Air Handling Unit
Air Handling Unit
cac.midea.com global.midea.com
Note: The data in this book may be changed without notice for further improvement
2015 JV with Carrier in China in chiller field, BOSCH in VRF production and Siix in smart control
2014 Launched the All DC Inverter V5X globally
2013 Launched the super high efficiency centrifugal chiller with full falling film technology
2012 Formed Midea-Carrier JV.Company in India and HK and entered the lighting field .
2011 Launched the third generation of AHU&MAHU
2010 Built the 3rd manufacturing base in Hefei
2008 Launched the second generation of AHU&MAHU
2006 Launched the first generation of AHU&MAHU Midea Company Midea CAC
Introduction Introduction
2004 Acquired MGRE entered the chiller industry, launched the world's first
digital scroll air-cooled heat pump module unit and JV with Toshiba Carrier
2001 Cooperated with Copeland to develop the digital scroll VRF system
2000 Developed the first inverter VRF with Toshiba
1999 Entered the CAC field
Air Handling Unit
Suspended AHU
2,000m3/h ~ 15,000 m3/h
(1,200CFM ~ 8,800CFM)
Horizontal AHU
Contents
5,000m3/h ~ 40,000 m3/h
(3,000CFM ~ 24,000CFM)
Vertical AHU
3,000m3/h ~ 40,000 m3/h 05 Air Handling Unit
(1,800CFM ~ 24,000CFM)
23 Modular Air Handling Unit
49 Installation
50 Reference Projects
03 04
Air Handling Unit
the requirements of all kinds of space cooling and heating, such as office buildings, shopping malls, exhibition halls, airports, Unit Structure
W: Horizontal;
L: Vertical;
railway stations, hotels, factories and any other central air-conditioning systems. D: Suspended
Midea AHUs have been widely used in most part of the world for a couple of years. Now, the 3rd generation AHU has been Air Flow Rate, x1,000m3/h
Midea Air Handling Unit
launched to provide you with more comfortable and convenient. It adapts unitary structure design, more outstanding
cold-bridge free performance, lower air leakage and more elegant appearance. There are 3 types - suspended type, horizontal Orientation
type and vertical type, including 66 standard models, and the air flow rate is available from 2,000m /h to 40,000m /h. Different
3 3 Air inlet
Unit handling orientation is determined by location of pipe
external static pressure (ESP) can be customized to meet different kinds of applications.
connection while facing unit in the direction of air flow. The unit below
is left-handed connection unit, otherwise is right-handed connection
unit.
Air outlet
Left-handed unit
05 06
Air Handling Unit
07 08
Air Handling Unit
Drain pan
The cooling coil is installed on reversed U-shaped support plate. Standard galvanized drain pan is coated to inhibit the growth of
Air dampers
algae and fungi. 10mm insulation is provided between the drain pan and the bottom panel. Stainless steel drain pan is optional. Air dampers in AHUs are optional. Aerodynamically designed damper
blades have built in high quality bearings. Blade edges are lined with
Filter sealing strip to restrict leakage to an absolute minimum. Air damper
blades are either linked to give parallel turning operation or gear set to
give opposing direction. The dampers are tested to yield linear control
Filter is aluminum alloy frame structure. Primary efficiency plate type filter
is designed as standard. The structure of filters are stable and firm, high characteristic.
strength and intensity, washable and easy changing. Filter can be
unloaded and loaded from both left and right side.
09 10
Air Handling Unit
Note: Return air condition: cooling, air inlet 27°C DB/19.5°C WB, entering water temp. 7°C, water temp. difference 5°C; Note: Return air condition: cooling, air inlet 27°C DB/19.5°C WB, entering water temp. 7°C, water temp. difference 5°C;
Heating, air inlet 21°C DB, entering water temp. 60°C, water temp. difference 10°C. Heating, air inlet 21°C DB, entering water temp. 60°C, water temp. difference 10°C.
Note: Fresh air condition: cooling, air inlet 35°C DB/28°C WB, entering water temp. 7°C, water temp. difference 5°C; Note: Fresh air condition: cooling, air inlet 35°C DB/28°C WB, entering water temp. 7°C, water temp. difference 5°C;
Heating, air inlet 7 °C DB, entering water temp. 60°C, water temp. difference 10°C. Heating, air inlet 7°C DB, entering water temp. 60°C, water temp. difference 10°C.
