AC Thermal Load Calculation
AC Thermal Load Calculation
Ser. Cooling Capacity Air Flow Rate 2 CU 02 47.4 161.7 123.2 VRV OR VRF 1 16 WORKSHOP GROUND FLOOR G ( 11:16 )
Description Input Power
No. QTY ( KW ) SERVICE AREA Notes GENERAL NOTES :
KW TMBH SMBH CFM
NOTES:
1 G -1 5.6 19.1 14.6 572 1 0.2 PAINT STORE 1.
2. COOLING CAPACITIES OF UNITS ARE SELECTED ON COIL TEMPERATURE AT 76 F DB / 63 F WB.
2 G-2 3.6 12.3 9.4 335 1 0.2 ELEC. ROOM 3. THE CONTRACTOR SHALL BE SIZED THE REFRIGERANT PIPING ACCORDING TO MANUFACTURER'S
RECOMMENDATION AND ACTUAL UNIT LOCATION.
4. ELECTRICAL DATE OF THE UNIT 3 / 415 / 50 OR ACCORDING TO MANUFACTURER'S RECOMMENDATION
3 G-3 2.2 7.5 5.7 200 1 0.2 STORE 5. REFRIGERANT TO BE ECO FRIENDLY PREFERRED R410A.
LEGENDS :
SPLIT DUCTED UNITS SCHEDULE ( INDOOR UNIT GROUND FLOOR ) SCHEDULE OF CONDENSING UNITS:
Ser. Cooling Capacity Air Flow Rate Ser. Cooling Capacity
Description Input Power Description Input Power
No. QTY ( KW ) SERVICE AREA Notes No. TYPE QTY ( KW ) SERVICE AREA INDOOR UNITS
KW TMBH SMBH CFM KW TMBH SMBH
1 M - ( 01:05 ), 10 7.1 24.2 18.5 720 6 0.2 1 CU 03 60.3 205.7 156.8 VRV OR VRF 1 22 WORKSHOP FIRST FLOOR M ( 1:10 )
NOTES: This document contains CONFIDENTIAL and PROPRIETARY information of ALTORATH. This
1) E.S.P FOR THE FAN TO BE CALCULATED BY THE CONTRACTOR. information is not to be used, disclosed or reproduced in whole or in part to anyone outside of
ALTORATH and subsidiaries, except pursuant to a written agreement with ALTORATH
2) ALL EXTRACT FAN SHOULD HAVE STATUS MONITORING PANEL CONNECTED TO BMS
SYSTEM WITH LIGHT INDICATION AND SOUNDER. PROJECT :
(WORKSHOP)
REV. SCALE:
DRAWING NO.
EE-04-101 N.T.S
SHEET:
00 A1