Interlock Protection Handbook PDF
Interlock Protection Handbook PDF
2
23 Turbine 54
Boiler& Auxiliaries
Interlock & Protection
WPCL, Warora
3
Interlock & Protection of ID fan system
Start permissive
Front or rear fan bearing temperature is very high, delay 2 sec (>90ºc).
Front or rear motor bearing temperature is very high, delay 2 sec (>105ºc).
Motor coil temperature is very high (<135ºc).
Corresponding side APH (both main motor & DC motor) stopped, delay 300 sec.
Accident button action.
Outlet damper closed and ID fan running, delay 5 sec.
Outlet flue gas damper has been closed when IDF startup, time delay 60 seconds.
Front bearing (x direction) vibration is very high, time delay 5 seconds (7.1mm/s).
4
Front bearing (y direction) vibration is very high, time delay 5 seconds (7.1mm/s).
Rear bearing (x direction) vibration is very high, time delay 5 seconds (7.1mm/s).
Rear bearing (y direction) vibration is very high, time delay 5 second (7.1mm/s).
Inlet oil pressure of coupler is very low, after IDF is running, time delay 10 seconds (<0.05MPa).
Inlet oil pressure of coupler is very low, when IDF startup, time delay 30 seconds (<0.035MPa).
Inlet oil temperature of coupler is very high, time 5s (>85ºc).
Outlet oil temperature of coupler is very high, time delay 5 seconds (>95ºc).
Bearing temperature of coupler is very high, time delay 5 seconds (>95ºc).
Furnace pressure is low-low (2of3), time delay 25 seconds (-1470Pa).
Furnace pressure is high-high (2of3), time delay 25 seconds (+1470Pa).
This side IDF trip and the other side IDF is running, close damper
5
IDF inlet control damper (IGV)
All IDF and FDF have been stopped, open damper, time delay 5 minutes(from asking for free ventilation)
This side IDF trip and the other side IDF is running, close damper
IDF scoop tube
6
Interlock & Protection of FD fan system
Start permissive
Protection
7
Outlet shut-off damper closed after FDF is running, delay 5 second
Outlet shut-off damper not opened when FDF startup, delay 20 seconds
This side FDF tripped and the other FDF is running, close damper
This side FDF trip and the other side FDF is running, close damper
8
Close outlet damper
Place inlet vane at minimum position
Start FDF motor
Open outlet damper
Release inlet vane
9
Inlet flue gas damper closed
Outlet flue gas damper closed
10
Interlock test of main driving motor and auxiliary driving motor
APH (main motor and AUX. motor) stopped and no asking for free
Ventilation, delay 300 second, close damper
11
Interlock of air pre-heater and outlet secondary air damper
APH (main motor and AUX .motor)stopped and no asking for free
Ventilation, time delay 300 seconds, close damper.
12
Condition: inlet flue gas damper has been closed
Instruction: close outlet second air damper
Condition: outlet second air damper has been closed
Instruction: close inlet/outlet air primary damper
Condition: inlet/outlet air primary damper has been closed
Instruction: stop main motor of APH
CONDITION: main motor of APH has been stopped
Instruction: stop procedures fulfilled
Outlet Oil pressure of working pump is low (<0.12MPa), start standby pump
Fault of working pump, start standby pump.
Outlet Oil pressure of two pumps operation is high (0.3MPa), stop working pump
Guide bearing temperature is
High (>55°C), alarm, start working pump
Guide bearing temperature is
High (>70°), alarm
Guide bearing temperature is
Low (<45°), stop operating pump
Support bearing temperature is
High (>55°), alarm, start pump
Support bearing temperature is
High (>70°), alarm
Support bearing temperature is
Low (<45°), stop pump
13
Interlock & Protection of PA fan system
Start permissive
14
Front / rear bearing temperature is very high, delay 2 seconds (>90°C)
Front / rear motor bearing temperature is very high, delay 2 seconds >105°C)
Motor coil temperature is very high, delay 2 seconds (>135°C)
Bearing vibration(x direction) is very high, delay 2 seconds (>7.1mm/s)
Bearing vibration (y direction)is very high ,delay 2 seconds (>7.1mm/s)
Motor bearing vibration(x direction) is very high, delay 2 seconds (>7.1mm/s)
Motor bearing vibration(y direction) is very high, delay 2 second (>7.1mm/s)
Accident button action
MFT action
This IDF stopped after this IDF is running
Two IDF stopped after two IDF are running
Two FDF stopped after two FDF are running
Outlet damper closed after PA fan is running, delay 5 seconds
Outlet damper closed when PA fan startup, delay 20 seconds
15
Open Outlet inlet primary damper of this side APH
Close Outlet damper
Place inlet vane at minimum position
Start PA fan motor
Open Outlet damper
Release inlet vane
Start permissive
Barring gear motor retreated.