11 12
Air Handling Unit
Vertical type
24
4R 22.8 39.9 1.09 52 1.1 58.2 150/192 M M
G
04L 4000 160 580×1050×1250 730×1300×1440 K
6R 29.3 45.1 1.40 62 1.1 60.3 162/204
4R 28.3 47.5 1.4 20 1.1 60.5 170/235
05L 5000 160 630×1110×1420 780×1360×1610
6R 36.6 56.4 1.7 40 1.5 61.2 185/250
H
J
E
N
4R 34.6 58.8 1.7 25 1.5 61.4 190/263
06L 6000 160 630×1200×1470 780×1450×1660
6R 44.1 67.7 2.1 54 1.5 61.9 210/283
S
4R 50.8 73.1 2.4 31 2.2 63.2 230/330
08L 8000 200 740×1350×1650 890×1600×1840
6R 59.1 90.2 2.8 42 2.2 63.6 255/355
D
4R 58.9 99.3 2.81 30 3 64.5 250/362
10L 10000 240 740×1410×1800 890×1660×1990 W+150
6R 74.6 112 3.6 58 3 65.4 290/402
4R 91 131.3 4.3 36 5.5 67.6 360/500 Drain pipe Y Water inlet X
15L 15000 240 740×1940×1880 960×2190×2070 F
6R 107 169 5.1 33 5.5 68.4 410/550
4R 113.7 183.4 5.4 28 7.5 70.5 480/675
20L 20000 280 860×2420×1980 1080×2670×2170
6R 149 224 7.1 59 7.5 71.2 540/735 50
4R 149.3 248.9 7.1 34 7.5 70.7 620/865
25L 25000 320 960×2790×2160 1180×3040×2350
6R 187 279 8.9 64 7.5 71.3 680/925
4R 179.2 298.7 8.6 53 11 73.1 690/950
30L 30000 320 960×2790×2360 1180×3040×2540
6R 225 335 10.8 69 11 73.5 760/1020
L
4R 209.1 348.4 10.0 40 11 73.6 780/1080
35L 35000 370 1000×3200×2360 1220×3450×2540
6R 265 391 12.7 67 15 74.2 860/1160
4R 238.9 398.2 11.4 41 15 76.2 850/1165 35
40L 40000 370 1000×3400×2360 1220×3650×2540
6R 300 447 14.3 68 15 77.5 940/1255
70
Note: Return air condition: cooling, air inlet 27°C DB/19.5°C WB, entering water temp. 7°C, water temp. difference 5°C; B
Heating, air inlet 21°C DB, entering water temp. 60°C, water temp. difference 10°C.
Drain pipe Y DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25
13 14
Air Handling Unit
35
W R C Water outlet X
24
M K M
G
Water outlet X
H
J
H
S
E
P
J
Q
D
W+140 Water inlet X
Drain pipe Y Water inlet X
F
P
Q
D
Water outlet X 50 R C F
50 L W
Water inlet X W+150
N
Drain pipe Y
35
S M K M
G
Model (MKS/C) 05W 06W 08W 10W 15W 20W 25W 30W 35W 40W Model 03L 04L 05L 06L 08L 10L 15L 20L 25L 30L 35L 40L
L 1,120 1,120 1,170 1,200 1,220 1,350 1,400 1,450 1,880 1,880 L 580 580 630 630 740 740 740 860 960 960 1,000 1,000
Unit dimension W 1,100 1,200 1,450 1,650 1,940 2,440 2,590 2,790 2,790 2,790 Unit dimension W 1,010 1,050 1,110 1,200 1,350 1,410 1,940 2,420 2,790 2,790 3,200 3,400
H 840 840 945 965 1,195 1,310 1,510 1,580 1,930 2,060 H 1,100 1,250 1,420 1,470 1,650 1,800 1,880 1,980 2,160 2,360 2,360 2,360
D 25 25 25 25 25 80 80 80 80 80 D 50 50 50 50 50 50 80 80 80 80 80 80
E 762 762 865 890 1,115 1,175 1,375 1,440 1,795 1,925 E 474 575 677 728 830 982 1,038 1,026 1,090 1,280 1,280 1,280
Air inlet Air inlet
F 1,050 1,140 1,390 1,600 1,880 2,390 2,540 2,740 2,740 2,740 F 960 1,000 1,060 1,150 1,300 1,360 1,890 2,370 2,740 2,740 3,150 3,350
G 157 157 177 291 422 349 533 593 797 924 G 188 202 205 205 249 249 233 247 309 309 303 307
S 237 337 467.5 583.5 283 589 333 334 414 414 S 212 207 232 271 307 347 266 290 348 348 616 854
J 498 498 599 599 853 923 1,114 1,117 669 733 J 304 405 507 558 660 805 856 839 918 1,108 1,098 1,098
K / / / / 282 335 446 446 666 666 K / / / / / / 282 373 448 448 438 438
M 395 395 460 460 373 430 557 557 638 638 M 298 331 395 395 471 471 373 471 557 557 569 569
Air outlet Air outlet
N 341 341 408 408 404 478 478 478 638 638 N 262 289 341 341 404 404 404 404 478 478 569 569
P 172 172 172 172 172 224 224 224 224 224 P 161 161 161 161 161 168 203 206 211 211 214 214
Q 71 71 71 71 71 126 126 126 126 126 Q 101 101 101 101 101 101 131 134 134 134 134 134
R 156 156 156 156 156 195 195 195 186 186 R 102 102 102 102 102 102 111 111 111 111 111 111
Connecting 4R DN40 DN40 DN50 DN50 DN50 DN65 DN65 DN65 DN65×2 DN65×2 Connecting 4R DN40 DN40 DN40 DN40 DN40 DN50 DN50 DN50 DN65 DN65 DN80 DN80
pipe X 6R DN40 DN40 DN50 DN50 DN65 DN65 DN80 DN80 DN65×2 DN65×2 pipe X 6R DN40 DN40 DN40 DN40 DN40 DN50 DN50 DN50 DN65 DN65 DN80 DN80
Drain pipe Y DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 Drain pipe Y DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25 DN25
15 16
Air Handling Unit
17 18
Air Handling Unit
1.05 1.05
- 1.00 1.00
Electrical control box Can be customized to meet the requirement
0.95 0.95
0.90 0.90
3.0 4.0 5.0 6.0 7.0 8.0 0.4 1.0 1.5 1.9
Figure 1 Temperature difference correction coefficient of water F2 Figure 2 Water velocity correction coefficient F3
Motor Coil Air filter Humidifier
Step 2:
Determine the external static pressure (Pa). If the ESP is beyond the standard value of the above specifications, please indicate the
required ESP when you take the order. Take table B as a reference to estimate the air pressure in the duct.
19 20
Air Handling Unit
10 1. 35 30 30 20
9 1 25 25 18
7 0. 55 15 15 12
6 0. 4 12 12 10
Note:
1. Pto= on-way resistance+ local resistance, Pa.
2. ESP≈ Pto.
Step 3:
Determine the unit structure: horizontal type (W), vertical type (L) and suspended type (D).
Step 4:
Determine the pipe connecting mode: right-handed (Y), left-handed (Z).
Selection software
You can make selections under varies entering air conditions, entering water conditions, different air volume, and different
cooling capacity or heating capacity.
User friendly interface make selection visual and easy.
Powerful project managemakes functions.
Selection interface Report data interface
21 22
Modular Air Handling Unit
Air outlet
Left-handed unit
23 24
Cold bridge free structure
Features Unitary structure design and module panel design. Panels are double-skin with injection of high density polyurethane. The outer
Reliable quality skin is anti-corrosion color-coated steel sheet, the inner skin is galvanized steel sheet, the density of polyurethane is more than
Modular Air Handling Unit
1.Pre-filter
3.Eliminator
4.Elestric heater
6.Fan
25 26
Mechanical specifications Fan assembly
The vibration levels of the complete fan assembly (fan wheel, motor and
Base frame
Modular Air Handling Unit
Vibration protector
The fan motors are mounted on a rigid base frame which is supported by effective spring
shock absorber. Shipping brackets are equipped at the base frame to protect fans, motors
and spring shock absorber during transportation.
27 28
Coil Filter
In Midea MAHUs, there are three typical types of coils: chilled water coils, hot water coils and steam Air filtration is an important component to achieve an acceptable indoor air quality. In MAHUs, earlier low-efficiency filters of the
heater coils. All coils are AHRI certified and provided to meet the scheduled performance. Coils are panel type are giving way to the medium- and high-efficiency bag type and cartridge type of filters.
Modular Air Handling Unit
Humidifier
Testing
Usually, there is no humidifier installed in the MAHUs for comfort air conditioning systems; but the outdoor climate is very cold in method
Arrestance Dust-spot Particle-counting
winter so that if a humidifier is not employed, the winter indoor relative humidity may be too low. Humidifiers are necessary for
health care facilities and processing systems in pharmaceutical, semiconductor, textile, communication centers, and computer
rooms. Filter
Plate Plate/bag bag Dense pleated HEPA
Type
In Midea MAHUs, wet film vaporization, dry steam, electrode boiler, and water spray humidifiers are widely used. Wet film
vaporization humidifier is a type of enthalpy humidifier or evaporation gasification humidifier. Through the principle of exchange
of heat and moisture, the air is humidified and cooled. The medium is inorganic material which is high-life, high reliability, clean,
good heat conduction and bacteria resistance. Dry steam or electrode boiler humidifiers are widely used in where a warm air Air dampers
supply and humidity control are needed in winter.
Air dampers in MAHUs are optional. Aerodynamically designed
damper blades have built in high quality bearings. Blade edges
are lined with sealing strip to restrict leakage to an absolute
minimum. Air damper blades are either linked to give parallel
turning operation or gear set to give opposing direction. The
dampers are tested to yield linear control characteristic.
Mixing dampers working in pairs and can be coupled in such a
Wet film Electrode way that if one is 75% open the other is 25% open.
