Papers and Summaries On Stator Earth Fault Protection
Papers and Summaries On Stator Earth Fault Protection
Undetected Earth fault may result in 1. Loss in operating Revenue 2. Millio-ns in damage. 3.
Generators are critical in power systems, they supply power to all energy consuming
machines.
Maintainance dependent on the size and complexity of the alternator.
Generator needs to be sent for rewinding.
Protection system ought to be robust so that it does interrupt the system for minor faults but
should be sensitive enough to detect a range of faults.
Coil inter turn to short circuit(not phase to earth)?
Protective relay—device that detects faults and triggers a circuit breaker to isolate the
defective element/ area. Measures electrical quantities and measures there from their normal
values.
Possible solutions
a) Differential protection.
Uses the flow of current for fault detection. Under normal conditions the
current flowing at two ends is equal but under fault these currents differ.
The difference between the current is directed to flow in the relay coils and
thus at an adequate difference the coils energise and trip circuit braker. This
is called the merz price circulating current system.
Limitation: Fault current is limited by the neutral line resistisatnce.
When the fault occurs near to the neutral the current that flows is very small
and not sufficient to trip breaker/energise the relay colis. Only protects 80 to
85% of the stator winding. So one could utilise a relay with low
setting(meaning that will trip breaker at this small currents but this dies not
provide the desired stability).
b) Modified differential protection
As an alternative to the merz price method one may utilize the modified
differential protection method.
Protects a greater portion of the of the stator windings.
c) 100% stator winding protection
Low frequency signal is injected into the secondary winding of the grounding
transformer.
The voltage signal is first passed through a low pass filter.
Machine is protected is even when the machine is offline.
Relay measures current on the grounded wire of the secondary side of the
grounding transformer. This current increases during faults.
For a special case of grounding capacitance and neutral resistance the relay
ought to a component inside that acts specifically on the real part of the
current.
For fault and non-fault conditions the power relay shows a significant
difference in power. So a power relay would be a very good option even at
high reactance and winding resistance values.
d) Power relay
e) Using the real component of the current resulting from low harmonic injection to
decide on fault and non-fault conditions. This is necessary for the conditions when the
grounding capacitance between the phase and grounding is very large for a
corresponding small grounding transformer resistance. The difference between the
neutral line current for fault and non-fault conditions becomes to small and makes it
very hard to set the relay pickup value. As alternative to a relay that uses the current
value to decide whether to initiate action employ (d).
Criteria for comparing methods: Sensitivity, speed, security, availability, complexity and
setting considerations.
NEMA(National Electrical Manufacture Association) does not allow fault currents to exceed
the fault current generated by a 3 phase fault in “standard generators”. Thus to limit the fault
current generated by the single phase to fault an impedance is required at the neutral line in
order to maintain the integrity of the stator windings.
High impedance grounding of transformer as a middle ground of two extremes of the solid
grounded and ungrounded.
The distribution transformer transforms the small resistance connected across it’s secondary
to a high value resistance in the primary side which is between the neutral and ground.
The charging current of the capacitance to ground(between line and ground) during a fault is
dependent of the distribution transformer 𝑘𝑉𝐴 rating as well as the distribution transformer
resistor.
So the resistor is selected such that the current in the transformer primary windings during
an EARTH FAULT matches the current in the capacitance. Also helps avoid ferroresonance.
Several harmonics are produced by the generator, but the protective element utilises the
fundamental to detect the fault and attenuate other harmonics.
Big concerns as coverage changes considerably at start up and shut down. Look reference 8.
Harmonic voltages are created in the phases of the generator in normal operating conditions
due to the limitations of the physical design of the machines.
METHODS: