type
equipment.
826. The Company will serve no gaseous tube or other types of lighting equipment if
the power factor is less than that of present available high power factor equipment.
If power factor corrective equipment is made necessary by this specification, it will
be provided and maintained by the customer at his own expense. This applies to
all new installations and any changes in existing installations.
827. In general, capacitors must be applied more carefully than most types of electrical
equipment in order that satisfactory operation and maintenance will result. The
customer should confer with the Company before any installations of this type of
equipment are made.
828. Some other items of equipment which require special consideration for proper
operations are:
The following Service Characteristics are generally standard. The Characteristics of Service
that are available shall be obtained from the Company before any wiring is installed or
equipment purchased. In cases of multiple occupancy installations, the combined load may
be such that the Characteristics of the Service required will be different from that which the
individual customer's loads might indicate. In such cases the Company reserves the right to
determine the type of service, which will be supplied. (Contact your local office or Customer
Service Engineering if you need assistance).
For highway signs, travel trailers, traffic controllers, CATV amplifiers or other small power
loads. The service from the Company's facilities up to, and including, the meter shall be a
120/240 volt, single phase, three wire circuit. Company approval must always be obtained
in advance.
For general lighting and/or heating and cooking, and small power loads with individual
motors generally not over 5 hp. Where the total load exceeds 50 KVA, the Company may,
at its option, require the customer to arrange the wiring for three phase service.
For general lighting, heating, cooking and small power loads with motors generally not over
5 hp. Where the total load exceeds 50 KVA, the Company may, at its option, require the
customer to arrange the wiring for three-phase four wire service.
For large lighting loads, or combination lighting, heating/cooling and power. Single phase
load shall be balanced between phases.
For combination 120/240 volts, three wire, single phase and 240 volts, three-phase service,
where the load of either class substantially exceeds that to the other.
For power and general service installations having demands of not less than 30 KVA
Normally, for power installations having demands of not less than 30 KVA.
H. Service voltages higher than 480 volts are available only by negotiation with the
Company. The size and type of customer's load must warrant such an installation.
I. The Company’s standard method of providing three phase service is four wire wye.
The customer must take the neutral to their service equipment. The Company will
not make provisions in its equipment to accommodate a customer’s impedance
grounded system. Any such equipment will have to be installed on the customer’s
side of the installation
Drawing # Title
06.01-01 ................. Secondary and Service Construction
06.01-02 ................. Service Details
06.03-01A............... Mobile Home Overhead Service Notes
06.03-01B............... Mobile Home Overhead Service Pole
06.03-02A............... Temporary Overhead Service Notes
06.03-02B............... Temporary Overhead Service Pole
06.03-03A............... Residential Overhead Service Notes
06.03-03B............... Residential Overhead Service (Mast)
06.03-03C .............. Residential Overhead Service (House Knob)
06.04-01A............... Mobile Home Underground Service Notes
06.04-01B............... Mobile Home Underground Service Pedestal
06.04-02A............... Temporary Underground Service Notes
06.04-02B............... Temporary Underground Service Pole / Pedestal
06.04-03A............... Hybrid Service
06.04-03B............... Residential Hybrid Service - OH to UG Conversion
06.04-03C .............. Underground Service
06.04-05 ................. Communication Underground Service
19.01-01 ................. Meter Sockets
19.01-03 ................. Meter Clearance Requirements
19.01-04 ................. Meter Socket Mounting Configurations
19.01-05 ................. Modular (Ganged) Meter Assembly
19.02-01 ................. Single-Phase 120V 2W Meter
19.02-02A ............... Single-Phase 120/240V 3W Meter (200 Amps)
19.02-02B ............... Single-Phase 120/240V 3W Meter (201 - 600 Amps)
19.02-03 ................. Single-Phase 240/480V 3W Meter (200 Amps)
19.02-04A ............... Single-Phase 120/208V Network 3W Wye Meter (200 Amps)
19.02-04B ............... Single-Phase 120/208V Network 3W Wye Meter (201 - 600 Amps)
19.03-01A ............... Three-Phase 120/208V 4W Wye (200 Amps)
19.03-01B ............... Three-Phase 120/208V 4W Wye (201 - 600 Amps)
19.03-01C............... Three-Phase 120/208V 4W Wye (201 - 600 Amps)
19.03-02A ............... Three-Phase 120/240V 4W Delta (200 Amps)
19.03-02B ............... Three-Phase 120/240V 4W Delta (201 - 600 Amps)
19.03-02C............... Three-Phase 120/240V 4W Delta (201 - 600 Amps)
19.03-03A ............... Three-Phase 277/480V 4W Wye (200 Amps)
19.03-03B ............... Three-Phase 277/480V 4W Wye (200 Amps)
19.04-01 ................. CT Metering Enclosure
19.04-02 ................. CT Metering - Overhead Mast
NOTES:
1. THE NEUTRAL SHALL BE COMMON TO BOTH PRIMARY AND SECONDARY CIRCUITS
ON WYE SYSTEMS AND THE NEUTRAL SHALL BE MULTI-GROUNDED (SEE SECTION 8
FOR ADDITIONAL INFORMATION).
2. THE NEUTRAL CONDUCTOR SHALL ALWAYS BE IN THE TOP POSITION ON ALL OPEN
WIRE SECONDARY CIRCUITS.
3. SIZING OF SECONDARY AND SERVICE CONDUCTORS WILL DEPEND ON THE AMOUNT
OF LOAD, THE TYPE OF LOAD (SUCH AS MOTORS, ETC.) AND THE VOLTAGE DROP.
THE REQUIRED SIZE SHALL BE SPECIFIED BY THE DESIGNER AND IDENTIFIED ON
ALL WORK ORDERS.
4. WHEN USED WITH A 477 AAC (SAC) NEUTRAL, THE PULLEY BRACKET WILL NOT
ACCOMMODATE SERVICE PAYOFFS. AS SUCH, A SECOND PULLEY BRACKET SHALL
BE INSTALLED UNDERNEATH THE NEUTRAL PULLEY BRACKET.
5. STREETLIGHT CIRCUITS ARE CONSIDERED AS SECONDARY.
6. SEE DRAWING 01.03-06 FOR CLEARANCE FROM SWIMMING POOLS.
7. SEE DRAWING 03.01-03 FOR OVERHEAD SECONDARY/SERVICE CONDUCTOR
AMPACITIES.
8. SEE DRAWING 14.02-01 FOR UNDERGROUND SECONDARY/SERVICE CONDUCTOR
AMPACITIES.
9. SEE DRAWINGS 15.01-04, 15.01-05A AND 15.01-05B FOR PAD MOUNT TRANSFORMER
AND CABLE IDENTIFICATION METHODS.
10. SEE DRAWING 06.01-02 FOR SERVICE DETAILS.
11. SEE THE CONTRIBUTIONS IN AID OF CONSTRUCTION (CIAC) MANUAL FOR
ADDITIONAL DETAILS.
12. SEE SECTION 19 FOR METER SOCKET AND METERING DETAILS.
13. SEE THE TABLE BELOW FOR MAXIMUM UNGUYED MULTIPLEX SPAN LENGTH.
#2 TRIPLEX 150'
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
OVERHEAD SERVICES
THE POINT OF ATTACHMENT AT THE HOUSE, BUILDING OR OTHER APPROVED POINT OF
ATTACHMENT SHALL PROVIDE SUFFICIENT GROUND CLEARANCE AND BE OF SUFFICIENT
REV. 2 (03/18/19) - CHANGED SCE&G TO COMPANY
STRENGTH TO SUPPORT THE MAXIMUM EXPECTED LOAD OF THE SERVICE CONDUCTORS. ALL
SECONDARIES AND SERVICES SHALL MEET MINIMUM CLEARANCE REQUIREMENTS OVER ROOF,
SIDEWALK AND/OR STREET (SEE DRAWINGS 01.02-01, 01.03-01A AND 01.03-01B).