Coal ignition of corresponding layer permitted
Suitable temperature at outlet of coal pulverizer (55> t <-90 °C)
Coal puverizer high oil system OK (≥2.5MPa)
17
Coal feeder stopped, time delayed 10min
Loading pump stopped ,time delay 2s
Loading oil pressure <2.0MPa, time delay 2s
18
Interlock damper conditions
20
Start coal pulverizer, constant load
21
Stop permission condition
Mill stopped, time delay 120 minute
22
Interlock & Protection of Coal Feeder
23
Start permission conditions
When two seal air fans is running, outlet main pipe pressure is normal, permit stopping any a fan.
All primary air fans stopped
MFT tripped
24
Interlock & Protection of Scanner Air Fan
Stop permission
When two Flame detector cooling fans is running, outlet main pipe pressure is normal, permit stopping any a fan.
After MFT tripped, have 3 hours and flue gas temperature is less than 80 degree.
25
Interlock of Boiler
Two airpreheaters tripped after delay 5 minute, trip two induced draft fans, two primary air fans, 4 coal pulverizers, 4 coal
feeders in manner of interlock, close feeding oil quick close valve in manner of interlock, and trip all the oil guns
Two induced draft fans tripped, trip 4 coal pulverizers, 4 coal feeders in manner of interlock, close feeding oil quick close
valve in manner of interlock, and trip all the oil guns
Two induced draft fans tripped, trip two primary air fans, 4 coal pulverizers, 4 coal feeders in manner of interlock, close
feeding oil quick close valve in manner of interlock, and trip all the oil guns
Two primary air fans tripped, trip 4 coal pulverizers, 4 coal feeders
One airpreheater tripped after delay 5 minute, trip this side induced draft fan, one this side primary air fan
One induced draft fan tripped, trip this side forced draft fan, trip this primary air fan
When three or excess three operating coal pulverizers are running. One primary air fan tripped , trip 2 coal pulverizers of A
and D, 2 coal feeders of A and D
26
Flame detector cooling air pressure normal (4KPa)
Steam drum water level normal (-230> drum level<200mm)
MFT conditions
27
Close all cold/hot air valves of coal pulverizer
Trip all primary air fans
Send the MFT action signal to soot blower, tripped
Open all dampers of fuel air and auxiliary air.
Send the MFT.action signal to electric dust catcher ,tripped
Turbine tripped
Interlock of BTG
28
Interlock test checklist of steam and water system
Boiler emergency blow-off electric valve for water1#, 2# (set interlock switch)
When the water level of drum decreases from 100mm to 50MM, interlock close emergency blow-off electric valve1#,2#, low
water level alarm
When the water level of drum increases to 100MM, interlock open emergency blow-off electric valve1#,2#, high water level
alarm
Electric valve and control valve interlock condition of boiler desuperheating water
When MFT is started or the load is less than 20%, interlock close superheat steam system desuperheating water sub-electric-valve,
each desuperheating water control valve automatically changed to manual control, and interlock close
When superheater primary desuperheating water control valve of side A is closed(<3%),or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
29
Superheater primary desuperheating water control valve of side A is opened (>3%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
When superheater primary desuperheating water control valve of side B is closed(<3%),or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
Superheater primary desuperheating water control valve of side B is opened (>5%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
When superheater secondary desuperheating water control valve of side A is closed(<5%,or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
Superheater secondary desuperheating water control valve of side A is opened (>5%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
When superheater secondary desuperheating water control valve of side B is closed(<5%,or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
Superheater secondary desuperheating water control valve of side B is opened (>5%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
MFT starts or the load is less than 20%,interlock closes reheating system desuperheating water electric sub-electric-valve, each
desuperheating water control valve automatically changed to manual control, and interlock close
When reheater desuperheating water control valve of side A is closed(<5% or MFT starts, or the load is less than 20%,interlock
closes corresponding reheat desuperheating water sub-electric-valve
Reheater desuperheating water control valve of side A is opened >5% interlock opens corresponding reheater desuperheating
water sub-electric-valve.
When reheater desuperheating water control valve of side B is closed(<5%,or MFT starts, or the load is less than 20%,interlock
closes corresponding reheat desuperheating water sub-electric-valve
Reheater desuperheating water control valve of side B is opened >5% interlock opens corresponding reheater desuperheating
water sub-electric-valve.
Reheater emergency spray water control valve is closed<5% or MFT starts, or the load is less than 20%, interlock close
corresponding reheater emergency spray water electric valve
Reheater emergency spray water control valve is opened >5% interlock open corresponding reheater emergency spray water
electric valve
Boiler (startup) hearth heating steam general electric valve
The temperature of furnace is less than 80° and MFT starts, startup is accessible
30
No MFT, interlock is closed, startup is not accessible.
The pressure of drum is to 0.2Mpa, interlock close, startup is forbidden.