Dry steam humidifier Water spray humidifier
vaporization humidifier boiler humidifier
29 30
Functional sections
Modular Air Handling Unit
W≤3300 700
8
3636~3663 800 W>3300 1100
0609~1821 600
Hot Water Coil
Inlet Section
1824~3342 700
4 rows L=400mm
3636~3663 800
4 rows L=400mm
Supply Fan L=700~3900mm, depending on the unit model and air volume Electrode Boiler L=700mm
Humidifier
31 32
Quick selection table
Name Sketch Description
Fan
External static
Modular Air Handling Unit
Eliminator Can be fixed in water spray humidifier. MKZ1212 9133 1.01 8219 9133 10046 260 335 2.2
Water Supply Thickness (mm) Length (mm) MKZ1221 17585 1.95 15827 17585 19344 300 500 5.5
50/100 300 MKZ1518 18122 2.01 16310 18122 19934 320 500 5.5
Direct water supply
Wet-film Humidifier 150/200 400 MKZ1524 25083 2.79 22575 25083 27591 360 560 7.5
100 /150/ 200 600/700/800 MKZ1821 26895 2.99 24205 26895 29584 380 560 11.0
Circular water supply
250/300 700/800/900 MKZ1827 35513 3.95 31962 35513 39064 420 710 11.0
Silencer Three options:L=600mm,L=900mm,L=1200mm MKZ2427 46440 5.16 41796 46440 51084 500 800 15.0
Diffuser L=700mm
MKZ3042 97064 10.78 87357 97064 106770 800 1120 55.0
33 34
Standard combination
Horizontal STD combination 1: Horizontal STD combination 3:
Mixing chamber + Prefilter +Dense pleated filter + Cooling coil + Supply air fan
Modular Air Handling Unit
MKZ0609 1500 950 650 295 MKZ0609 2700 950 650 452
A
C
MKZ0612 1600 1250 650 342 MKZ0612 2800 1250 650 516
C
MKZ0909 1600 950 950 369 MKZ0909 2800 950 950 550
MKZ0912 1700 1250 950 432 MKZ0912 2900 1250 950 624
MKZ0915 1800 1550 950 491 MKZ0915 3000 1550 950 706
A
MKZ1212 1900 1250 1250 542 A MKZ1212 3100 1250 1250 762
MKZ1215 2000 1550 1250 618 MKZ1215 3200 1550 1250 864
B
MKZ1218 2100 1850 1250 715 MKZ1218 3300 1850 1250 1007
B
MKZ1221 2200 2150 1250 813 MKZ1221 3400 2150 1250 1104
MKZ1518 2200 1850 1550 838 MKZ1518 3400 1850 1550 1135
MKZ1524 2400 2450 1550 1068 MKZ1524 3600 2450 1550 1447
MKZ1821 2400 2150 1850 1174 MKZ1821 3600 2150 1850 1502
MKZ0612 2300 1250 650 441 MKZ0612 3200 1250 650 637
C
MKZ0909 3200 950 950 671
C
B
MKZ1218 3700 1850 1250 1266
MKZ1218 2800 1850 1250 876
B
MKZ1821 3100 2150 1850 1355 MKZ1821 4000 2150 1850 1910
Notes:
1. Height of unit = C + Height of base.
2. Two kinds of base height can be optioned: 80mm and 100mm.
3. Section should be CKD transported if a. The divided section's length is over 4000mm. or
b. Divided section's length and width is over 2300mm at the same time.
4. The above data are for reference only, and may deviate from latest development.
Please contact your local Midea sales representative for detail and updated data.
35 36
Vertical STD combination 1: Vertical STD combination 3:
Prefilter + Cooling coil + Supply air fan Mixing chamber + Prefilter +Dense pleated filter + Cooling coil + Humidifier + Supply air fan
Modular Air Handling Unit
A B C Net weight
Unit model
mm mm mm kg
C
MKZ1215 1400 1550 2500 300+383
MKZ0609 900 2000 950 1300 136+357 MKZ0609 900 2500 950 1300 136+418
MKZ0612 1000 2000 1250 1300 157+412 MKZ0612 1000 2500 1250 1300 165+483
C
MKZ0909 1000 2000 950 1900 171+436 MKZ0909 1000 2500 950 1900 171+507
MKZ0912 1100 2000 1250 1900 197+504 MKZ0912 1100 2500 1250 1900 202+584
MKZ0915 1200 2000 1550 1900 230+570 MKZ0915 1200 2500 1550 1900 230+661
A2
MKZ1212 1300 2000 1250 2500 262+597 MKZ1212 1300 2500 1250 2500 273+688
B
MKZ1215 1400 2100 1550 2500 310+692 MKZ1215 1400 2600 1550 2500 328+792
MKZ1218 1500 2100 1850 2500 352+796 MKZ1218 1500 2600 1850 2500 369+907
MKZ1221 1600 2100 2150 2500 414+867 MKZ1221 1600 2600 2150 2500 429+990
C
MKZ1518 1600 2100 1850 3100 418+899 MKZ1518 1600 2600 1850 3100 433+1024
MKZ1524 1800 2300 2450 3100 622+1065 MKZ1524 1800 2800 2450 3100 622+1214
MKZ1821 1800 2300 2150 3700 625+1181 MKZ1821 1800 2800 2150 3700 625+1328
MKZ1827 2200 2700 2750 3700 888+1579 MKZ1827 2200 3000 2750 3700 841+1787
Notes:
1. Height of unit = C + Height of base.
2. Two kinds of base height can be optioned: 80mm and 100mm.
3. Section should be CKD transported if a. The divided section's length is over 4000mm. or
b. Divided section's length and width is over 2300mm at the same time.
4. The above data are for reference only, and may deviate from latest development.
Please contact your local Midea sales representative for detail and updated data.