WIRE HOLDERS SHALL BE FURNISHED BY THE COMPANY AND INSTALLED BY THE CUSTOMER. SEE
DRAWING 06.01-07 FOR SERVICE ATTACHMENT DEVICES. SCREW-TYPE WIRE HOLDERS (HOUSE
KNOBS) OR OTHER ATTACHMENTS (TOGGLE BOLT OR LAG BOLT) SHALL BE SECURELY ANCHORED
INTO A STRUCTURAL MEMBER SUCH AS A STUD OR RAFTER OF WOOD FRAME BUILDINGS. POINTS
OF ATTACHMENT INSTALLED IN BRICK OR BLOCK STRUCTURES SHALL EMPLOY THE USE OF
LEAD-SHIELDS OR TOGGLE BOLTS. THESE DEVICES SHALL NOT BE INSTALLED IN MORTAR JOINTS;
RATHER THEY SHALL BE INSTALLED INTO OR THROUGH THE BRICK OR BLOCK ITSELF.
B B
A C A C
DURING STORM TROUBLE SERVICE RESTORATION, REMOVE THE CUSTOMER'S METER AND USE A
PHASE ROTATION METER TO ENSURE THE RECONNECTION WILL PROVIDE THE PROPER PHASE
ROTATION FOR THAT CUSTOMER AS INDICATED BY THE STICKER. IN ADDITION, IF THE SERVICE IS
DELTA, USE A VOLTMETER AT THE METER SOCKET TO ENSURE PROPER RECONNECTION OF THE
HIGH LEG/POWER LEG CONDUCTOR.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
MOBILE HOME OVERHEAD 03-18-19
06.03-01A
SERVICE NOTES 1
REV. 1 (03/18/19) - CHANGED SCE&G TO COMPANY
ITEM # DESCRIPTION
1 METER
2 PULLEY BRACKET
3 SERVICE (SOURCE) CONDUCTORS
ITEM # DESCRIPTION
4 CABINET AND CIRCUIT BREAKER(S)
5 CONDUIT (GALVANIZED IRON OR PVC) 2 INCH MIN DIAMETER
6 GROUND ROD (5/8" X 8' GALVANIZED OR COPPER CLAD)
7 PIPE STRAPS (SECURELY ATTACHING CONDUIT)
8 COPPER GROUND WIRE #6 MIN. (ALUMINUM NOT ACCEPTABLE)
9 SERVICE CONDUCTORS
10 METER SOCKET (RINGLESS AND UL APPROVED)
11 TREATED POLE (TIMBER NOT ACCEPTABLE FOR OVERHEAD SERVICE POLE)
12 CONDUIT SERVICE WEATHERHEAD
NOTES:
1. SOURCE SIDE CONNECTIONS IN METER SOCKET TO BE MADE BY COMPANY. LOAD SIDE
CONNECTIONS IN METER SOCKET TO BE MADE BY CUSTOMER. (EXCEPTION: FOR
OVERHEAD SERVICE THE CUSTOMER IS RESPONSIBLE FOR SOURCE AND LOAD SIDE
CONNECTIONS).
2. WEATHERHEAD TO BE LOCATED NO LOWER THAN 6 INCHES BELOW PULLEY BRACKET,
ITEM #2.
3. HEIGHT OF POLE MUST MEET NESC CLEARANCE REQUIREMENTS. (MINIMUM CLEARANCE
IS 12 FEET FOR PEDESTRIAN TRAFFIC, 15.5 FEET FOR DRIVEWAY AND 16.5 FEET FOR
TYPICAL ROADWAY).
4. METER POLE MUST BE SPOTTED BY COMPANY REPRESENTATIVE AND CAN NOT BE
INSTALLED FURTHER THAN 125 FEET FROM COMPANY POLE/TRANSFORMER.
5. IF DOWN GUY AND ANCHOR IS REQUIRED THE CUSTOMER SHALL BE RESPONSIBLE TO
FURNISH, INSTALL AND MAINTAIN.
6. GROUNDING CONDUCTOR (ITEM 8) TO BE SECURELY ATTACHED TO STRUCTURE.
7. ENTIRE ASSEMBLY TO MEET COMPANY, NEC AND LOCAL CODE REQUIREMENTS.
8. CALL PALMETTO UTILITIES PROTECTION SERVICE (PUPS) AT 811 BEFORE YOU DIG.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
MOBILE HOME OVERHEAD 11-14-16
06.03-01B
SERVICE POLE 0
FORMERLY DWG # MTR-MH, S2
3 2
12
9 5
7
1
MINIMUM REQUIREMENT
10 15' MIN
FOR METER IS
ROUND TREATED POLE
4
WITH 5 INCH DIAMETER
AT TOP 6' - 0" MAX
4' - 6" MIN
8
5
11
NOTES:
1. SEE DRAWING 06.03-01A FOR A LIST OF ITEMS AND NOTES.
2. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
3. SEE DRAWING 06.01-03 FOR MOBILE HOME SERVICE DETAILS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
01-15-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
TEMPORARY OVERHEAD 03-18-19
06.03-02A
SERVICE NOTES 1
REV. 1 (03/18/19) - CHANGED SCE&G TO COMPANY
ITEM # DESCRIPTION
1 METER
2 PULLEY BRACKET
3 SERVICE (SOURCE) CONDUCTORS
ITEM # DESCRIPTION
4 CIRCUIT BREAKER(S) AND RECEPTACLES.
5 CONDUIT (GALVANIZED IRON OR PVC) 2 INCH MIN DIAMETER
6 GROUND ROD (5/8" X 8' GALVANIZED OR COPPER CLAD)
7 PIPE STRAPS (SECURELY ATTACHING CONDUIT)
8 COPPER GROUND WIRE #6 MIN. (ALUMINUM NOT ACCEPTABLE)
9 SERVICE CONDUCTORS (FROM WEATHERHEAD TO METER SOCKET)
10 METER SOCKET (RINGLESS AND UL APPROVED)
11 TREATED TIMBER/POLE (4 X 6 TIMBER OR 5 INCH DIAMETER @ POLE TOP MINIMUM)
12 CONDUIT SERVICE WEATHERHEAD
13 LUMBER (2 EACH - 2 X 4 MINIMUM) SECURELY FASTENED TO POLE AND STAKE
NOTES:
1. SOURCE AND LOAD SIDE CONNECTIONS IN METER SOCKET TO BE MADE BY CUSTOMER.
2. HEIGHT OF POLE MUST MEET NESC CLEARANCE REQUIREMENTS. (MINIMUM CLEARANCE
IS 12 FEET FOR PEDESTRIAN TRAFFIC, 15.5 FEET FOR DRIVEWAY AND 16.5 FEET FOR
TYPICAL ROADWAY).
3. TEMPORARY SERVICE POLE CAN NOT BE INSTALLED FURTHER THAN 125 FEET FROM
COMPANY POLE/TRANSFORMER.