Start condition
Remote control
Trip condition
Motor fault
Interlock start conditions of LDO supply pump
Outlet pressure is low, start standby pump
Motor fault of operating pump, start standby pump
31
Light oil manifold pressure low: Low pressure of oil manifold (2of 3) lasts for more than 5s, and some oil angle valves still
open (<1.8MPa)
Light oil supply fast valve closed, and some oil angle valves still open;;
Low pressure of compressed air (2of 3) lasts for more than 10s, and some oil angle valves still open
32
Open the oil return quick close valve of light oil (meanwhile, open the fuel pressure regulation valve), closed after 10s. And
display "light oil fuel leakage test Actual actions proceeding" on operator station screen;
Within 300s, if the manifold pressure after the light oil feeding quick close valve low (difference value <0.05MPa), then the
light oil feed quick close valve leakage test passed; Or else, light oil feeding quick close valve considered leaked, fuel oil
leakage test failed, and it will be displayed on the operator station screen
If the light oil feeding quick close valve leakage test passed, open the light oil feeding quick close valve, charge oil: After the
manifold pressure becomes high
Within 180s, if manifold pressure after the light oil feeding quick close valve high (>2.8MPa, difference value <0.4MPa), then
the light oil return oil quick close leakage test passed; Or else, light oil return oil quick close valve considered leaked, leakage
test failed, and it will be displayed on the operator station screen
Trip Conditions
Light oil OFT
Ignition failed
Oil valve open failed
33
Oil valve not closed AND oil gun not forward
Sequence Start
Forward light oil gun
Forward igniter gun
Open light oil valve
Sequence stop
Close light oil valve
Forward light oil gun
Forward igniter gun
Open purge valve
Close purge valve
Backward light oil gun
Heavy oil system
HFO supply pump
Start condition
Remote control
Trip condition
Motor fault
34
Heavy oil manifold pressure low: Low pressure of oil manifold (2of 3) lasts for more than 5s, and some oil angle valves still
open;
Heavy oil supply fast valve closed, and some oil angle valves still open;;
Low pressure of atomizing steam (2of3) lasts for more than 10s, and some oil angle valves still open
Low temperature of heavy oil, time delayed 1min, and oil angle valve still open
35
Weight oil system fuel leakage test sequence
If permissive conditions are met, command to start up leakage test can be sent from the operator station screen;
Open the oil return quick close valve of heavy oil (meanwhile, open the fuel volume regulation valve), closed after 10s.
Within 300s, if the manifold pressure after the heavy oil feeding quick close valve low (<0.3MPa), then the heavy oil feeding
quick close main valve leakage test passed; Or else, heavy oil feeding quick close main valve considered leaked, fuel oil
leakage test failed, and it will be displayed on the operator station screen.
The heavy oil feeding quick close main valve leakage test passed, open the heavy oil feeding quick close main valve, charge
oil: After the manifold pressure becomes high, close heavy oil feeding quick main valve.
Within 180s, if manifold pressure after the heavy oil feeding quick close main valve high (>1.2MPa, difference value
<0.4MPa), then the heavy oil return oil quick close valve and oil valve leakage test passed; Or else, heavy oil return oil quick
close valve considered leaked, leakage test failed, and it will be displayed on the operator station screen.
Oil leakage test interrupting conditions
36
Heavy oil OFT
Il gun not feeded in place
Ignition failed
Oil valve open failed
Oil valve not closed AND oil gun not forward
Oil valve opened AND atomizing valve not opened.
Sequence Start
Forward Heavy oil gun
Open heavy oil atomizing valve
Open heavy oil valve.
Sequence stop
Close heavy oil valve
Close atomization valve
Forward heavy oil gun
Open purge or atomizing valve
Close purge or atomizing valve
Backward heavy oil gun
When the flue temperature ≤180°C, treats it as the normal situation, close the Bypass system and open the shield air circuit.
When the flue temperature >180°C, the Flue temperature will be bad for the filter bag, the control system will open the bypass
Valve and close the lifting valve in bag field, then the flue go though bypass directly to the outlet.
When the flue temperature descends to ≤160°C, the Control system will open the bag field’s lifting valve, and close bypass
valve. Right now the system is considered as normal status.
Seriously monitor the conditions of flue temperature, pressure drop and pressure of precipitator’s each point, makes a record
each 30 min, immediately contact with the supervisor or boiler mid-control while appears abnormal situation.
37
.