37 38
Horizontal STD combination 1: Horizontal STD combination 3:
Prefilter + Cooling coil + Supply air fan Mixing chamber + Prefilter +Dense pleated filter + Cooling coil + Supply air fan
Modular Air Handling Unit
MKZ1827 2700 2750 1850 1603 MKZ1827 1900 2200 2750 1850 1094+1034
MKZ2124 2700 2450 2150 1642 MKZ2124 1900 2200 2450 2150 1120+1003
C
C
MKZ2127 2700 2750 2150 1779 MKZ2127 1900 2200 2750 2150 1204+1095
MKZ2427 2800 2770 2470 2078 MKZ2427 1900 2300 2770 2470 1348+1420
MKZ2433 3000 3370 2470 2537 MKZ2433 1900 2500 3370 2470 1532+1704
A A1 A2 MKZ2733 1900 2500 3400 2800 1755+1929
MKZ2733 3000 3400 2800 2854
MKZ2736 3500 3700 2800 3292 MKZ2736 2200 2600 3700 2800 1975+2159
MKZ3036 3500 3700 3100 3556 MKZ3036 2200 2600 3700 3100 2145+2318
MKZ3042 3800 4100 3100 3542 MKZ3042 2200 2900 4300 3100 2345+2709
B
MKZ3342 2200 2900 4300 3400 2466+2014
B
MKZ3645 900+3200 4600 3700 1786+3314 MKZ3645 2300 3200 4600 3700 2750+2370
MKZ3654 900+3500 5500 3700 2088+4159 MKZ3654 2300 3500 5500 3700 3154+4159
MKZ3663 900+3500 6400 3700 2369+4310 MKZ3663 2300 3500 6400 3700 3549+4319
MKZ2124 3600 2450 2150 1954 MKZ2124 2300 2200 2450 2150 1599+1003
C
MKZ2127 3600 2750 2150 2057 MKZ2127 2300 2200 2750 2150 1731+1095
C
MKZ2427 3700 2770 2470 2489 MKZ2427 2300 2300 2770 2470 1946+1420
MKZ2433 3900 3370 2470 2878 MKZ2433 2200 2500 3370 2470 2102+1704
A
MKZ2733 3900 3400 2800 3263 MKZ2733 2600 2500 3400 2800 2273+1929
A1 A2
MKZ2736 1700+2600 3700 2800 1620+2159 MKZ2736 2900 2600 3700 2800 2523+2269
MKZ3036 1700+2600 3700 3100 1769+2208 MKZ3036 2900 2600 3700 3100 2735+2318
MKZ3042 1700+2900 4300 3100 2042+2574 MKZ3042 2900 2900 4300 3100 2901+1953
B
B
MKZ3342 1700+3000 4300 3400 2026+2014
MKZ3645 1800+3200 4600 3700 2268+2370 MKZ3645 3000 3200 4600 3700 3511+2370
MKZ3654 1800+3500 5500 3700 2600+4159 MKZ3654 3000 3500 5500 3700 4007+4159
MKZ3663 1800+3500 6400 3700 2920+4310 MKZ3663 3000 3500 6400 3700 4505+4319
Notes:
1. Height of unit = C + Height of base.
2. Two kinds of base height can be optioned: 80mm and 100mm.
3. Section should be CKD transported if a. The divided section's length is over 4000mm. or
b. Divided section's length and width is over 2300mm at the same time.
4. The above data are for reference only, and may deviate from latest development.
Please contact your local Midea sales representative for detail and updated data.
39 40
Coil performance
Cooling coil__Fresh air condition
Modular Air Handling Unit
Unit model Air volume Sensible Unit model Air volume Sensible Water
Sensible Air Water Cooling Water Cooling
Cooling resistance Water flow cooling Air resistance Water flow Air resistance Water flow pressure
cooling pressure drop capacity cooling
capacity capacity pressure drop capacity
capacity capacity drop
MKZ0609 2680 32.9 14.27 88 1.6 46.45 41.37 17.54 132 MKZ0609 2680 2 33.72 48.18 20.22 176 2.3 72.37
MKZ0612 3760 46.82 20.24 88 2.2 47.88 60.01 25.34 132 MKZ0612 3760 2.9 79.61 67.27 28.24 176 3.2 59.85
MKZ0909 4595 56.42 24.47 88 2.7 44.95 70.12 29.77 132 MKZ0909 4595 3.3 30.15 82.21 34.51 176 3.9 66.97
MKZ0912 6447 80.29 34.71 88 3.8 44.55 102.34 43.25 132 MKZ0912 6447 4.9 72.01 115.34 48.41 176 5.5 58.27
MKZ0915 8298 104.79 45.17 88 4.6 73.65 130.99 55.39 132 MKZ0915 8298 6.2 68.54 147.00 61.73 176 7.0 47.47
MKZ1212 9133 113.73 49.17 88 5.4 51.87 145.77 61.56 132 MKZ1212 9133 6.9 73.15 163.39 68.59 176 7.8 56.01
MKZ1215 11756 142.28 61.88 88 6.8 30.32 185.58 78.48 132 MKZ1215 11756 8.8 65.65 208.26 87.46 176 9.9 47.61
MKZ1218 14670 182.69 78.96 88 8.7 54.15 226.43 96.00 132 MKZ1218 14670 10.8 38.92 257.31 108.12 176 12.3 33.82
MKZ1221 17585 222.07 95.71 88 9.9 75.80 277.59 117.36 132 MKZ1221 17585 13.2 62.80 313.06 131.42 176 14.9 53.38