4. SERVICE ENTRANCE CONDUCTOR (ITEM 9) SHALL EXTEND MINIMUM OF 3 FEET OUT OF
WEATHERHEAD.
5. POLE MUST SUPPORT COMPANY SERVICEMAN ON A LADDER. UNSAFE CONDITIONS ARE
NOT ACCEPTABLE.
6. GROUNDING CONDUCTOR (ITEM 8) TO BE SECURELY ATTACHED TO STRUCTURE.
7. IF DOWN GUY AND ANCHOR ARE REQUIRED, THE CUSTOMER SHALL BE RESPONSIBLE TO
FURNISH, INSTALL AND MAINTAIN.
8. ENTIRE ASSEMBLY TO MEET COMPANY, NEC AND LOCAL CODE REQUIREMENTS.
9. CALL PALMETTO UTILITIES PROTECTION SERVICE (PUPS) AT 811 BEFORE YOU DIG.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
TEMPORARY OVERHEAD 11-14-16
06.03-02B
SERVICE POLE 0
FORMERLY DWG # MTR-T1, S2
2
12
3
18"
9
5
11
10 1
10' MIN
13 4
6' - 0" MAX
8 4' - 6" MIN
4' MIN
6
GROUND IN
ACCORDANCE
WITH LOCAL
BUILDING CODES
NOTES:
1. SEE DRAWING 06.03-02A FOR A LIST OF ITEMS AND NOTES.
2. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
01-15-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
RESIDENTIAL OVERHEAD 03-18-19
06.03-03A
SERVICE NOTES 1
NOTES:
REV. 1 (03/18/19) - CHANGED SCE&G TO COMPANY
1. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
2. CONTACT COMPANY TO HAVE FIELD PERSONNEL SPOT METER LOCATION BEFORE
INSTALLING METER SOCKET. IF NOT LOCATED PROPERLY, CUSTOMER COULD BE
REQUIRED TO RELOCATE.
3. METER SOCKET MUST BE INSTALLED ON LEFT OR RIGHT SIDE OF STRUCTURE
TOWARD FRONT; REAR OF PROPERTY IS UNACCEPTABLE. SPOT TO BE DECIDED BY
COMPANY BASED ON TRANSFORMER LOCATION.
4. COMPANY IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE OF OVERHEAD
SERVICE CONDUCTOR AND METER. ALL OTHER MATERIALS, I.E., METER SOCKET,
ENTRANCE WIRE AND CONDUIT, ARE THE RESPONSIBILITY OF THE CUSTOMER.
5. METER SOCKET AND CONDUIT MUST BE SECURELY ATTACHED TO STRUCTURE
(REFERENCE THE ELECTRIC SERVICE AND METER INSTALLATIONS MANUAL,
PARAGRAPH 520).
6. AT A MINIMUM, CONDUIT MUST BE ELECTRICAL GRADE SCHEDULE 40 GRAY PVC. IF
SERVICE MAST IS INSTALLED THROUGH AND ABOVE ROOF LINE, IT MUST BE
GALVANIZED IRON PIPE (ELECTRICAL METALLIC TUBING (EMT) IS UNACCEPTABLE).
THE CONDUIT MUST BE SECURED AND OF ADEQUATE STRENGTH TO "WITHSTAND
SAFELY THE STRAIN IMPOSED BY THE SERVICE DROP" (REFERENCE NEC 230.28)).
7. RECOMMENDED CONDUIT DIAMETER IS BASED ON ESTIMATED LOADING ON PIPE.
ACTUAL LOADING VARIES WITH SERVICE LENGTH AND CONDUCTOR SIZE.
8. FOR MAST SERVICE, THE WEATHER HEAD SHALL BE LOCATED ABOVE POINT OF
ATTACHMENT OF CONDUCTORS, AND SHALL NOT BE MORE THAN 4 FEET FROM
ROOF EAVE (EDGE) OR FASCIA BOARD.
9. FOR HOUSE KNOB SERVICE, THE WEATHER HEAD SHALL BE NO MORE THAN 24
INCHES FROM POINT OF SERVICE (REFERENCE NEC 230.54 (C)).
10.IF USED, HOUSE KNOB IS TYPICALLY ATTACHED BY USE OF LAG SCREW. HOUSE
KNOB (POINT OF ATTACHMENT) MUST BE SECURED AND OF ADEQUATE STRENGTH
TO "WITHSTAND SAFELY THE STRAIN IMPOSED BY THE SERVICE DROP"
(REFERENCE NEC 230.28).
11. SERVICE CABLE SHALL BE SUPPORTED WITHIN 12 INCHES OF WEATHER HEAD
(REFERENCE NEC 230.51 (A)).
12. SEE DRAWING 06.01-07 FOR SERVICE ATTACHMENT DEVICES.
13.IF SERVICE IS 4 WIRE DELTA, HIGH-LEG MUST BE MARKED/IDENTIFIED AT WEATHER
HEAD (REFERENCE NEC 230.56).
14.METER SOCKET MINIMUM/MAXIMUM HEIGHT IS ABOVE FINAL GRADE WITHIN 10 FEET
OF METER.
15.ENTIRE ASSEMBLY TO MEET COMPANY, NEC AND LOCAL CODE REQUIREMENTS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
RESIDENTIAL OVERHEAD JAL
11-14-16
06.03-03B
SERVICE (MAST) 0
4 IN. MIN.
FORMERLY DWG # MTR-D, S3
12 IN. MAX.
SEE CHART
4 FT. MAX.
PIPE STRAPS
METER SOCKET
SEE DRAWINGS
01.03-01A AND 01.03-01B
GROUND IN
ACCORDANCE
MINIMUM CONDUIT DIAMETER WITH LOCAL
BUILDING
HEIGHT ABOVE ROOF CONDUIT SIZE CODES
12" TO 24" 2"
24" TO 48" 2-1/2"
48" TO 84" 3"
84" TO 120" 3-1/2"
NOTE:
1. SEE DRAWING 06.03-03A FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
01-15-17 DOMINION ENERGY SOUTH CAROLINA, INC.
RESIDENTIAL OVERHEAD JAL
11-14-16
06.03-03C
FORMERLY DWG # MTR-D, S4
SERVICE (HOUSE KNOB) 0
SEE DETAIL
PIPE STRAP
METER SOCKET
SEE DRAWINGS
01.03-01A AND 01.03-01B
NOTE:
1. SEE DRAWING 06.03-03A FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
01-15-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
MOBILE HOME UNDERGROUND 03-18-19
06.04-01A
SERVICE NOTES 1
REV. 1 (03/18/19) - CHANGED SCE&G TO COMPANY
ITEM # DESCRIPTION
1 METER
2 SERVICE (SOURCE) CONDUCTORS
ITEM # DESCRIPTION
3 CABINET AND CIRCUIT BREAKER(S)
4 CONDUIT (GALVANIZED IRON OR PVC) 2 INCH MIN DIAMETER
5 GROUND ROD (5/8" X 8' GALVANIZED OR COPPER CLAD)
6 PIPE STRAPS (SECURELY ATTACHING CONDUIT)
7 COPPER GROUND WIRE #6 MIN. (ALUMINUM NOT ACCEPTABLE)
8 SERVICE CONDUCTORS
9 METER SOCKET (RINGLESS AND UL APPROVED)
10 TREATED TIMBER / POLE
11 ADDRESS OR LOT NUMBER (PERMANENTLY MARKED ON METER SOCKET COVER)
NOTES:
1. SOURCE SIDE CONNECTIONS IN METER SOCKET TO BE MADE BY COMPANY. LOAD SIDE
CONNECTIONS IN METER SOCKET TO BE MADE BY CUSTOMER.