39
Vibration of CEP shaft is high (alarm≥ 7.1mm/s Trip≥ 11.2mm/s)
Interlock
Proper flash chamber temperature high (≥60◦C), opened in manner of interlock, non-high release
Condenser hot well water level regulation valve
Hot well water level high, closed in manner of interlock, non-high release
Hot well water level low, opened in manner of interlock
40
Temperature downstream LP bypass > 100◦C open in a manner of interlock
Interlock
When running CWP emergency tripped starts standby CWP in interlock
When Header pressure is low automatically start the standby pump in interlock
Discharge butterfly valve automatically after pump startup
When butterfly valve open 20deg CWP startup
41
After CWP startup 60 sec outlet butterfly valve accident, stop CWP
When CWP outlet valve close to 20 deg, stop CWP
When CWP tripped, outlet butterfly valve automatically closes
When running cooling water booster pump tripped and enable standby pump, interlock start up the standby pump
When cooling water booster pump main pipe pressure lower, start standby pump in interlock
Pump suction pressure <0.1MPa both pump will not start
42
Boiler Feed Pump Interlock & Protection
Protection
Deaerator water level LL (2of3) ≤380mm
Lube oil pressure LL ≤0.05 MPa
BFP operating booster pump inlet motor valve closed
Inlet oil temp working oil ≥130°C alarm 110°C
BFP thrust bearing temp ≥95°C alarm 80°C
Motor bearing temperature of booster pump end ≥90°C alarm 80°C delay 3 sec
Motor bearing temperature of hydraulic coupler end ≥90°C alarm 80°C delay 3 sec
Booster pump drive/free end bearing temp ≥90°C alarm 75°C delay 3
BFP inside /outside radial bearing temp ≥90°C alarm 75°C delay 3
BFP hydraulic couples radial bearing temp ≥95°C alarm 85°C delay 3 (1-7)
BFP winding temp ≥130°C alarm 110°C delay 3 (1 -6)
Local emergency button operated
When BFP operation, flow ≤128 t/hr and minimum flow valve is closed., delay 15 sec BFP will tripped.
Motorized feed water pump operating and booster pump inlet valve closed
Start Permissives
43
Booster pump inlet motorized valve & Recirculation valve fully opened
Lube oil pressure normal ≥0.1MPa
Deaerator water level normal
Booster pump inlet valve opened
Scoop tube position≤5%
Booster pump drive/free end radial bearing temperature <75°C
Motor bearing temperature of booster pump end <80°C
Motor bearing temp of hydraulic-coupler end <80°C
Hydraulic coupling bearing (10th point )< 85°C
BFP thrust bearing temp(upside, downside) <85°C
BFP winding temperature <110°C
Working oil cooler inlet temp<110°C
BFP outlet motor valve closed OR standby
Differential pressure of inlet screen for motorized feed water pump and booster pump is abnormal
44
Actions to enable motorized feed water pump as standby
Startup auxiliary oil pump
Interlock
Motorized feed water pump operating and lube oil pressure lower than 0.08 MPa, automatic startup
Enable motorized feed water pump as standby and start in manner of interlock
Motorized feed water pump stopped and protection ON
BFP operating and lube oil pressure higher than 0.3 MPa , delay 5 sec and auxiliary oil pump automatically stop
Vacuum system
45
Steam/water separator level is normal
Interlock
Start vacuum pump, interlock start-up circulate pump and open inlet butterfly valve
Stop vacuum pump, interlock close inlet butterfly valve
Running pump trip, interlock start standby pump
Steam/water separator level low, delay 5 min trip the pump
Vacuum pump A operating or standby, and separator water level low, automatically open water makeup solenoid valve of
steam-water separator
Vacuum pump A water level high, automatically close water makeup solenoid valve of steam-water separator
When condenser pressure >14 Kpa and one pump in operation , interlock start standby pump.
46
EH oil system
EH oil pump interlock protection
EH oil manifold pressure lower to 11.2 MPa alarm, and start up standby EH oil pump by means of interlock
DEH oil pump emergency trip, interlock start standby pump.
Start-up permissive
Oil tank level normal
Oil temperature is >20 deg C.
Deaerator system
Interlock
Deaerator water level HH (.2550mm), Deaerator overflow valve opened in manner of interlock,
Deaerator water level not high,(<2350mm) Deaerator overflow valve closed in manner of interlock
When water level is high II, close MOV of extraction # 3 , check valve of extraction # 3 , close drain control valve of HP
heater # 2 to dearator.(>2650mm)
HP heater system
Interlock
HPH # 1 water level is high II, open emergency drain control valve. (>600mm)
HPH # 1 water level is low I, close emergency drain control valve. (<250mm)
47
HPH # 1 water level is high III, HP heater is tripping (.>800mm)
HPH # 2 water level is high II, open emergency drain control valve, close normal drain control valve from HPH # 1 to HPH #
2 (>600mm)
HPH # 2 water level is low I, close emergency drain control valve. (<250mm)
HPH # 2 water level is high III, HP heater is tripping (.>800mm)
LP heater system
48
10s delay and load larger than 30% , close pipe drain valve after electric valve/before check valve for 4th stage steam
extraction
49
LPH # 6 water level is high II, open emergency drain control valve, close LPH # 5 normal drain to LPH # 6 control valve ,
close extraction #6 MOV , open extraction # 6 drain valve, Water side bypass MOV open & i/l & o/l MOV closed.
