0% found this document useful (0 votes)
110 views

Subject: External Static Losses Summary: Al-Diyar Consultants

The document provides calculations of the external static pressure losses for 3 air handling units (AHUs) in a building. For each AHU, it calculates the supply and return duct static losses based on duct length and fittings. Additional static losses from components like sound attenuators and dampers are also included. A 10% factor of safety is applied to determine the total external static pressure required for each AHU, which ranges from 180Pa to 185Pa for AHU-01 and AHU-02, and 175Pa for AHU-03.

Uploaded by

Fasil E
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views

Subject: External Static Losses Summary: Al-Diyar Consultants

The document provides calculations of the external static pressure losses for 3 air handling units (AHUs) in a building. For each AHU, it calculates the supply and return duct static losses based on duct length and fittings. Additional static losses from components like sound attenuators and dampers are also included. A 10% factor of safety is applied to determine the total external static pressure required for each AHU, which ranges from 180Pa to 185Pa for AHU-01 and AHU-02, and 175Pa for AHU-03.

Uploaded by

Fasil E
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

AL-DIYAR CONSULTANTS

Made by Date : :MAY-2011 Project MOI- 2110


Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 01 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 49.6 + 24.8
= 74.4 MT
Supply duct static losses = Total equ. length x D P/M
= 74.4 x 0.49
= 36.456 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 161.456 PA


Adding 10% factor of safety = 16.1456 PA
Total supply external static losses = 177.6016 PA

SAY 180 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 19.3 + 9.65
= 28.95 MT
Return duct static losses = Total equ. length x D P/M
28.95 x 0.49
14 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

Additional return duct static losses = 100 PA

Total external static losses = 114 PA


Adding 10% factor of safety = 11 PA

2111-JAZAN HAIE AL SWAES


Total return external static losses = 126 PA

SAY 130 PA

AL-DIYAR CONSULTANTS
Made by Date : :MAY-2011 Project MOI- 2110
Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 02 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 49.4 + 24.7
= 74.1 MT
Supply duct static losses = Total equ. length x D P/M
= 74.1 x 0.571
= 42.3111 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 167.3111 PA


Adding 10% factor of safety = 16.73111 PA
Total supply external static losses = 184.0422 PA

SAY 185 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 14.4 + 7.2
= 21.6 MT
Return duct static losses = Total equ. length x D P/M
21.6 x 0.571
12 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

2111-JAZAN HAIE AL SWAES


Additional return duct static losses = 100 PA

Total external static losses = 112 PA


Adding 10% factor of safety = 11 PA
Total return external static losses = 124 PA

SAY 125 PA

AL-DIYAR CONSULTANTS
Made by Date : :MAY-2011 Project MOI- 2110
Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 03 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 31.4 + 15.7
= 47.1 MT
Supply duct static losses = Total equ. length x D P/M
= 47.1 x 0.653
= 30.7563 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 155.7563 PA


Adding 10% factor of safety = 15.57563 PA
Total supply external static losses = 171.3319 PA

SAY 175 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 6 + 3
= 9 MT
Return duct static losses = Total equ. length x D P/M
9 x 0.653
6 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA

2111-JAZAN HAIE AL SWAES


2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

Additional return duct static losses = 100 PA

Total external static losses = 106 PA


Adding 10% factor of safety = 11 PA
Total return external static losses = 116 PA

SAY 120 PA

AL-DIYAR CONSULTANTS
Made by Date : :MAY-2011 Project MOI- 2110
Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 04 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 30.7 + 15.35
= 46.05 MT
Supply duct static losses = Total equ. length x D P/M
= 46.05 x 0.735
= 33.84675 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 158.84675 PA


Adding 10% factor of safety = 15.88468 PA
Total supply external static losses = 174.7314 PA

SAY 175 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 6 + 3
= 9 MT
Return duct static losses = Total equ. length x D P/M
9 x 0.735

2111-JAZAN HAIE AL SWAES


7 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

Additional return duct static losses = 100 PA

Total external static losses = 107 PA


Adding 10% factor of safety = 11 PA
Total return external static losses = 117 PA

SAY 120 PA

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 01 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 02 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 03 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 04 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


2111-JAZAN HAIE AL SWAES