2. METER POLE MUST BE SPOTTED BY COMPANY REPRESENTATIVE AND CANNOT BE
INSTALLED FURTHER THAN 125 FEET FROM COMPANY POLE/TRANSFORMER.
3. GROUNDING CONDUCTOR (ITEM 7) TO BE SECURELY ATTACHED TO STRUCTURE.
4. ENTIRE ASSEMBLY TO MEET COMPANY, NEC AND LOCAL CODE REQUIREMENTS.
5. CALL PALMETTO UTILITIES PROTECTION SERVICE (PUPS) AT 811 BEFORE YOU DIG.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
MOBILE HOME UNDERGROUND 03-18-19
06.04-01B
SERVICE PEDESTAL 1
REV. 1 (03/18/19) - CHANGED SCE&G TO COMPANY
10 1
3
1
11 3
101
MINIMUM
9 REQUIREMENT
6 FOR METER IS
6' - 0" MAX 4" X 6" TREATED
7
4' - 6" MIN TIMBER
CUSTOMER LOAD
30" MIN WIRE DEPTH AS
COMPANY SOURCE REQUIRED BY CODE
4' MIN
5
2 8
GROUND IN
ACCORDANCE WITH
LOCAL BUILDING
CODES
NOTES:
1. SEE DRAWING 06.04-01A FOR A LIST OF ITEMS AND NOTES.
2. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
3. SEE DRAWING 06.01-03 FOR MOBILE HOME SERVICE DETAILS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
TEMPORARY UNDERGROUND 03-18-19
06.04-02A
SERVICE NOTES 2
REV. 2 (03/18/19) - CHANGED SCE&G TO COMPANY
ITEM # DESCRIPTION
1 METER
2 PAD MOUNTED TRANSFORMER
ITEM # DESCRIPTION
3 CIRCUIT BREAKER(S) AND RECEPTACLES
4 CONDUIT (GALVANIZED IRON OR PVC) 2 INCH MIN DIAMETER
5 GROUND ROD (5/8" X 8' GALVANIZED OR COPPER CLAD)
6 PIPE STRAPS (SECURELY ATTACHING CONDUIT)
7 COPPER GROUND WIRE #6 MIN. (ALUMINUM NOT ACCEPTABLE)
8 SERVICE CONDUCTORS #4 MIN.-#2 MAX. (FROM TRANSFORMER TO METER SOCKET)
9 METER SOCKET (RINGLESS AND UL APPROVED)
10 CONDUIT SERVICE WEATHERHEAD
11 TREATED TIMBER / POLE (4X4 TIMBER OR 5 INCH DIAMETER AT POLE TOP MINIMUM)
NOTES:
1. SOURCE AND LOAD SIDE CONNECTIONS IN METER SOCKET TO BE MADE BY CUSTOMER.
2. TEMPORARY SERVICE POLE TO BE INSTALLED FRONT (DOOR/PAD LOCK) RIGHT SIDE OF
TRANSFORMER AND NO CLOSER THAN FOUR (4) FEET.
3. TEMPORARY SERVICE POLE CAN BE CONNECTED AT SECONDARY HANDHOLE OR
PEDESTAL.
4. CUSTOMER TO INSTALL SERVICE CONDUCTOR (ITEM 8) MINIMUM OF 12 INCHES BELOW
GRADE AND TO WITHIN ONE (1) FOOT OF POINT OF SERVICE (I.E., TRANSFORMER). WITHIN
ONE (1) FOOT OF TRANSFORMER, COMPANY REQUIRES AN ADDITIONAL 10 FEET OF
SERVICE CONDUCTOR TO MAKE CONNECTIONS.
5. GROUNDING CONDUCTOR (ITEM 7) TO BE SECURELY ATTACHED TO STRUCTURE.
6. ENTIRE ASSEMBLY TO MEET COMPANY, NEC AND LOCAL CODE REQUIREMENTS.
7. CALL PALMETTO UTILITIES PROTECTION SERVICE (PUPS) AT 811 BEFORE YOU DIG.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
TEMPORARY UNDERGROUND 11-14-16
06.04-02B
SERVICE POLE / PEDESTAL 0
4 FEET POLE
FORMERLY DWG # MTR-T2, S2
SERVICE POLE
AREA 10
11
TRANSFORMER FRONT
4
(PAD LOCK)
6
SERVICE POLE LOCATION 4
(TYPICAL) 1
9
2 8' MIN.
8
3
6
6' - 0" MAX
4' - 6" MIN
7
1' MIN.
4' MIN
1' MIN.
GROUND IN
5 ACCORDANCE
4' MIN
WITH LOCAL
BUILDING CODES
11
PEDESTAL 1
9
8 3
6 7
2
1' MIN.
4' MIN
1' MIN.
4' MIN
5
GROUND IN ACCORDANCE WITH
LOCAL BUILDING CODES
NOTES:
1. SEE DRAWING 06.04-02A FOR A LIST OF ITEMS AND NOTES.
2. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
01-15-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
METER NEUTRAL
SOCKET
12"
MSPD2
MSPD3
30" 30"
GROUND IN
ACCORDANCE
WITH LOCAL
BUILDING CODES 2" CONDUIT IS REQUIRED FOR 200 AMP METER
3" CONDUIT IS REQUIRED FOR 201 - 600 AMP METER
NOTES:
1. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
2. FOR SERVICE IN CONDUIT, THE CONDUIT SHALL BE INSTALLED 30 INCHES BELOW GRADE WITH
A MINIMUM OF 36 INCH RADIUS SWEEPS. IF NECESSARY, CUSTOMER MUST MODIFY STRUCTURE
FOOTING TO ALLOW 36 INCH RADIUS SWEEP.
3. ALL CONDUIT SHALL BE ELECTRICAL GRADE GRAY SCHEDULE 40 PVC.
4. NO MORE THAN THREE (3) 90 DEGREE BENDS ARE PERMITTED IN A SERVICE RUN.
5. SEE DRAWINGS 15.01-05A AND 15.01-05B FOR SECONDARY CABLE IDENTIFICATION.
6. HANDHOLE LOCATION DETERMINED BY COMPANY REPRESENTATIVE. HANDHOLE AND
UNDERGROUND CONNECTORS ARE NOT INCLUDED IN MACRO. SEE SECTION 13 FOR
SECONDARY ENCLOSURES AND HANDHOLES.
7. SEE DRAWING 06.04-03B FOR CONVERTING OVERHEAD TO UNDERGROUND SERVICE.
8. SEE DRAWING 07.02-01 FOR REQUIRED FOREIGN ATTACHMENT CLEARANCES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
RESIDENTIAL HYBRID SERVICE 03-19-19
06.04-03B
OH TO UG CONVERSION 2
MATCH A-A
REV. 2 (03/19/19) - CHANGED SCE&G TO COMPANY
OVERHEAD
SERVICE
METER
SOCKET
6'-0" MAX.
4'-6" MIN.
NEUTRAL
MATCH A-A
12"
METER
SOCKET
UNDERGROUND COMPANY
SERVICE HANDHOLE
6'-0" MAX. SEE NOTE 6
4'-6" MIN.
PIPE STRAP(S)
MATCH B-B
MATCH B-B
30" 30"
GROUND IN
ACCORDANCE WITH
LOCAL BUILDING 2" CONDUIT IS REQUIRED FOR 200 AMP METER
CODES 3" CONDUIT IS REQUIRED FOR 201 - 600 AMP METER
NOTES:
1. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
2. FOR SERVICE IN CONDUIT, THE CONDUIT SHALL BE INSTALLED 30 INCHES BELOW GRADE WITH
A MINIMUM OF 36 INCH RADIUS SWEEPS. IF NECESSARY, CUSTOMER MUST MODIFY STRUCTURE
FOOTING TO ALLOW 36 INCH RADIUS SWEEP.
3. ALL CONDUIT SHALL BE ELECTRICAL GRADE GRAY SCHEDULE 40 PVC.
4. NO MORE THAN THREE (3) 90 DEGREE BENDS ARE PERMITTED IN A SERVICE RUN.
5. COMPANY WILL INSTALL UNDERGROUND CONDUCTOR. RESIDENTIAL "CUSTOMER OWNED"
WIRE IS UNACCEPTABLE.
6. HANDHOLE LOCATION DETERMINED BY COMPANY REPRESENTATIVE. SEE SECTION 13 FOR
SECONDARY ENCLOSURES AND HANDHOLES.
7. INSTALLATION MUST CONFORM TO COMPANY, NEC, NESC AND LOCAL CODE REQUIREMENTS.
8. SEE DRAWING 07.02-01 FOR REQUIRED FOREIGN ATTACHMENT CLEARANCES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
COMPANY
HANDHOLE
FORMERLY DWG # MTR-D, S2
SEE NOTE 6
MATCH A-A
30"
METER
SOCKET
SOURCE
COMPANY
PAD MOUNT
TRANSFORMER
6'-0" MAX.
PIPE STRAP(S)
4'-6" MIN.
MATCH A-A
MATCH A-A
30"
30"
GROUND IN
ACCORDANCE WITH
LOCAL BUILDING
CODES 2" CONDUIT IS REQUIRED FOR 200 AMP METER
3" CONDUIT IS REQUIRED FOR 201 - 600 AMP METER
NOTES:
1. SEE DRAWINGS 06.01-01 AND 06.01-02 FOR GENERAL INFORMATION AND NOTES.
2. FOR SERVICE IN CONDUIT, THE CONDUIT SHALL BE INSTALLED 30 INCHES BELOW GRADE
WITH A MINIMUM OF 36 INCH RADIUS SWEEPS. IF NECESSARY, CUSTOMER MUST MODIFY
STRUCTURE FOOTING TO ALLOW 36 INCH RADIUS SWEEP.
3. ALL CONDUIT SHALL BE ELECTRICAL GRADE GRAY SCHEDULE 40 PVC.
4. NO MORE THAN THREE (3) 90 DEGREE BENDS ARE PERMITTED IN A SERVICE RUN.
5. SEE DRAWINGS 15.01-05A AND 15.01-05B FOR SECONDARY CABLE IDENTIFICATION.
6. HANDHOLE LOCATION DETERMINED BY COMPANY REPRESENTATIVE. SEE SECTION 13 FOR
SECONDARY ENCLOSURES AND HANDHOLES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
COMMUNICATION 03-20-19
06.04-05
UNDERGROUND SERVICE 1
CATV MANUFACTURED
PEDESTAL OR CABINET
REV. 1 (03/20/19) - CHANGED SCE&G TO COMPANY
SEE NOTE 3 1 3
2
101
5'-0" MAX. 4
2'-3" MIN.
30" MIN.
1'
5
6 GROUND IN ACCORDANCE
WITH LOCAL BUILDING CODES
ITEM # DESCRIPTION
1 METER
2 TRANSFORMER, PEDESTAL OR HANDHOLE
ITEM # DESCRIPTION
3 METER SOCKET (RINGLESS AND UL APPROVED)
4 COPPER GROUND WIRE (#6 MIN. - ALUMINUM NOT ACCEPTABLE)
5 GROUND ROD (5/8" X 8' COPPER CLAD)
6 CONDUIT AND SERVICE CONDUCTOR
NOTES:
1. ADDRESS OR LOT NUMBER TO BE PERMANENTLY MARKED ON COVER OF METER SOCKET.
2. CUSTOMER MUST INSTALL CONDUIT AND SERVICE CONDUCTOR WITHIN ONE (1) FOOT OF
COMPANY FACILITY (ITEM #2).
3. ADDITIONAL SERVICE CONDUCTOR, 10 FEET MINIMUM, IS REQUIRED FOR CONNECTING TO
COMPANY FACILITY (ITEM #2).
4. BONDING SHALL BE PROVIDED BETWEEN ALL ABOVE GROUND METALLIC POWER AND
COMMUNICATIONS APPARATUS THAT ARE SEPARATED BY A DISTANCE OF 6 FEET OR LESS
(REFERENCE NESC 384C).
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
METER SOCKETS
METER SOCKETS ARE FURNISHED, INSTALLED AND MAINTAINED BY THE CUSTOMER. ALL
REV. 2 (03/20/19) - CHANGED SCE&G TO COMPANY
METER SOCKETS SHALL BE RINGLESS, HAVE UL APPROVAL, AND COMPLY WITH ANSI C12.7
SPECIFICATIONS.
OVERHEAD SERVICE: SOURCE AND LOAD WIRES ARE TERMINATED IN METER SOCKET BY
THE CUSTOMER.
UNDERGROUND SERVICE: CONDUIT TERMINATES AT METER SOCKET ON BOTTOM LEFT OR
BOTTOM RIGHT (NEVER IN THE CENTER); SOURCE WIRES ARE
TERMINATED BY COMPANY; LOAD WIRES ARE TERMINATED BY THE
CUSTOMER.
UNDERGROUND
SERVICE
SOURCE
CONDUIT
OVERHEAD
SERVICE
NOTES:
1. ALL INSTALLATIONS SHALL MEET COMPANY, NEC AND LOCAL CODE REQUIREMENTS.
2. SOURCE CONDUCTORS SHALL ALWAYS BE TERMINATED IN THE TOP SIDE OF THE METER. FOR
CUSTOMER GENERATION APPLICATIONS, I.E., SOLAR, COMPANY IS ALWAYS THE SOURCE/LINE
AND THE CUSTOMER IS ALWAYS THE LOAD.
3. METER SOCKETS FOR UNDERGROUND MUST BE SIZED TO ACCOMMODATE THE BEND RADIUS
OF THE CONDUCTORS BEING INSTALLED (REFERENCE NEC TABLE 312.6(B)).
4. METERED AND UNMETERED CONDUCTORS SHALL NOT OCCUPY THE SAME RACEWAY.
5. ONLY COMPANY OWNED EQUIPMENT IS ALLOWED IN METER SOCKET.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
SEE NOTE 3
3' 3'
3'
6'-0" MAX
4'-6" MIN
3'
3' 3'
NOTES:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
2. PERMANENT AND/OR TEMPORARY OBSTRUCTIONS ARE NOT PERMITTED WITHIN THREE
FEET IN ANY DIRECTION OF AN ELECTRIC METER.
3. OBSTRUCTIONS INCLUDE, BUT ARE NOT LIMITED TO TREES, SHRUBS, HVAC UNITS,
GENERATORS, WALLS, FENCES, GAS METERS AND/OR BUILDINGS.