MKZ1518 18122 225.68 97.54 88 10.7 51.15 279.71 118.59 132 MKZ1518 18122 13.3 42.93 317.85 133.56 176 15.1 40.60
MKZ1524 25083 312.36 135.05 88 12.2 79.40 391.55 165.78 132 MKZ1524 25083 18.7 59.51 417.95 176.38 176 19.9 40.68
MKZ1821 26895 311.34 136.88 88 14.8 13.37 424.56 179.49 132 MKZ1821 26895 20.2 58.04 478.81 201.00 176 22.8 46.94
MKZ1827 35513 429.79 186.98 88 20.5 28.15 535.68 227.89 132 MKZ1827 35513 25.5 27.08 604.20 254.44 176 28.8 27.63
MKZ2124 35833 427.38 186.50 88 20.4 21.57 527.94 225.36 132 MKZ2124 35833 25.1 22.41 641.07 269.10 176 30.5 71.11
MKZ2127 40977 495.92 215.75 88 23.6 30.43 618.10 262.95 132 MKZ2127 40977 29.4 31.71 697.16 293.58 176 33.2 33.52
MKZ2427 46440 562.03 244.52 88 26.8 33.34 700.51 298.01 132 MKZ2427 46440 33.4 36.99 790.11 332.72 176 37.6 40.24
MKZ2433 58099 723.52 312.78 88 34.5 59.58 896.75 380.25 132 MKZ2433 58099 42.7 63.79 1013.94 426.09 176 48.3 68.65
MKZ2733 68351 851.19 367.97 88 40.5 69.36 1054.99 447.35 132 MKZ2733 68351 50.3 78.81 1192.86 501.27 176 56.8 87.86
MKZ2736 74524 941.13 405.59 88 44.8 62.32 1163.34 492.57 132 MKZ2736 74524 55.4 51.25 1320.20 554.48 176 62.9 47.15
MKZ3036 81976 1035.24 446.21 90 49.3 64.60 1279.67 541.68 135 MKZ3036 81976 61.0 47.00 1437.83 604.26 180 68.5 37.86
MKZ3042 97064 1123.63 493.80 90 53.5 16.92 1532.22 647.87 135 MKZ3042 97064 73.0 72.55 1728.01 725.45 180 82.3 58.45
MKZ3342 105888 1300.07 563.68 88 62.10 37.06 1690.09 713.74 132 MKZ3342 105888 80.73 73.36 1894.39 795.21 176 90.49 60.43
MKZ3645 124187 1524.74 660.95 90 72.83 44.65 1938.60 820.63 134 MKZ3645 124187 92.60 48.99 2221.76 932.33 179 106.13 75.28
MKZ3654 151448 1912.15 824.39 90 91.31 76.09 2390.71 1010.93 134 MKZ3654 151448 114.20 80.05 2682.91 1126.42 179 128.15 85.71
MKZ3663 178708 2225.48 961.90 90 160.30 60.22 2789.69 1180.86 134 MKZ3663 178708 133.25 83.71 3131.40 1304.84 179 149.58 93.73
Notes:
1. Totally fresh air cooling condition: Entering air: 35°C WB / 28°C DB, entering water: 7°C, leavinging water: 12°C.
2. Coil is copper tube and aluminum fin type, the water velocity is 0.8~2.0 m/s.
3. The above performance are for reference only, and may deviate from latest development.
Please contact your local Midea sales representative for detail and updated selections.
41 42
Cooling coil__Return air condition
Entering air: 27°C WB / 19.5°C DB, entering water: 7°C Entering air: 27°C WB / 19.5°C DB, entering water: 7°C
Modular Air Handling Unit
MKZ0609 2680 13.39 10.44 88 0.6 9.35 18.24 12.90 132 MKZ0609 2680 0.9 22.25 21.58 14.49 176 1.0 37.99
MKZ0612 3760 20.08 15.15 88 1.0 23.32 26.56 18.49 132 MKZ0612 3760 1.3 53.01 30.61 20.46 176 1.5 41.00
MKZ0909 4595 22.96 17.91 88 1.1 9.11 31.27 22.12 132 MKZ0909 4595 1.5 21.79 37.01 24.84 176 1.8 37.35
MKZ0912 6447 34.43 25.97 88 1.6 22.77 45.54 31.71 132 MKZ0912 6447 2.2 52.05 52.20 34.97 176 2.5 38.00
MKZ0915 8298 45.74 33.98 88 2.2 44.23 57.89 40.52 132 MKZ0915 8298 2.8 31.47 68.62 45.62 176 3.3 73.23
MKZ1212 9133 48.77 36.80 88 2.3 21.46 64.51 44.92 132 MKZ1212 9133 3.1 49.75 74.34 49.70 176 3.5 42.48
MKZ1215 11756 64.81 48.17 88 3.1 41.92 82.02 57.40 132 MKZ1215 11756 3.9 31.90 97.21 64.63 176 4.6 80.70
MKZ1218 14670 83.40 61.09 88 4.0 76.43 105.51 72.94 132 MKZ1218 14670 5.0 58.22 119.41 79.82 176 5.7 44.42
MKZ1221 17585 99.21 72.95 88 4.7 62.01 124.20 86.50 132 MKZ1221 17585 5.9 42.54 146.17 96.98 176 7.0 72.30
MKZ1518 18122 103.02 75.46 88 4.9 79.38 130.34 90.11 132 MKZ1518 18122 6.2 59.72 147.51 98.60 176 7.0 43.14
MKZ1524 25083 143.68 104.92 88 6.8 82.68 180.40 124.74 132 MKZ1524 25083 8.6 60.92 205.25 136.99 176 9.8 48.98
