Connections and Working Principles of Three-Phase Distribution Transformers - EEP
Connections and Working Principles of Three-Phase Distribution Transformers - EEP
distribution transformers
electrical-engineering-portal.com/three-phase-transformer-connections
Three-Phase Transformers
A three-phase service can be supplied by one three-phase transformer unit or by
interconnecting three single-phase transformer units. One three-phase unit is smaller than an
equivalent size bank consisting of three single-phase units.
One three-phase unit is easier to install because the polarity and interconnections between
the phases are fixed. The use of three single-phase units is common in overhead distribution.
When single-phase transformers are banked together, they can be interconnected to supply
more than one type of service. For example, three transformers with 120/24 V
secondaries can supply a 120/208, 240/416, or a 240 V three-wire service.
Fewer specialized emergency spare transformers are needed when single-phase
transformers are used.
Let’s start now with fundamentals of 3-phase distribution transformers and their
connections:
Go back to contents ↑
Spec #1 – The voltage rating of the transformer primary coil must be compatible with the
applicable circuit.
The voltage impressed across the primary coil will depend on whether the coil is connected
in a wye (phase-to-neutral) or a delta (phase-to-phase) configuration.
Spec #2 – The transformer must be able to deliver the needed secondary voltage. The
supplied secondary voltage will be dependent on:
Spec #3 – If equipped with tap changers, the transformers must be on the same voltage tap.
Dual-voltage transformers must be set on the proper voltage.
Spec #4 – The impedance of the transformers in the bank should be within 0.2 % of each
other to avoid having the transformer with the lowest impedance taking a greater share of the
load.
Go back to contents ↑
1. One way is to connect a coil between a phase and another phase. When each of the
three transformers has its coils connected between the phases AB, BC, and CA, the
transformers are interconnected in a delta configuration.
2. The second way is to connect a coil between a phase and the neutral. When each of
the three transformers has its coils connected between a phase and a common
neutral, the transformers are interconnected in a wye configuration.
Go back to contents ↑
Note how labeling the polarity of the transformers on a drawing reduces confusion when
making connections. Each transformer coil in a delta primary or delta secondary is connected
phase to phase.
When two or more transformers are interconnected in a delta configuration, the coils are
connected in series with each other. To connect a coil in series, each positive terminal of
one coil is connected to a negative terminal of another coil.
If a transformer primary is to be delta connected on a wye circuit, the voltage rating of the
primary coil must be equal to the phase-to-phase voltage of the circuit.
Figure 4 – Three types of delta connections
Go back to contents ↑
The three ways to connect a transformer primary into a wye (phase-to-neutral) configuration
are shown in Figure 5. Note how labeling the polarity of the transformers on a drawing
reduces confusion when making connections.
Each transformer coil in a wye primary or wye secondary is connected phase to neutral.
When two or more transformers are interconnected in a wye configuration, the coils are
connected in parallel with each other. To connect a coil in parallel, each positive terminal is
connected to a phase and each negative terminal is connected to a neutral.
Go back to contents ↑
Figure 6 shows the connections for a typical three-phase wye-wye transformer bank. A wye-
primary-wye-secondary transformer bank can supply 120/208 Vt, 240/416 V, 277/480 V, or
347/600-volt services. The phase-to-phase voltage is √3 or 1.73 times the phase-to-neutral
voltage.
The voltage across each transformer coil is equivalent to the phase-to-neutral voltage.
Go back to contents ↑
Figure 7 shows the connections for a typical delta-delta transformer bank. A delta-primary-
delta-secondary transformer bank supplies three-phase power at 120 V, 240 V, 480 V, or 600
V.
The voltage across each transformer secondary coil is equivalent to the voltage supplied to
the customer, which is the phase-to-phase voltage.
The load on a delta-delta transformer bank needs to be well balanced. Any unbalance will
result in circulating currents within the service as the unbalanced current tries to find its way
back to the source.
To ensure that the utility is supplying a balanced voltage to the customer, the three
transformers must have similar impedance and be on the same voltage tap.
Figure 7 – Delta-delta transformer bank
Go back to contents ↑
A wye-delta bank must have transformers with insulated H2 bushings. The H2 bushings are
interconnected to each other, but they are not connected to system
neutral or grounded. The neutral connection is left floating (ungrounded) and, therefore, can
have a high potential on it.
It must not be treated like a grounded neutral by anyone working on the transformer bank.
If the H2 bushings were connected to the system neutral, the transformer bank would carry
extra current not related to the current needed to supply the normal service load.
If the primary wye circuit is unbalanced, extra current flows through the delta secondary as it
tries to balance itself through the secondary of the transformer bank. If one phase on the
primary circuit is faulted to ground, the high unbalanced current flows through the delta
secondary.
When the H2 is connected to the system neutral, the transformer bank automatically
becomes a wye-open-delta transformer bank if one of the primary phases is opened.
The two energized transformers continue to provide three-phase power but are subject to
burnout because of overload. Two transformers now carry the load normally supplied by
three transformers.
This arrangement has a capacity of 57.7 percent of the capacity of three transformers.
Go back to contents ↑
Figure 9 shows the connections for a typical delta-wye transformer bank. A delta-primary-
wye-secondary transformer bank can supply standard wye services.
The secondary neutral should be well grounded because of the unavailability of a primary
system neutral.
Figure 9 – Delta-Wye transformer bank
Go back to contents ↑
Figure 10 shows the open-delta loop with the availability of three phases.
To feed an open-delta, three-phase secondary service, three primary wires are needed. A
wye primary would need two phases and a neutral, and a delta primary would need three
phases.
This hookup is sometimes used as an economical way to feed a small three-phase delta
load. One of the two transformers is often called the lighting transformer and is sized larger
in order to feed the single-phase portion of the load.
The smaller transformer is often called the power transformer and is there .to help provide
the three-phase load, typically a motor. A three-phase wye secondary service cannot be fed
from two transformers.
The customer should be told to reduce demand on service until the transformer is replaced,
because the two good transformers will now only have the capacity to supply 57.7 percent
of the capacity of three transformers.
Go back to contents ↑
4. Scott Connections
Scott-connected transformers provide two-phase power from a three-phase system. They
can also be used to supply three phases from a two-phase system. Two special single-phase
transformers are used.
Each single-phase transformer has three primary bushings and special taps on the primary
coil where the three-phase primary connections are made.
More about Scott-connected transformers you can find in this technical article.
Go back to contents ↑
More about connecting transformers in parallel you can find in this technical article.
Go back to contents ↑
There is no way a lines crew can switch secondary connections to allow these two
transformer banks to be connected in parallel.
There is no way a lines crew can switch secondary connections to allow these two
transformer banks to be connected in parallel.
Go back to contents ↑
7. Angular Displacement of Substation Transformers
Control-room operators have to be aware of the existence of a phase shift between different
feeders. A line fed from a substation, where the substation transformer is delta-wye, cannot
be connected in parallel with a line fed from a substation where the substation transformer is
wye-wye.
Similarly, lines from a delta-delta substation transformer cannot be connected in parallel with
a line from a wye-delta substation transformer.
To further add to the confusion, a wye-delta or delta-wye transformer bank can also be
connected so that there is a 180-degree phase shift in addition to the 30-degree phase
shift. A lines crew, therefore, should always check with operating control before closing a tie
switch between two feeders fed from different stations.
Phasing sticks can be used for a field test to determine if there is a voltage difference across
an open tie switch.
Go back to contents ↑
where the average V is the average of the three voltages and the max or min V are the
voltages that have the greatest difference from the average.
Go back to contents ↑