4. SEE DRAWING 19.01-05 FOR GANGED METER SOCKETS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
METER SOCKET MOUNTING 05-03-17
19.01-04
CONFIGURATIONS 0
6'-0" MAX
6'-0" MAX 4'-6" MIN
4'-6" MIN
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
104
101 105
SEE NOTE 4
ON
OFF
6'-0" MAX
102 106
103 107
3'-6" MIN
NOTES:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
2. EACH METER SOCKET SHALL BE PLAINLY AND PERMANENTLY MARKED, I.E., STENCILED
WITH ENAMEL PAINT, WITH UNIT NUMBER OR OTHER DESCRIPTION ON THE INSIDE OF THE
METER SOCKET AND ON THE OUTSIDE OF THE METER SOCKET COVER.
3. COMPANY PERSONNEL SHALL VERIFY THE UNIT NUMBER OR OTHER DESCRIPTION
MATCHES WHAT IS STENCILED BEFORE SETTING A METER.
4. COMPANY CANNOT ATTACH TO MAIN BREAKER OR DISCONNECT DEVICE. IF INSTALLED,
CUSTOMER CONNECTION POINT WILL BE A HANDHOLE OR OTHER DESIGNATED LOCATION.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
A
FORMERLY DWG # MTR-1, S1
H1 H2
A D
C B
X1 X3
X2
N
120V
L1
240V 120V
L2
JUMPER
REQUIRED
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
SINGLE-PHASE 120/240V JAL
04-24-17
19.02-02A
3W METER (200 AMPS) 0
A
FORMERLY DWG # MTR-1, S1
H1 H2
A D
C B
X1 X3
X2
N
120V
L1
240V 120V
L2
3 WIRE METER
200 AMP - 120/240V
FORM 2S METER
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
SINGLE-PHASE 120/240V JAL
04-24-17
19.02-02B
3W METER (201 - 600 AMPS) 0
A
FORMERLY DWG # MTR-1, S1 & S2
H1 H2
3 WIRE METER
201 - 600 AMPS - 120/240V
FORM 2K METER
A D
C B
X1 X3
X2
N
120V
L1
240V 120V
L2
K-4SW SOCKET
K-4UT SOCKET
ALTERNATE
LOCATION
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
SINGLE-PHASE 240/480V JAL
04-24-17
19.02-03
3W METER (200 AMPS) 0
A
N
FORMERLY DWG # MTR-2, S3
H1 H2
A D
C B
X1 X3
X2
N
240V
L1
480V 240V
L2
SEE NOTE 3
3 WIRE METER
200 AMP - 240/480V
FORM 16S METER
DISCONNECT
SWITCH
NOTES:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
2. SEE DRAWING 19.03-03A FOR METER SOCKET DETAILS.
3. NEUTRAL MUST BE TERMINATED ON SOURCE SIDE.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
SINGLE-PHASE 120/208V NETWORK JAL
05-04-17
19.02-04A
3W WYE METER (200 AMPS) 0
A
FORMERLY DWG # MTR-3, S1
B
C
N
H1 H2 H1 H2 H1 H2
A A A
C BD C BD C BD
X1 X3 X1 X3 X1 X3
X2 X2 X2
RED WHITE BLUE
N
120V
a
208V 120V
b
208V 208V 120V
c
3 WIRE METER
200 AMP - 120/208V
FORM 12S / 25S METER
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
SINGLE-PHASE 120/208V NETWORK JAL
05-04-17
19.02-04B
3W WYE METER (201 - 600 AMPS) 0
A
B
FORMERLY DWG # MTR-3, S2 & S3
C
N
H1 H2 H1 H2 H1 H2
A A A
C BD C BD C BD
X1 X3 X1 X3 X1 X3
X2 X2 X2
RED WHITE BLUE
N
120V
a
208V 120V
b
208V 208V 120V
c
3 WIRE METER
201 - 600 AMPS - 120/208V
FORM 12K METER
K-5T SOCKET
DO NOT REMOVE
GROUND TERMINAL
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 120/208V JAL
04-25-17
19.03-01A
4W WYE (200 AMPS) 0
A
B
FORMERLY DWG # MTR-4, S1 & S3
C
N
H1 H2 H1 H2 H1 H2
A A A
C BD C BD C BD
X1 X3 X1 X3 X1 X3
X2 X2 X2
RED WHITE BLUE
N
120V
a
208V 120V
b
208V 208V 120V
c
4 WIRE METER
200 AMP - 120/208V
FORM 16S METER
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 120/208V JAL
04-25-17
19.03-01B
4W WYE (201 - 600 AMPS) 0
A
B
FORMERLY DWG # MTR-5, S1 & S3
C
N
H1 H2 H1 H2 H1 H2
A A A
C BD C BD C BD
X1 X3 X1 X3 X1 X3
X2 X2 X2
RED WHITE BLUE
N
120V
a
208V 120V
b
208V 208V 120V
c
4 WIRE METER
201 - 600 AMPS - 120/208V
FORM 9K METER (KWH)
FORM 17K METER (KWH/KVA)
K-7T SOCKET
DO NOT REMOVE
GROUND TERMINAL
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 120/208V JAL
04-26-17
19.03-01C
4W WYE (201 - 600 AMPS) 0
A
B
FORMERLY DWG # MTR-5, S2
C
N
H1 H2 H1 H2 H1 H2
A A A
C BD C BD C BD
X1 X3 X1 X3 X1 X3
X2 X2 X2
RED WHITE BLUE
N
120V
a
208V 120V
b
208V 208V 120V
c
4 WIRE METER
201 - 600 AMPS - 120/208V
FORM 9K METER (KWH)
FORM 17K METER (KWH/KVA)
K-7SW SOCKET
DO NOT REMOVE
GROUND TERMINAL
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 120/240V JAL
04-26-17
19.03-02A
4W DELTA (200 AMPS) 0
A
B
FORMERLY DWG # MTR-4, S1 & S2
C
N
NO
H1 H2 H1 H2 H1 H2
A D A D A D
C B C B C B
X3 X1 X3 X1 X3 X1
X2 X2 X2
BLUE RED WHITE BLUE
N
120V
a
240V 120V
b
240V 240V
c
GH
HI G
LE
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 120/240V JAL
04-26-17
19.03-02B
4W DELTA (201 - 600 AMPS) 0
A
B
FORMERLY DWG # MTR-5, S1 & S4
C
N
NO
H1 H2 H1 H2 H1 H2
A D A D A D
C B C B C B
X3 X1 X3 X1 X3 X1
X2 X2 X2
BLUE RED WHITE BLUE
N
120V
a
240V 120V
b
240V 240V
c
GH
HI G
LE
4 WIRE METER
201 - 600 AMPS - 120/240V
FORM 9K METER (KWH)
FORM 17K METER (KWH/KVA)
K-7T SOCKET
DO NOT REMOVE
GROUND TERMINAL
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 120/240V JAL
04-26-17
19.03-02C
4W DELTA (201 - 600 AMPS) 0
A
B
FORMERLY DWG # MTR-5, S2
C
N
NO
H1 H2 H1 H2 H1 H2
A D A D A D
C B C B C B
X3 X1 X3 X1 X3 X1
X2 X2 X2
BLUE RED WHITE BLUE
N
120V
a
240V 120V
b
240V 240V
c
H
HIG G
LE
4 WIRE METER
201 - 600 AMPS - 120/240V
FORM 9K METER (KWH)
FORM 17K METER (KWH/KVA)
K-7SW SOCKET
DO NOT REMOVE
GROUND TERMINAL
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 277/480V JAL
03-20-19
19.03-03A
4W WYE (200 AMPS) 1
REDUCER
HUB PLATE
REV. 1 (03/20/19) - CHANGED SCE&G TO COMPANY
13-5/8"
DISCONNECT
SWITCH
(SEE NOTE 3)
41-1/2"