MKZ1821 26895 151.74 111.58 88 7.2 57.76 189.96 132.29 132 MKZ1821 26895 9.0 40.51 223.55 148.32 176 10.6 69.49
MKZ1827 35513 195.77 145.45 88 9.3 37.15 247.77 173.42 132 MKZ1827 35513 11.8 27.75 295.19 195.84 176 14.1 70.93
MKZ2124 35833 205.25 149.88 88 9.8 84.62 257.72 178.20 132 MKZ2124 35833 12.3 61.34 293.22 195.70 176 14.0 45.91
MKZ2127 40977 225.89 167.83 88 10.8 38.16 285.89 200.10 132 MKZ2127 40977 13.6 28.51 340.60 225.97 176 16.2 66.25
MKZ2427 46440 256.01 190.21 88 12.2 39.31 324.01 226.78 132 MKZ2427 46440 15.4 29.37 386.01 256.09 176 18.4 68.27
MKZ2433 58099 330.29 241.98 88 15.7 72.72 415.36 287.79 132 MKZ2433 58099 19.8 53.74 472.91 316.14 176 22.5 44.62
MKZ2733 68351 388.57 284.68 88 18.5 69.70 488.66 338.58 132 MKZ2733 68351 23.3 56.21 556.36 371.93 176 26.5 48.80
MKZ2736 74524 410.83 305.27 88 19.6 42.88 539.21 371.81 132 MKZ2736 74524 25.7 70.58 616.24 409.74 176 29.4 53.29
MKZ3036 81976 451.91 335.55 90 21.5 44.34 593.13 408.95 135 MKZ3036 81976 28.3 78.08 670.80 447.55 180 32.0 53.80
MKZ3042 97064 551.80 404.01 90 26.3 71.23 685.57 477.36 135 MKZ3042 97064 32.7 49.36 802.62 533.46 180 38.2 83.70
MKZ3342 105888 601.91 441.07 88 28.75 71.11 747.90 520.81 132 MKZ3342 105888 35.72 49.27 861.91 576.20 176 41.17 38.54
MKZ3645 124187 663.21 500.11 90 31.68 26.04 887.84 615.18 134 MKZ3645 124187 42.41 60.64 1016.20 678.02 179 48.54 46.62
MKZ3654 151448 834.88 619.94 90 39.88 45.06 1056.65 739.54 134 MKZ3654 151448 50.47 34.16 1252.32 832.37 179 59.82 78.29
MKZ3663 178708 1015.94 743.90 90 48.53 71.99 1277.63 885.22 134 MKZ3663 178708 61.03 53.97 1446.95 969.14 179 69.12 44.11
Notes:
1. Return air cooling condition: Entering air: 27°C WB /19.5°C DB, entering water: 7°C, leavinging water: 12°C.
2. Coil is copper tube and aluminum fin type, the water velocity is 0.8~2.0 m/s.
3. The above performance are for reference only, and may deviate from latest development.
Please contact your local Midea sales representative for detail and updated selections.
43 44
Heating coil performance
1-row 2-rows
Return air condition (15°C) Fresh air condition (7°C) Return air condition (15°C) Fresh air condition (7°C)
Modular Air Handling Unit
m³/h kW L/s kPa kW L/s kPa m³/h kW L/s kPa kW L/s kPa
MKZ0609 2680 8.4 0.2 9 10.1 0.24 13 MKZ0609 2680 14.0 0.33 25 17.9 0.43 40
MKZ0612 3760 11.5 0.28 17 13.8 0.33 24 MKZ0612 3760 19.1 0.46 45 24.5 0.59 72
MKZ0909 4595 14.4 0.34 9 17.3 0.41 13 MKZ0909 4595 23.9 0.57 25 30.7 0.73 40
MKZ0912 6447 19.4 0.46 17 23.3 0.56 23 MKZ0912 6447 32.3 0.77 44 41.4 0.99 70
MKZ0915 8298 26.6 0.64 30 32 0.76 43 MKZ0915 8298 44.2 1.06 37 56.7 1.36 59
MKZ1212 9133 30.2 0.72 20 36.3 0.87 28 MKZ1212 9133 50.2 1.2 24 64.4 1.54 39
MKZ1215 11756 39.6 0.95 33 47.5 1.14 47 MKZ1215 11756 65.7 1.57 40 84.3 2.01 65
MKZ1218 14670 50.4 1.2 81 60.5 1.44 74 MKZ1218 14670 83.7 2 17 107.4 2.56 27
MKZ1221 17585 63.4 1.51 15 76 1.82 115 MKZ1221 17585 105.2 2.51 26 135 3.22 42
MKZ1518 18122 63.4 1.51 25 76 1.82 35 MKZ1518 18122 105.2 2.51 18 135 3.22 28
MKZ1524 25083 90.0 2.15 49 108 2.58 69 MKZ1524 25083 149.4 3.57 34 191.7 4.58 55
MKZ1821 26895 93.6 2.24 35 112.3 2.68 50 MKZ1821 26895 155.4 3.71 25 199.4 4.76 40
MKZ1827 35513 126.7 3.03 63 152.1 3.63 89 MKZ1827 35513 210.4 5.03 44 269.9 6.45 71
MKZ2124 35833 126.7 3.03 48 152.1 3.63 67 MKZ2124 35833 210.4 5.03 33 269.9 6.45 54
MKZ2127 40977 143.3 3.42 60 171.9 4.11 85 MKZ2127 40977 237.8 5.68 42 305.2 7.29 68
MKZ2427 46440 165.6 3.96 62 198.7 4.75 89 MKZ2427 46440 274.9 6.57 44 352.7 8.43 70
MKZ2433 58099 208.8 4.99 97 250.6 5.99 138 MKZ2433 58099 346.6 8.28 68 444.7 10.62 110
MKZ2733 68351 244.8 5.85 97 293.8 7.02 137 MKZ2733 68351 406.4 9.71 68 444.7 10.62 110
