0% found this document useful (0 votes)
751 views1 page

AVR sps-101

This document provides specifications and technical details for an AVR model SPS-101 voltage regulator. It describes the alternator connections for 3-phase 415V and 1-phase 220V configurations. It also explains the functions of various pots on the AVR board, including those for voltage adjustment, stability, under-frequency roll-off, and over-excitation protection. Instructions are given for setting or adjusting these pots based on the application.

Uploaded by

Sunil Sanga
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
751 views1 page

AVR sps-101

This document provides specifications and technical details for an AVR model SPS-101 voltage regulator. It describes the alternator connections for 3-phase 415V and 1-phase 220V configurations. It also explains the functions of various pots on the AVR board, including those for voltage adjustment, stability, under-frequency roll-off, and over-excitation protection. Instructions are given for setting or adjusting these pots based on the application.

Uploaded by

Sunil Sanga
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SPECIFICATIONS & TECHNICAL DETAILS OF AVR MODEL SPS-101

VOLT:
3 PHASE 415 V Rotate these pot clockwise to increase AC terminal voltage and anticlockwise to decrease
ALTERNATOR CONNECTIONS AC terminal voltage.
STAB:
Stability potentiometer is factory set such that optimum response of voltage recovery is achieved
during sudden load changes. In some cases in order to release burden on engine it is required to
sluggish the recovery time of voltage, therefore to increase the response time STAB potentio-
meter is carefully rotated anti clock wise direction such that response time will increase resulting
Remove link to larger dip in terminal voltage during sudden load. Kindly note that by excessively rotating STAB
connect remote potentiometer to clock wise direction at one stage voltage will become unstable and cause hun-
potentiometer - 1 K ting. Again by gradually rotating the STAB pot to i clock wise direction will stabilize the generator
voltage. ( It is advisable that only technically qualified person should adjust these pot.)
UFRO:
Link for 415 V The under frequency roll off ( UFRO ) is factory set at 47 Hz for 50 Hz generator. In case if it
Sensing is required to set UFRO level for 60 Hz generator than remove 50/60 Hz link to set at 57 Hz.
Under frequency activation is indicated by UFI LED. Additionally a UFRO potentiometer is
provided on AVR if UFRO level is requred to set between frequency range from 45 Hz to 59
Hz.. Rotating UFRO potentiometer clock wise direction will set UFRO level in increasing
frequency direction and rotating in anti clock wise direction will set to decreasing frequency.
OE:
Excitation field voltage exceeding its specified limit indirectly indicates alternator over
load. AVR has in built accurate excitation voltage sensing circuitry to protect alternator
windings from over load. DC field voltage monitored by AVR circuitry will cut off field
U V N F1 F2 supply after 20-25 seconds when field voltage exceeds preset value. The over excita-
tion trip level is factory set to maximum 95 V DC. It will be required to set trip level by
user as specified by excitation voltage on alternator name plate. The OE potentiometer
is factory set to fully clock wise direction. By rotating the potentiometer to anti clock
wise direction will set DC voltage trip level from maximum to downwards to 0 V DC.
Vice versa rotating OE potentiometer to clock wise direction will set trip level from 0 V
upwards to maximum. In order to set to set trip level apply full load on generator and
then rotate OE potentiometer anti clock wise direction till OE LED turns ON. Once OE
U LED turns ON the timer will be activated and after 20-25 seconds field supply will be
cut off. Tripping will be indicated OEI indicator LED.
TO LOAD

V ACG
415 V
W
N EXC. FIELD Remove link to
connect remote
potentiometer - 1 K
Link for 220 V
Sensing

CONNECTING ISOLATED AUXILIARY


INPUT TO AVR FOR 415 V SENSING.

1 PHASE 220 V
ALTERNATOR U V N F1 F2
Remove link to
CONNECTIONS
connect remote
potentiometer - 1 K

Link for 415 V


P
Sensing
TO LOAD

1 PHASE
ACG
N 220 V

EXC. FIELD

SPECIFICATIONS:
U V N F1 F2 2 Phase(415 V) + N for 3 Ph. Alternator
INPUT VOLTAGE 1 Phase(230 VAC)+ N for 1 Ph. Alternator.
SENSING VOLTAGE 415 or 230 V AC ( Link Select )
OUTPUT EXCI. VOLTAGE 100 V DC
OUTPUT EXCI. CURRENT 6 A DC.
FIELD OHMS MINIMUM 12 OHMS
INPUT FREQUENCY 50 / 60 Hz
RESIDUAL BUILD UP 2 V AC AT 50 Hz.
VOLTAGE REGULATION +/- 1 %. Thermal drift 0.04 %per deg C
U
TO LOAD

FACTORY SETTING 47 Hz,


V ACG UNDER FREQUENCY
FOR 60 Hz REMOVE 50/60 Hz LINK.
415 V (UFRO / UFI )
W INDICATION BY UFI - LED
N Auxiliary EXC. FIELD 10- 25 SECONDS DELAY TIMER.
Winding OVER EXCITATION ADJUSTABLE POT RANGE 0 - 90V DC.
VOLTAGE TRIP INDICATION BY OEI - LED
( OE SET / OEI LED) (Factory setting to max )
WARNING: To prevent personal Injury or equipment damage only qualified
technician / operator should install, operate or service this device 20-100Hz 50 mm/sec
VIBRATION
CAUTION: While using meager & high potential equipment, disconnect all 100Hz - 2 Khz 3.3g
connections of AVR. Incorrect use of such equipments could damage OPERATING TEMPERATURE -20 TO +70 C
components of AVR
STORAGE TEMPERATURE -40 TO +80 C
RELATIVE HUMIDITY 0 TO +70 C : 95 %
NOTE: Continuous development of our products entitles us to change FUSE ( FAST ACTING) 6.3 AMPS ( SIZE: 20 X 5 mm)
specifications& other details without notice. Please contact factory for
latest information ( [email protected] ) DIMENSIONS (L X B X H) 106 X 70 X 35 mm
WEIGHT 240 gms

You might also like