C & R Panel PDF

The document provides equipment specifications for the control and relay panel of a 220/33kV substation. It outlines requirements for the construction, wiring, components, and functions of the control and relay panel. Key points include that the panel will be floor mounting and dust/moisture proof. It will include terminal blocks, wiring, mimic diagrams, annunciators, and instruments to monitor and control the substation equipment. The panel will also include protection relays and auxiliary relays for transformer monitoring.

Uploaded by

DipaNshu Dipz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
237 views

C & R Panel PDF

The document provides equipment specifications for the control and relay panel of a 220/33kV substation. It outlines requirements for the construction, wiring, components, and functions of the control and relay panel. Key points include that the panel will be floor mounting and dust/moisture proof. It will include terminal blocks, wiring, mimic diagrams, annunciators, and instruments to monitor and control the substation equipment. The panel will also include protection relays and auxiliary relays for transformer monitoring.

Uploaded by

DipaNshu Dipz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Equipment Specifications NIT of 220/33kV Substation at Gevra OCP

10‐ Temperature Rise Test Measurements shall be made with the Fiber Optic
Thermometers. The equipment shall be operational during temperature tests
and be demonstrated during these tests. During probe verification, the hottest
probes for each phase shall be identified, and temperature data for all probes
recorded and reported in the test report.

2.4.8.0 SPECIFICATIONS OF CONTROL AND RELAY PANEL

2.4.8.1 General Requirements

i) The control/relay panels (CR panel) shall be simplex type suitable for
indoor installation. The cubicles shall be free-standing, floor mounting
type, and shall be made of rigid structural frames enclosed completely
with specifically selected, smooth finished rolled sheet steel of
thickness not less than 3 mm (min.) for front of control panels and 2.5
mm (min) for sides, top and bottom portions as well as doors. There
shall be sufficient reinforcement to ensure level surfaces, resistance to
vibration and rigidity during transportation, installation and operation.
The cubicles shall be vermin, dust and moisture proof and shall provide
degree of protection not less than IP: 31 as per IS: 12036.

ii) All sheet steel works shall be properly phosphated and treated as per
the relevant standards. The cubicles shall be finally painted by powder
coating process or by oven baking process. The colour shade for final
paint shall be Light Grey to shade no. 631 as per IS-5 for both interior
and exterior surfaces.

iii) The General Arrangement and constructional details, as also the


mounting arrangement of different equipment on the control and relay
panels shall be as per standard practices in similar EHV substations.
The schematic/ wiring diagrams shall be in line with standard wiring
diagrams. These drawings shall be furnished by the successful
Tenderers along with the offer.

iv) All wiring shall be carried out with 660 V grade single core multi-strand
flexible copper conductor wires with PVC insulation. Colour coded
wires shall be used for CT/PT circuits. Wiring troughs shall be used for
routing the cables. Ferrule numbers shall be provided at both ends of
cable and the ferrule numbering shall correspond to the numbering in
the approved schematic drawings.

v) Terminal blocks shall be 660V grade, 10 Amps rated, one-piece


mounted type, complete with insulated barriers, stud type brass
terminals, washers, brass nuts and identification strips. Markings on
the terminal strip shall conform to the terminal numberings on the
approved wiring diagram. Terminals meant for CT and PT supplies
shall be provided with disconnecting type terminals, and having
shorting facility for CT circuits. The terminals meant for bus-wiring
shall be provided at the top.

RI –5 CMPDI Job No.503256 (VOL –II) Page no- 106


Equipment Specifications NIT of 220/33kV Substation at Gevra OCP

vi) The overall dimensions of the control and relay panel shall be suitably
and appropriately designed by the Tenderer. The relay panels shall be
modular rack-mounting type in accordance with relevant standards.
The protective relays shall be drawout / plug in type as far as possible.
Non-draw out type relays and ancillary components like switches,
lamps etc. wherever required in protection circuits shall be installed on
plates suitable for mounting in racks.

vii) All front mounted as well as internally mounted equipment shall be


provided with individual labels having equipment designation engraved
on. Metal photo-printed anodized aluminum plates or PVC strips duly
engraved (white lettering in black background) shall be used for labels.

viii) All control switches and instrument switches shall be rotary type, with
escutcheon plates clearly marked to show the operating positions.

ix) Semaphore indicators with mimic diagram shall be provided for actual
status indication (ON/OFF) of isolators and circuit breakers.

x) Mimic diagrams depicting the bus-bar arrangement shall be provided


on the control panel. These shall be painted (overlaid) type or screw-
on type aluminum strips. The mimic shade shall be as follows:

a) 220 kV - Dark brown to shade no. 412 as per IS:5

b) 33 kV - Brilliant green to shade no. 221 as per IS:5

c) Earth - Black

xi) Static annunciators suitable for visual and audible alarm annunciation
shall be provided on the control panel. Annunciator fascia units shall
have translucent plastic windows for each alarm point. Annunciator
shall be provided with Accept/Reset/Lamp test push buttons. One bell
for trip alarm and one buzzer for non-trip alarm shall be provided for
each annunciation scheme. Visual alarm shall continue to glow till the
abnormality is cleared. Provision for testing of healthiness of visual &
audio alarm shall be provided.

xii) It shall be ensured that spurious/nuisance alarm does not occur due to
influence of external magnetic field or switching disturbances from
neighboring circuits within the panel.

xiii) Auxiliary supply available for the C&R panels will be as follows:

a) Main DC -110 V with variation (-15%) to (+10%) :


for control, indication, relays, trip etc.

RI –5 CMPDI Job No.503256 (VOL –II) Page no- 107


Equipment Specifications NIT of 220/33kV Substation at Gevra OCP

b) AC supply -240V, single phase & 415V, 3 phase 50 Hz, with


voltage variation (-5%) to (+5%) and frequency variation (+/- )3% :
for cubicle lighting, space heaters, power plug etc.

xiv) All the indicating instruments shall be of suitable. size. All 220
kV and 33 kV meters shall be digital microprocessor based power
meters for various data display with memory for storing data. Meters
shall be provided with TTB (Testing Terminal Board). The meters shall
have long life and reliability. For this supporting literatures and test
certificates shall be provided with the offer.

2.4.8.2 Special Requirements

i) Contact multiplication relays if required for multiplication of auxiliary


contacts of breaker and isolator, a single latch relay (electrically
operated type) having N/O and N/C contacts as per the scheme
requirement may be provided for breaker/isolator. These relays shall
be mounted on a frame inside the respective control panel, and shall
be accessible after opening the rear doors.

ii) In transformer relay panels, auxiliary relays (self reset type with hand
reset flags) shall be provided for supervisory functions of transformer
buchholz, WTI, OTI, etc.

iii) In the control and relay panels, separate fuses are to be provided for
various sub-circuits, as per standard practices. Each of these fuses
shall be supervised using suitable auxiliary relays and an alarm shall
be sounded when failure of any fuse takes place. The DC supervision
scheme is to be suitably designed so that failure of 110V DC supply will
be announced through a hooter and indicating lamp.

iv) 220kV/33 kV transformers shall be provided with biased differential


protection and earth fault protection. The relay shall have adjustable
bias setting, and shall be immune to magnetizing in rush currents, but
shall operate correctly for internal faults. The relays shall be suitable
for 2-winding transformers.

v) Each control panel shall have individual fire extinguisher inside the
panel with auto sensor.

vi) The control panel shall be electronic circuit based.

RI –5 CMPDI Job No.503256 (VOL –II) Page no- 108