(>1050mm)
LPH # 6 water level is low I close emergency drain control valve (<700mm)
LPH # 6 water level is low II , interlock stop drain water pump. (≤550mm)
Drain valve in front of LPH # 4 extraction MOV interlock open
Turbine load is <20%
Check valve of extraction # 4 is close
MOV of extraction # 4 is close
50
Steam turbine HP main steam valve (right) upper seat drain valve
Steam turbine HP main steam valve (right) lower seat drain valve
Steam turbine HP casing steam exhaust pipe (left) drain valve
Steam turbine HP casing steam exhaust pipe (right) drain valve
Steam turbine HP casing steam exhaust manifold drain valve
Drain valve before 1st stage steam extraction electric valve
Drain valve before 1st stage steam extraction check valve
Drain valve after 1st stage steam extraction electric valve
Drain valve after 1st stage steam extraction check valve
HP bypass pipe drain valve
51
Left side reheating steam pipe drain valve
Right side reheating steam pipe drain valve
Steam turbine combined reheat valve (left) drain valve
Steam turbine combined reheat valve (right) drain valve
Drain valve before 3rd stage steam extraction electric valve
Drain valve after 3rd stage steam extraction check valve
Drain valve before 4th stage steam extraction electric valve
Drain valve after 4th stage steam extraction check valve
52
Steam turbine HP casing steam exhaust pipe (left) drain valve
Drain tank water level HH, opened in manner of interlock, not high, closed in manner of interlock
Steam turbine HP casing steam exhaust pipe (right) drain valve
Drain tank water level HH, opened in manner of interlock, not high, closed in manner of interlock
Steam turbine HP casing steam exhaust manifold drain valve
Drain tank water level HH, opened in manner of interlock, not high, closed in manner of interlock
Steam pipe drain valve before LP bypass valve A
Drain tank water level HH, opened in manner of interlock, not high, closed in manner of interlock
Steam pipe drain valve before LP bypass valve B
Drain tank water level HH, opened in manner of interlock, not high, closed in manner of interlock
Bypass system
HP Bypass
Automatic opening
53
Turbine trip
Automatic closing
Temperature behind HP bypass is High (360◦C)
Desuperheating water pressure is low (switch)
Interlock
HP bypass valve open, open desuperheating isolating valve
HP bypass closes, interlock close desuperheating isolated valve
HP bypass closed, interlock close desuperheating control valve
Relief valve is close, desuperheating control valve is forbidden to open
LP bypass
Automatic opening
Turbine trip
Automatic closing
Condenser vacuum low ≤-70Kpa (2/3)
Condenser temperature high ≥70◦C
After-LP bypass valve temperature high ≥170◦C
LP bypass spray water pressure low
Interlock
LP Bypass open, open desuperheating control valve is open
LP Bypass control valve open, open desuperheating isolating valve
LP Bypass control valve close, close desuperheating isolating valve
Turbine
54
Lubricating oil pressure is low II (≤.0392MPa ≤.0392MPa Trip)
Over speed (DEH 3300rpm, TSI 3300rpm)
EH oil pressure is low II (≤7.8MPa ≤7.8 MPa Trip)
Bearing vibration is high (.25mm/s .127mm/s)
Vacuum is low (19.7 Kpa /14.7 KPa )
Displacement of axial direction is high (alarm +0.6mm,-1.05mm. trip +1.2mm,
-1.65mm)
Differential expansion of HP MP casing is high (alarm +6.2mm,-3mm. trip +6.2mm,
-3.2mm)
Differential expansion of LP casing is high (alarm +7mm,-6mm. trip +7.2mm, -6.2mm)
LPT Exhaust temperature is high (alarm 80◦C trip 120◦C)
Bearing temp is high (alarm 105◦C trip 115◦C)
Thrust bearing temp is high (alarm 100◦C trip 110◦C)
Trip in the control room
Local trip turbine
Boiler MFT
Main protection of generator acts
DEH fault.
55
Procedure of Latching and Rolling
Screen Status
Auto Control In message screen 1) Trip 2) Auto 3) All control valve closed
Solenoid
monitor All solenoids should be green ( Discharged )
Auto Control Click on ' LATCH' ( Gray )
Solenoid
monitor Solenoid 5, 6, 7 and 8 turn ' RED'.
Auto Control Check ' LATCH ' turned ' RED'
With above sequence Latching get completed. Now turbine ready to roll, If all parameters built up as per Turbine condition
Auto Control Click on ' SPEED RATE ' and give a value ( Exa.- 100 - 200 RPM/Minute)
Click on ' TARGET ' and give a value ( Exa- 500 RPM )
Auto Control Click on ' GO/HOLD ' and select 'GO' and watch the speed rise.