CU CODE: QSC277C2
STOCK CODE: 018.7740.6010
NOTES:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
2. THIS METER SOCKET IS SUPPLIED BY THE COMPANY AND INSTALLED BY THE CUSTOMER.
3. THE DISCONNECT SWITCH IS FOR COMPANY USE ONLY AND IS EQUIPPED WITH AN
INTERLOCKING MECHANISM THAT PREVENTS THE METER FROM BEING REMOVED OR
INSTALLED WHILE THE SOCKET IS ENERGIZED. THE DISCONNECT SWITCH SHALL BE
LOCKED/SEALED OPEN OR CLOSED BY USE OF A COMPANY LOCK.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
THREE-PHASE 277/480V JAL
04-26-17
19.03-03B
4W WYE (200 AMPS) 0
A
B
C
FORMERLY DWG # MTR-2, S4
H1 H2 H1 H2 H1 H2
X1 X2 X1 X2 X1 X2
NOTES:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
2. SEE DRAWING 19.03-03A FOR METER SOCKET DETAILS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
2-3/4"
FORMERLY DWG # MTR-CT, S2 & S3
8-1/2"
24-3/4"
080.7960.0513
NOTICE
3'
080.7960.0150
Please keep trees, shrubs,
bushes, fences or other
structures and debris at least
4 feet from this area.
6"
5/8"
METER
HANGER
GROUND
STUD
12"
4-1/2"
NOTE:
1. SEE DRAWING 19.01-01 FOR GENERAL INFORMATION AND NOTES.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
CT'S
48"
MIN
24" 24"
MAX MAX
1" SCH 40
GRAY PVC
CONDUIT
NOTICE
6'-0" MAX
4'-6" MIN CT METERING
ENCLOSURE
(SEE 19.04-01)
NOTES:
1. COMPANY WILL FURNISH CT METERING ENCLOSURE, CURRENT TRANSFORMERS (CT'S)
AND CT MOUNTING BRACKET. CT METERING ENCLOSURE SHALL BE NO MORE THAN 50
FEET FROM CT'S.
2. CUSTOMER IS RESPONSIBLE FOR INSTALLING CT METERING ENCLOSURE, CONDUIT, CT'S,
CT MOUNTING BRACKET AND GROUNDING.
3. METERING CONDUIT SHALL NOT BE ROUTED THRU BUILDING FACADE, GUTTER OR ANY
OTHER STRUCTURE (CONDUIT MUST OFFSET AS SHOWN).
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
TRANSFORMER
POLE
REV. 1 (03/20/19) - CHANGED SCE&G TO COMPANY
LIFT
POLE
CT'S
1" SCH 40
GRAY PVC
CONDUIT
CT METERING
ENCLOSURE
(SEE 19.04-01)
NOTICE NOTICE
6'-0" MAX
4'-6" MIN
NOTES:
1. COMPANY WILL FURNISH AND INSTALL CT METERING ENCLOSURE, CURRENT
TRANSFORMERS (CT'S), CT MOUNTING BRACKET AND GROUNDING. CT METERING
ENCLOSURE SHALL BE NO MORE THAN 50 FEET FROM CT'S.
2. ALL SECONDARIES AND SERVICES SHALL MEET MINIMUM CLEARANCE REQUIREMENTS
(SEE DRAWINGS 01.02-01, 01.03-01A AND 01.03-01B).
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
CT METERING - PAD MOUNT 03-20-19
19.04-04
TRANSFORMER 1
REV. 1 (03/20/19) - CHANGED SCE&G TO COMPANY
CT METERING
ENCLOSURE
CT'S (SEE 19.04-01)
X0 X1 X2 X3
PRIMARY
COMPARTMENT
SECONDARY SECONDARY
COMPARTMENT CONDUITS
NOTE:
1. COMPANY WILL FURNISH AND INSTALL CT METERING ENCLOSURE, CURRENT
TRANSFORMERS (CT'S), CT MOUNTING BRACKET AND GROUNDING. CT METERING
ENCLOSURE SHALL BE NO MORE THAN 50 FEET FROM CT'S.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
CT ENCLOSURES
SMALL: 24"W X 24"H X 10"D
(STOCK CODE: 018.0067.0500)
OR CT METERING
LARGE: 36"W X 32"H X 14"D ENCLOSURE
(STOCK CODE: 018.0067.0356) (SEE 19.04-01)
NOTICE
3'
6'-0" MAX
4'-6" MIN
NOTES:
1. COMPANY WILL FURNISH CT METERING ENCLOSURE, CURRENT TRANSFORMERS (CT'S), CT
MOUNTING BRACKETS AND CT ENCLOSURE. CT METERING ENCLOSURE SHALL BE NO
MORE THAN 50 FEET FROM THE CT'S.
2. CUSTOMER WILL FURNISH 1 INCH SCH 40 GRAY PVC CONDUIT/COUPLERS AND IS
RESPONSIBLE FOR INSTALLING CT METERING ENCLOSURE, CT ENCLOSURE, CT'S, CT
MOUNTING BRACKETS, 1 INCH SCH 40 GRAY PVC CONDUIT/COUPLERS AND GROUNDING.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
METER
WITH
PULSE
OUTPUT
ISOLATION RELAY
END-OF-INTERVAL
KWH PULSES
PULSES
(2 WIRE OR 3 WIRE)
(2 WIRE)
CUSTOMER'S CIRCUIT
(BY CUSTOMER)
NOTES:
1. SEE DRAWING 19.04-14B FOR PULSE TERMINAL ENCLOSURE WIRING DETAIL.
2. SEE DRAWING 19.04-14C FOR PULSE TERMINAL ENCLOSURE MOUNTING OPTIONS.
3. CUSTOMER IS RESPONSIBLE FOR INSTALLING CONDUIT AND CONDUCTORS FROM THE
PULSE TERMINAL ENCLOSURE TO THEIR EQUIPMENT.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
1
2
3
Z 4 Z
Y 5 Y
K 6 K
T1 7 T1
T2 8 T2
4/C #18 STR
CUSTOMER'S
CIRCUIT
(BY CUSTOMER)
PULSE
TERMINAL
ENCLOSURE
NOTE:
1. SEE DRAWING 19.04-14C FOR PULSE TERMINAL ENCLOSURE MOUNTING OPTIONS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
PULSE TERMINAL ENCLOSURE 05-04-17
19.04-14C
MOUNTING OPTIONS 0
CT METERING
ENCLOSURE CT METERING
(SEE 19.04-01) ENCLOSURE
(SEE 19.04-01)
PULSE
TERMINAL
ENCLOSURE NOTICE
NOTICE
6'-0" MAX
4'-6" MIN
PULSE 6'-0" MAX
4'-6" MIN
TERMINAL
1" SCH 40 ENCLOSURE
GRAY PVC
CONDUIT 1" SCH 40
GRAY PVC
CONDUIT
X0 X1 X2 X3
CT ENCLOSURE
NOTICE
3'
1" SCH 40
1" SCH 40 GRAY PVC
GRAY PVC CONDUIT
CONDUIT
NOTES:
