Vent Pipe Sizing - UpCodes
Vent Pipe Sizing - UpCodes
The minimum required diameter of stack vents and vent stacks shall be determined fro
developed length and the total of drainage fixture units connected thereto in accordanc
Table 906.1, but in no case shall the diameter be less than one-half the diameter of the
served or less than 11/4 inches (32 mm).
TABLE 906.1 SIZE AND DEVELOPED LENGTH OF STACK VENTS AND VENT STACKS
TOTAL
DIAMETER MAXIMUM DEVELOPED LENGTH OF VENT (feet)a
FIXTURE
OF SOIL DIAMETER OF VENT (inches)
UNITS
OR WASTE
BEING
STACK
VENTED
(inches) 11/4 11/2 2 21/2 3 4 5 6 8
(dfu)
11/4 2 30
11/2 8 50 150 ‒ ‒ ‒ ‒ ‒ ‒ ‒
11/2 10 30 100
2 12 75 200
2 10 30 50 150 ‒ ‒ ‒ ‒ ‒
3 53 27 94 230 680
4 43 ‒ 35 85 250 980 ‒ ‒ ‒
10 4,000 31 78 310 9
10 7,200 24 60 240 7
10 11,000 ‒ ‒ ‒ ‒ ‒ ‒ 51 51 200 6
10 15,000 18 46 180 5
12 7,300 31 120 3
12 13,000 ‒ ‒ ‒ ‒ ‒ ‒ ‒ 24 94 3
12 20,000 20 79 2
12 26,000 18 72 2
15 15 000 ‒ ‒ ‒ ‒ ‒ ‒ ‒ 40 1
15 15,000 40 1
15 25,000 31
15 38,000 26
‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
15 50,000 24
a. The developed length shall be measured from the vent connection to the open air.
The diameter of individual vents, branch vents, circuit vents and relief vents shall be
not less than one-half the required diameter of the drain served. The required size
of the drain shall be determined in accordance with Table 710.1(2). Vent pipes shall
not be less than 11/4 inches (32 mm) in diameter. Vents exceeding 40 feet (12 192
mm) in developed length shall be increased by one nominal pipe size for the entire
developed length of the vent pipe. Relief vents for soil and waste stacks in buildings
having more than 10 branch intervals shall be sized in accordance with Section
908.2.
The developed length of individual, branch, circuit and relief vents shall be
measured from the farthest point of vent connection to the drainage system to the
point of connection to the vent stack, stack vent or termination outside of the
building.
Where multiple branch vents are connected to a common branch vent, the common
branch vent shall be sized in accordance with this section based on the size of the
common horizontal drainage branch that is or would be required to serve the total
drainage fixture unit load being vented.
Sump vent sizes shall be determined in accordance with Sections 906.5.1 and
906.5.2.
Drainage piping below sewer level shall be vented in the same manner as that
of a gravity system. Building sump vent sizes for sumps with sewage pumps or
sewage ejectors, other than pneumatic, shall be determined in accordance
with Table 906.5.1.
No No
10 No limitb No limit No limit No limit
limit limit
No No
20 270 No limit No limit No limit
limit limit
No No
40 72 160 No limit No limit
limit limit
No No
60 31 75 270 No limit
limit limit
No No
80 16 41 150 380
limit limit
No No
100 10c 25 97 250
limit limit
Not No
150 10c 44 110 370
permitted limit
Not Not No
200 20 60 210
permitted permitted limit
Not Not No
250 10 36 132
permitted permitted limit
Not Not
300 10c 22 88 380
permitted permitted
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785
L/m.
The air pressure relief pipe from a pneumatic sewage ejector shall be
connected to an independent vent stack terminating as required for vent
extensions through the roof. The relief pipe shall be sized to relieve air
pressure inside the ejector to atmospheric pressure, but shall be not less than
11/4 inches (32 mm) in size.
one-half the required diameter of the drain served. The required size of the drain shall be
determined in accordance with Table 710.1(2). Vent pipes ...
Plumbing Code 2015 of Utah > 9 Vents > 906 Vent Pipe Sizing
Section P3113 Vents, Vent Pipe Sizing
diameter of the drain served. The required size of the drain shall be determined in
accordance with Chapter 30. Vent pipes shall be not less than 1 1 / 4 ...
Residential Code 2015 of Utah > 31 Vents > P3113 Vent Pipe Sizing
or less than 1 1 / 4 inches (32 mm). TABLE 906.1 SIZE AND DEVELOPED LENGTH OF STACK
VENTS AND VENT STACKS DIAMETER OF SOIL OR WASTE ...
Plumbing Code 2015 of Utah > 9 Vents > 906 Vent Pipe Sizing > 906.1 Size of Stack Vents and Vent Stacks
The developed length of individual, branch, circuit and relief vents shall be measured from
the farthest point of vent connection to the drainage ...
Plumbing Code 2015 of Utah > 9 Vents > 906 Vent Pipe Sizing > 906.3 Developed Length
Where multiple branch vents are connected to a common branch vent, the common branch
vent shall be sized in accordance with this section based ...
Plumbing Code 2015 of Utah > 9 Vents > 906 Vent Pipe Sizing > 906.4 Multiple Branch Vents