Then as per the Turbine temperature diffrence between top and bottom, Diffrencial Expansion,Bearing Vibration soak the turbine .
56
BLACKOUT CHECKLIST
57
AUTO SYNCHRONIZATION
: 1 /2
Operation task:generator Unit-1 voltage up through auto excitation; auto synchronization
ti
Seq. Operation Item √ m
e
一 safety measures
Implement operation supervision system strictly. The supervisor should be experienced operator or
1
above.
2 Wear insulation gloves and proper working tools.
3 The staff is both physically and psychologically well and familiar with the system.
二 operation measures
1 Rehearse the operation mentally.
2 Unit-1 Check the cooling water system of generator Unit-1 air cooler is working normally.
# 1 Check the rotation speed of turbine Unit-1 is steady. Maintain the rotation speed of the turbine be
3
the same with grid frequency.
Unit-1 Verify that generator transformer Unit-1 is put into service correctly.(only
4
one set of rotor earthing protection is to be put into service)
5 Close “power Ⅰto operation box 4QF”and “power Ⅱ to operation box 5QF”
Unit-1 “CH1” AVR ON” “REMOTE” Check AVR of generator Unit-1 excitation room(small) is
6 running at "CH1", "AVR ON" lamp is on and "REMOTE" lamp is off.
DCS # 1 “Excitation Launch” Click AVR Unit-1 on the DCS panel and enter its
7 interface. Close excitation suppression switch and take “Excitation Launch”.
8 Unit-1 Check the generator excitation system of Unit Unit-1 is put into service normally.
Unit-1 13.11kV 13.8*0.95Check the voltage of generator Unit-1 automatically rises to around 13.11kV.
9 13.8*0.95
10 “INC EXC” 13.8 kVUg=U(220KVg)×13.8/235
58
Use “INC EXC”button to increase the generator voltage to the rated value of 13.8kv;
(follow busbar voltage regulating and slightly higher than busbar voltage)
Ug=U(220KVg)×13.8/235
Unit-1 75.4v; 567.4A) Verify that 3 phases voltage of generator Unit-1 is balanced
11 and no-load excitation parameters such as voltage and current are correct.( compare
to no-load rated parameters 75.4v; 567.4A)
12 # 1 DCS Verify that there is no abnormal signal in generator Unit-1 protection
panel, excitation room and DCS.
13 “SELF” Confirm that synchronization select switch is at “SELF”position.
1 SWJ 2ZK Confirm that the SWJ power 22K of mazaic control panel #1 is already
14 closed and synchronization is put into service.
3 1MCB Confirm that the power MCB of synchronizing unit of mazaic control panel #3
15
is already closed.
16 4 STK "AUTO" Confirm "AUTO" is selected at mosaic control panel #4 STK.
4 ATRESIA(QK “Exit atresia” Confirm “Exit atresia” is selected at mosaic control
17
panel #4 ATRESIAQK
1 #1 1DL “CLOSE”
DCS 1DL “START” Change outlet breaker 1DL of generator transformer Unit-1 on mosaic control
18
panel Unit-1 over to “CLOSE”and put synchronization into service.(or click "START" at the interface
of DCS generator transformer outlet breaker 1DL to put synchronization into service)
59
DEH AUTO Control “sync” Check the interface of DEH AUTO Control and verify that
19
“sync”lamp is on (RED)
DEH AUTO Control “sync”,DEH Click "sync" in the interface of DEH AUTO Control to put
20
DEH synchronization into service.
DEH Check DEH to send synchronization permission signal and the synchronization meter
21
should be charged.
22 Manually adjust the generator frequency and voltage to be the same with those of grid system.
3 “START UP Press close button of auto sync "START UP" breaker on mosaic control panel
23
#3.
Verify that synchronization unit is working normally.(it automatically regulate the generator frequency and
24
voltage be the same with those of the grid system.
25 # 1 1DLVerify that the auto closing of generator Unit-1 breaker 1DL is normal. (Red lamp on)
26 # 1 Verify that the indication of stator 3-phases current is correct..
27 DEH “sync” Verify the DEH synchronisation request is cancelled.(“sync” becomes grey)
DCS 1DL “Exit” Click "EXIT" on the interface of DCS generator transformer outlet breaker 1DL to cancel
28
synchronization.
1 SWJ DEH Confirm the SWJ on the control panel 1 should be reset.(sync out and withdraw
29
from "request sync from DEH" signal)
# 1 1DL Confirm that synchronization of 1DL breaker of generator transformer Unit-1 is cancelled.(lamp of
30
synchronization meter dies)
4 MANUAL HANDLE(STK)开关选择"UNCHAN"
31
Select "UNCHAN" of MANUAL HANDLE(STK) switch on mosaic control panel #4.