1. CUSTOMER WILL TAKE PULSES AT PULSE TERMINAL ENCLOSURE (SEE DRAWING 19.04-14A).
2. SEE DRAWING 19.04-14B FOR PULSE TERMINAL ENCLOSURE WIRING DETAIL.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
06-05-17 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
LOAD SOURCE
REV. 1 (11/12/18) - CHANGED SPACING FOR CLUSTER MOUNT & CLUSTER MOUNT STOCK CODE; SPECIFIED TRIM WIRE SIZE
24"
SEE
NOTE 5
25"
"
78
CT (3 EA)
52"
"
36
14"
14"
#4 SD
CU
48"
PT (3 EA) SEE TABLE BELOW FOR USE 3/4"
MINIMUM CLEARANCES BOLTS FOR
CLUSTER
CLUSTER MOUNT MOUNT
NOTICE
018.0066.0200
CT METERING
6'-0" MAX
ENCLOSURE #4 SD CU
4'-6" MIN
(SEE 19.04-01) (CLUSTER MOUNT
TO POLE GROUND)
#4 HD CU
POLE GROUND
C A C A A C
4.16 KV 9" 9"
8.32 KV 9" 9"
12.47 KV 15" 12"
A A A 13.8 KV 15" 12"
EQUIPMENT SPACING DETAIL 23.9 KV 24" 18"
NOTES:
1. SEE DRAWINGS 04.01-01 AND 19.01-01 FOR GENERAL INFORMATION AND NOTES.
2. SEE SECTION 8 FOR GROUNDING DETAILS.
3. VERIFY AND MAINTAIN PROPER CLEARANCE BETWEEN CONDUCTORS, GROUNDS AND GUYS.
4. CONTACT DISTRIBUTION PLANNING FOR FUSE SIZE.
5. CT TRIM WIRE MUST MATCH THE AMPACITY OF THE PRIMARY CONDUCTOR.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
02-15-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
CUSTOMER GENERATION 04-10-19
19.06-01
METERING CONFIGURATIONS 1
C
O
M
CUSTOMER M P
A
PHOTOVOLTAIC ARRAY OR OTHER TRANSFORMER N
QUALIFYING GENERATION TYPE Y
GENERAL GUIDELINES:
CUSTOMER OFFSETS ENERGY REQUIREMENTS WITH ON-SITE GENERATION
CUSTOMER PURCHASES ENERGY FROM UTILITY AT APPLICABLE RATE
CUSTOMER DOES NOT RECEIVE CREDIT FOR ENERGY THAT MAY BE DELIVERED TO UTILITY
C
O
M
CUSTOMER M P
A
PHOTOVOLTAIC ARRAY OR OTHER TRANSFORMER N
QUALIFYING GENERATION TYPE M Y
GENERAL GUIDELINES:
GENERATION METER MAY BE REQUIRED FOR CERTAIN BILLING PROGRAMS
CUSTOMER OFFSETS ENERGY REQUIREMENTS WITH ON-SITE GENERATION
CUSTOMER PURCHASES ENERGY FROM UTILITY AT APPLICABLE RATE
CUSTOMER COMPENSATED FOR EXCESS ENERGY SENT BACK TO UTILITY AT APPLICABLE RATE
REFER TO DRAWING 19.06-02 FOR WIRING DIAGRAM AND METER BASE CONFIGURATION
C
O
M
CUSTOMER M P
A
PHOTOVOLTAIC ARRAY OR OTHER M TRANSFORMER N
QUALIFYING GENERATION TYPE Y
GENERAL GUIDELINES:
DUAL METERS REQUIRED
CUSTOMER PURCHASES ALL ENERGY FROM UTILITY AT APPLICABLE RATE
CUSTOMER SELLS ALL ENERGY TO UTILITY ACCORDING TO APPLICABLE RATE
REFER TO DRAWING 19.06-03 FOR WIRING DIAGRAM AND METER BASE CONFIGURATION
NOTES:
1. CUSTOMER EQUIPMENT MUST COMPLY WITH UTILITY SPECIFIED SAFETY REQUIREMENTS,
INCLUDING UL AND IEEE STANDARDS.
2. CUSTOMER ELECTRICAL MODIFICATIONS ARE SUBJECT TO LOCAL INSPECTION
REQUIREMENTS.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
COMPANY
TRANSFORMER
CUSTOMER
H1 H2
REV. 1 (04/10/19) - CHANGED DWG TITLE; RENAMED CONFIGURATION #2 "OFFSET / SELL" (FORMERLY "NET METERING"); UPDATED NOTES
(CONFIGURATION #2)
L1
120
240 N
120 SEE NOTE 4
L2
MAIN
SERVICE
METER
CUSTOMER
GENERATION
LOAD METER
CENTER (SEE NOTE 5)
CUSTOMER
DISCONNECT
(SEE NOTE 3)
NOTES:
1. CUSTOMER GENERATOR CAN BE SOLAR, WIND OR OTHER QUALIFYING SYSTEM.
2. ALL EQUIPMENT MUST BE UL APPROVED, MEET IEEE STANDARDS AND COMPANY SAFETY
REQUIREMENTS. INSTALLATION MUST MEET COMPANY, NEC, AND LOCAL CODE REQUIREMENTS.
3. MAIN SERVICE METER SOCKET AND CUSTOMER DISCONNECT MUST BE MARKED WITH PERMANENT
LABELS (SUPPLIED BY COMPANY). STOCK CODE 080.7960.0380 (WARNING LABEL); STOCK CODE
080.7960.0377 (OFFSET / SELL LABEL).
4. IF REQUIRED, A NON-UTILITY METER SOCKET MAY BE INSTALLED BETWEEN THE GENERATOR AND THE
MAIN SERVICE METER SOCKET. THE LOCATION OF THE NON-UTILITY METER SOCKET SHALL BE
DETERMINED BY A COMPANY REPRESENTATIVE (THE PREFERRED LOCATION IS NOT ADJACENT TO THE
MAIN SERVICE METER).
5. GENERATION METER ONLY REQUIRED FOR NET METERING.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.
JAL
COMPANY CUSTOMER
TRANSFORMER GENERATOR
REV. 1 (03/20/19) - CHANGED SCE&G TO COMPANY; UPDATED NOTES
H1 H2
BUY ALL / SELL ALL
(CONFIGURATION #4)
SEE NOTE 4
L1
120
240 N
120
L2
HOUSE GENERATION
METER METER
CUSTOMER
LOAD CUSTOMER
CENTER DISCONNECT
NOTES:
1. CUSTOMER GENERATOR CAN BE SOLAR, WIND OR OTHER QUALIFYING SYSTEM.
2. ALL EQUIPMENT MUST BE UL APPROVED, MEET IEEE STANDARDS AND COMPANY SAFETY
REQUIREMENTS. INSTALLATION MUST MEET COMPANY, NEC, AND LOCAL CODE REQUIREMENTS.
3. GENERATION METER SOCKET AND DISCONNECT SWITCH MUST BE MARKED WITH PERMANENT
LABELS (SUPPLIED BY COMPANY). STOCK CODE 080.7960.0380 (WARNING LABEL); STOCK CODE
080.7960.0376 (BUY ALL / SELL ALL LABEL).
4. UTILITY SIDE CONNECTIONS CANNOT BE MADE IN METER SOCKET; GANGED METER SOCKET IS
ACCEPTABLE.
EFFECTIVE
DATE:
DISTRIBUTION CONSTRUCTION STANDARD
04-29-19 DOMINION ENERGY SOUTH CAROLINA, INC.