MKZ2736 74524 259.2 6.19 29 311 7.43 41 MKZ2736 74524 430.3 10.28 20 552.1 13.19 32
MKZ3036 81976 288.0 6.88 29 345.6 8.26 41 MKZ3036 81976 478.1 11.42 20 613.4 14.65 33
MKZ3042 97064 352.8 8.43 43 423.4 10.11 61 MKZ3042 97064 585.6 13.99 30 751.5 17.95 49
MKZ3342 105888 381.6 9.12 42 457.9 10.94 60 MKZ3342 105888 633.5 15.13 30 812.8 19.42 48
MKZ3645 124187 439.2 10.49 46 527.0 12.59 65 MKZ3645 124187 729.1 17.42 32 935.5 22.35 54
MKZ3654 151448 540.0 12.90 68 648.0 15.48 96 MKZ3654 151448 896.4 21.41 48 1150.2 27.48 77
MKZ3663 178708 619.2 14.79 88 743.0 17.75 125 MKZ3663 178708 1027.9 24.55 62 1318.9 31.51 100
Notes:
1. Return air heating condition: Entering air:15°C DB, entering water: 60°C, leavinging water:50°C.
2. Fresh air heating condition: Entering air:7°C DB, entering water: 60°C, leavinging water:50°C.
3. Coil is copper tube and aluminum fin type, the water velocity is 0.8~2.0 m/s.
4. The above performance are for reference only, and may deviate from latest development.
Please contact your local Midea sales representative for detail and updated selections.
45 46
Selection software Selection interface
To help customers define their product requirements easily, a user-friendly software selection program is provided. The program
leads the user through the selection process by pertinent input data for all components required. Component sections are
Modular Air Handling Unit
Report interface
Main interface
47 48
Modular Air Handling Unit
Installation Reference Projects
Unit should be installed on a horizontal foundation to avoid running noise and keep the condensing water draining smoothly. Hotel & Restaurant
Allow sufficient space for maintenance. At least 1m width should be reserved in the direction of setting up the accesses door
as shown in figure installation space.
Piping
Flexible fittings should be used in water piping to absorb thermal expansion and contraction strains.
Drainage pipe should be equipped a U shape water seal to keep water draining fluently as shown in figure draining pipe.
≥600mm
H=Pst(mmH2O)+20
≥600mm B=150~250mm
AHU or MAHU
Installation
2H
H
Basement
≥100mm
B
Drain to sewer
Reference Projects
Installation space Draining pipe
Wiring L1 L2 L3 N
Start-up requirements
Before start-up the units, do make sure that ductwork is clean, filters are in place, bearings lubricated, condensate properly
trapped, piping connections verified and leak tested, belts aligned and tensioned, all shipping braces have been removed, and
fan has been test run under observation.
Maintenance
Check and make sure valves in water pipe and air duct are in normal working condition before unit running. Hilton Hotel in Foshan (Five Star)
Check the lubrication of fan bearings and tension of belts regularly. Country: China
Check and adjust the connection, operation and transmission of fan, motor and other moving parts regularly. City: Foshan
Total Capacity: 3,700 RT
Wash the air filters once a month.
Outdoor Unit: Centrifugal chiller &
Exhaust the water in the coil if the unit stops using for a long period. Water-cooled screw chiller
In winter, keep the water in the coil circulating when stop the unit for a short time. Indoor Unit: AHU & FCU
The water in the coil should be softened water. Clear away scale in the coil and dirty thing among the fins once a year. Completion Year: 2013
Total Floor Area: 90,000 m²
For the detail information about installation, usage and maintenance, please refer to the ‘installation manual’, or consult
Midea company.
49 50
Transportation Sports
Reference Projects
City: Maputo
Total Capacity: 4,000 RT
Outdoor Unit: Air-cooled screw chiller
Indoor Unit: FCU & AHU
Completion Year: 2012
Culture facilities
Industry
51 52