# 1 A 屏 19XP Disconnect “19XP GENERATOR START\STOP EARTH FAULT” protection on
32
protection panel A of generator transformer Unit-1.
# 1 A 屏 28XP Disconnect “28XP ACCIDENTAL ENERGISATION RELAY” protection on protection
33
panel A of generator transformer Unit-1.
# 1 A 屏 31XP Disconnect “31XP FLASH OVER”protection on protection panel A of generator
34
transformer Unit-1.
# 1 A “4XB CLOSE MAIN VALVE I ” Put “4XB CLOSE MAIN VALVE I ” protection into service
35
on protection panel A of generator transformer #1.
# 1 A “23XB CLOSE MAIN VALVE II” Put “23XB CLOSE MAIN VALVE II” protection into
36
service on protection panel A of generator transformer #1.
# 1 B 19XP Disconnect “19XP GENERATOR START\STOP EARTH FAULT” protection on protection
37
panel B of generator transformer Unit-1.
# 1 B 19XP Disconnect “19XP GENERATOR START\STOP EARTH FAULT” protection on protection
38
panel B of generator transformer Unit-1.
# 1 B 31XP Disconnect “31XP FLASH OVER”protection on protection panel B of generator
39
transformer Unit-1.
40 Unit-1 Verify that generator Unit-1 is working normally. 60
# 1 B “4XB CLOSE MAIN VALVE I ” Put “4XB CLOSE MAIN VALVE I ” protection into service
41
on protection panel B of generator transformer #1.
# 1 B “23XB CLOSE MAIN VALVE II” Put “12XB CLOSE MAIN VALVE II” protection into
42
service on protection panel B of generator transformer #1.
Turbine Triping and Alarm
+1.2mm,-
1
Axial position 1.65mm (+0.6/-1.05) Auto
2 Shaft Vibration >0.25mm (>0.125mm) Auto
3 EH oil pressure low <7.8Mpa <12MPA Auto
4 Lube oil pressure low <0.0392Mpa <0.049MPA Auto
5 19.7Kpa
Vaccum of condenser low 14.4KPA Auto
6 TSI overspeed 3300 RPM 3240RPM Auto
7 DEH Over speed 3300rpm Auto
8 DEH Failure Auto
9 Boiler MFT action Auto
TURBINE TRIP
10 Electrical Generator and transformer protection Auto
11 Remote manual emergency shutdown Auto
12 Thrust Brg. Temp HI Auto
a.Thrst. Pad temp. >110 ºC >100 ºC Auto
b. Brg. Metal.temp.
>115 ºC >105 ºC
13 Auto
LP exhaust temp.HI >120 ºC >80 ºC Auto
14 Local manual emergency shutdown TURBINE TRIP
61
15 HIP Differential expansion +6.2mm/-3.2mm +6mm/-3mm Auto
16 LP Differential expansion +7.2mm/-6.2mm +7.2mm/-6mm Auto
17
Bearing cap vibration high 0.08mm Auto
18 >65 ºC
Bearing Drain Oil Temptreture
19 Main Steam Pressure High >16.4 MPAºC Manual
20 >30Um
Eccentricity of rotor
21 >0.13MPA&<0.02MPA
Pressure of Gland Seal
ALL CVs & ICVs AUTO CLOSE Over speed protection Control(OPC) act)
RESETS
62
COORDINATED MASTER CONTROL
In a Thermal Power Unit operation the critical internal unit parameters related to production are MW, Main steam pressure. The
critical external parameter is frequency of the network. In a boiler the steam production depends on combustion control (Fuel control
and Air flow control). So one of the unit parameters MW or main steam pressure must be used for Boiler control. Turbine Generator
produces electrical output (MW) proportional to steam input to turbine. The turbine control system (EHC) varies steam input to
turbine to achieve unit parameter MW or Main steam pressure. The network stability always depends on the balance of power
production and power consumption. Any unbalance in the power production and power consumption leads to change in the frequency
of operation in the direction of attaining natural stabilization i.e., balancing of power consumption with power production. However as
the capacity of this stabilization is limited for the network for stability, proportional frequency correction is given in turbine control
system to vary the power production in the direction to achieve stability of network. The 5% regulation used generally in thermal
power units, gives 100% load correction for 5% frequency disturbance in the network. This is selected mainly to achieve network
stability within the rotating machines speed variation of 95% to 105%. At 110% Turbo generators have over speed trip protection.
In a network the power production or power consumption can change due to several reasons like units tripping on some internal
problems or load breaker tripping. So to ensure the stability of network it is necessary to have frequency regulation in Turbine control
it is also to be emphasized here that if only few units in the network implement the frequency control the total disturbance in the
network will be passed on to the units having regulation by the many units which do not have regulation. Frequency is network
parameter which can not be controlled by few units in the network.
