Check Maximum Shear Around Column Perimeter (PUNCHING SHEAR)

1) The document analyzes the punching shear capacity of a slab around a column. 2) It calculates the punching perimeter, column dimensions, slab thickness, reinforcement details, and applied load. 3) The calculated shear stress is found to be 0.301 N/mm2, which is less than the shear capacity of 0.6599 N/mm2, so no additional shear reinforcement is required.

Uploaded by

reynold
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
80 views4 pages

Check Maximum Shear Around Column Perimeter (PUNCHING SHEAR)

1) The document analyzes the punching shear capacity of a slab around a column. 2) It calculates the punching perimeter, column dimensions, slab thickness, reinforcement details, and applied load. 3) The calculated shear stress is found to be 0.301 N/mm2, which is less than the shear capacity of 0.6599 N/mm2, so no additional shear reinforcement is required.

Uploaded by

reynold
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

DEVELOPED BY : ROYCE AGA

PROJECT NAME : Rev.01: 2016


PROJECT LOCATION : Rev.02: 2017

Check Maximum Shear Around Column Perimeter (PUNCHING SHEAR)

U = punching perimeter (1.5d from face of the column)


Uo = Column Perimeter
d = Effective depth of Slab EXTRA BARS
Vu = Ultimate Column Load/Reactions Bar Diam = 0
Column b = 250 mm Spacing = 200
Column hc = 400 mm 0
Uo = 1300 mm 3.1416
ØDb = 6 mm 6.66667
Slab Thk h = 250 mm b
d = 227 mm hc
Vu = 275 KN (Ultimate)
Bar Spacing = 150
Bar Diam = 16 mmØ
Vu
As = 1340.416 mm²
fcu = 20.6 Mpa
fy = 248 Mpa

vmax = Vu < .8√fcu = 3.63 N/mm² (BS Code Sec 3.4.5.12)


Uod

vmax = 275,000 = 0.93 N/mm²


295,100

Calculated Shear Capacity,vmax = 0.93 < 3.63 N/mm² OK!!!

>>Thus, If OK, The slab thickness is adequate

Calculate Shear Stress at Shear Perimeter 1.5d from the column face

U = 4024 mm

v = V = 275000 = 0.301 N/mm²


Uxd 4024 x 227

Calculate Vc

Vc = 0.79 {100 As/bvd}^1/3 x (400/d)^1/4


Ym
Vc = 0.65985392

v = 0.301 < 0.6599 No Shear Reinforcement is required

clause 3.7.7.5 of the code for slabs over 200 mm thick.


if, vc<v≤ 2vc, shear reinforcement is required

Notes:
Input data in Blue caption
Don't erase any cell

Ref: Reinforced Concrete : Design Theory and Examples


3Rd Ed.
Bhatt, P.; MacGinley, T. J.; Choo, B. S.
DEVELOPED BY : ROYCE AGABAS
Rev.01: 2016
Rev.02: 2017

A BARS
mm
mm 5

Punching Perimeter

134041.6
227000
0.590492

400
227

fcu
25