In Thermal Power Units the Turbines are fastly responding components and Boilers are having transport lag and Thermal inertia
and hence delayedly respond with variation in command. So the Turbine will be able to meet MW demand or main steam pressure set
value quickly by positioning the control valves of Turbine to the required values. Turbine will be able to maintain only one unit
parameter MW or main steam pressure. The other is to be controlled, naturally by the boiler. The modes of operating the unit are
named as turbine follow mode and boiler follow mode. In Turbine follow mode Turbine maintains throttle steam pressure. The MW
depends on the steam output from the Boiler. The variations in the Boiler steam output will be resulting variations in MW output.
Boiler steam output variations can result from changing Calorific values of coal etc. Turbine follow mode gives more stability to unit
by controlling main steam pressure perfectly and fastly which is a very important unit parameter. If Boiler combustion controls fuel
and air are in Auto corrective actions will be taken by boiler controllers to change combustion to give desired steam for the set MW.
63
These responses will be slow when compared to turbine responses. So it may be reemphasized that this mode of operation gives
maximum stability to unit operations with slow response to grid
Contd……….2/-
64
::02::
requirements by initiating combustion controls first and turbine valves positioning after steam production. However the combustion
controls will be responding to grid requirements if frequency influence in CMC console is in ‘ON’ position only.
In Boiler follow mode Turbine maintains MW demands and Boiler maintains main steam pressure. Turbine will be responding
to grid requirement fastly because of droop characteristic set in EHC and Boiler will be following to maintain main steam pressure if
combustion controls are in Auto. This mode of operation gives maximum stability to network because MW requirements are met by
Turbine fastly and lesser importance to unit stability, because the action by Turbine will be disturbing main steam pressure. If all units
in the network do not implement 5% regulation then the network disturbances will be passed on to the units in Boiler follow mode
disturbing their MW level of operation often. Boiler combustion controls must be kept in Auto in this mode of operation which will be
taking main steam flow and main steam pressure error as inputs for control. The main steam pressure is the final trimming signal to
boiler for boiler follow mode of operation. Response of Turbine to grid requirements is quickly perceived by boiler controls through
main steam flow variations. Finally Boiler controls ensure the set throttle pressure.
In coordinated mode of operation unit/master control station sets MW set point which will be pursued by combustion controls
by taking main steam pressure error as final trimming input signal. Turbine will be controlling the MW at the set point or changes in
grid frequency will be leading to changes in the MW. Main steam pressure error will have proportional influence for stability of the
unit. Boiler will be trying to control main steam pressure. Coordinated mode and boiler follow mode are similar in response except
that base signal required for boiler combustion control is MW set point in coordination mode and main steam flow signal in Boiler
follow mode.Sustained throttle pressure controller output will be the result due to calorific value deviation from design calorific value
and this output will be getting added to unit demand going to boiler master .the calorific value correction controller in auto mode takes
the output of throttle pressure controller as input and works as long time integrator to produce output to represent calorific value
which works as multiplier for fuel demand to boiler .In the process of this long time action, the throttle pressure controller output
returns to almost zero. The advantages in this control action are better transient response since the calorific value is as per actual
calorific value of coal going to the boiler and the throttle pressure controller has margins all the time on both positive and negative
sides.
Unit capability is capacity of the unit to produce the MW at that time. Unit capability signal depends on the number of
Auxiliaries in service and their contribution is expressed as MW signal which they can support. For example if six mills are required
to produce 500MW each mill capability will be taken as 85 MW approximately. The capability will be computed from each type of
Auxiliaries and minimum of all these will be the unit capability. On any running Auxiliary tripping, unit capability signal will be
dependent on the type of auxiliary tripped.
65
::03::
In Runback mode Boiler combustion controls give commands in proportion to unit capability and boiler will be coming to the state
of steady combustion and hence will be stabilizing. Turbine will be controlling main steam pressure as this will give maximum
stability to the unit. Runback mode gives highest stability to
unit because unit has gone to instability (ex.Mill/BFP/ID/FD tripped) this Runback mode gets selected automatically and ensures
stability. Whenever unit capability is less than unit master command the Runback mode sets in automatically.
The four modes of operation described above can be summarized in the following way.
Mode Boiler Controls Turbine Controls Input to Boiler Input to Turbine
Controls Controls
Turbine MW Pressure MW Set point Pressure error
follow (base signal)
MW error signal
Boiler Pressure MW Steam Flow MW error
follow (base signal)
Pressure error
Coordinated Pressure MW MW set point MW error
Mode (base signal)
Pressure error
Runback Produces steam Pressure Unit capability Pressure error
mode as per unit signal
capability (computed)
The Coordinated Master Control is written with a view to bring all concepts in it together to give a complete view of it.
Emphasis is given on concepts rather than on the CMC scheme.
66
67