Introduction
Medium Voltage Switchgear is in our DNA . CGL
CG a leading member of
Avantha group of
has over 50 years of experience in the design and
manufacturing of MV Switchgear.
companies, is one of India’s CG was established in 1937 in India and since then
the Company has been a pioneer and has retained
largest private sector enterprise its leadership position in the management and
& is in operations since last application of electrical energy.
seven decades. It is engaged As one of the world`s leading engineering
in design, manufacture & corporations, CG provides end-to-end solutions,
helping its customers, use electrical power,
marketing of technologically effectively and increase industrial productivity with
advanced electrical products and sustainability.
1
Product Range
Products Rated Voltage Rated Current Breaking Capacity
Metal Clad Claix VCB - Roof Bushing 12kV upto 1250 A upto 25 kA
Metal Clad Felix VCB - Roof Bushing 36kV upto 1250 A upto 25 kA
CG Arista (Single & double Busbar) 36kV upto 1250 A upto 26.3 kA
CG Arista (Single & double Busbar) 36kV upto 2500 A upto 31.5 kA
Protection Relays
Under Voltage, Over Voltage & Neutral Displacement Relay- CGV 24C
Product Range 2
Why CG ? Following good engineering
practices are followed by CG. This
4. Welding
Welding quality is checked by non
destructive Dye Penetration test as per
(Good results in to low operating and ASME section 9 & ASNDT standards to
ensure defect free welding like porosity,
maintenance cost during the life
Engineering cycle of equipment and ensure
blow holes, discontinuity, cracks etc.
5. Thermal Reliability
Practices) enhanced reliability and long Outdoor VCB
Flexible laminations of electrolytic copper
service life of our product.
to be used with the ends of the laminations
solidified with hot pressed/electro fusion/
1. Sheet steel (Raw Material) Electro solidification method to ensure
a. All metal enclosures are fabricated good electrical contacts and achieve
from CRCA sheet steel free from all minimum contact resistance.
surface defects. The panel enclosure have
sufficient structural re-enforcement to Indoor VCB
ensure a plane surface to limit vibration Laminated contacts in Calix VCB and heat
and to provide rigidity during dispatch and sink block for faster dissipation of heat to
installation. increase thermal reliability.
b. Procurement from reputed companies 6. Trip and close coil
avoid bad finish, surface defect, low tensile The trip and close coil used in the breaker
strength, cracks during bending. should be adjustment free, fixed factory
setting & consume less power.
c. Every lot of raw material are tested for
surface finish, tensile strength, material 7. Electrical accessories:
composition, % elongation to ensure the All electrical accessories like Switches,
Powder coating plant finish & strength of the final product. Lamps, Push buttons, terminal blocks,
and fuses are procured only from
2. Emphasis on special processes reputed manufacturers. Only type tested
Validation accessories as per IEC standards are
a. Welding, Brazing, Painting, Plating, procured.
Crimping, Casting etc.
8. Control wires:
b. Audit Tests : Thermal cycle, Salt spray,
Endurance etc FRHR / FRLS (Fire retardant, Low Smoke)
grade wires are procured confirming to
IEC standards from reputed manufacturers.
3. Phosphating, Pre-treatment and
Painting 9. Higher Dielectric Strength
a. All switchgear cubicles are made
Breaker are validated and type tested for
absolutely vermin-proof. All metal
higher Basic Insulation Level.
enclosures treated in 7 tank Pre-treatment
process & painted with UV Resistant
11KV : 38kV / 95 kVp
Pure Polyester Powder coating. Adequate
thickness of Painting/Powder coating
Advantage to Customers: Eliminates
withstands tropical heat and extremes of
the probability of flashovers increasing
weather.
the service life of VCB with reduced
maintenance cost, at no extra capital
b. Powder coating quality checks by expenditure.
scratch hardness, peal off test, cross cut
Surface Roughness Tester hatch test, bend test, impact test & salt 10. Protection against overcharging of
spray test, UV resistance test. springs
After the charging motor supply is cut off
c. All mechanism components are zinc the springs are likely to get further charged
plated by trivalent passivation in a ROHS due to high inertia of rotating motor.
Compliant system. To verify the efficacy Overcharging of springs are prevented by
of the plating on the components, random incorporating specially designed ratchet
samples are subjected to 150 hours salts & thereby preventing mechanism closing
spray test. hard.
3 Good Engineering Practices
Why CG ? Inspection and Testing Facilities
(Good
Engineering
Practices)
Peace of Mind
For MV power distribution CG switchgears has very distinct advantages: Smooth
operation, exemplary availability and optimal safety.
Features
† †
†
†
† †
†
† †
† †
†
† †
2. Training
9 - Feeder Protection
50/51 Instantaneous & Inverse Time Phase Over Current Protection
50G/51G Instantaneous & Inverse Time Measured Earth Fault Protection
50N/51N Instantaneous & Inverse Time Derived Earth Fault Protection
67 Directional Instantaneous & Inverse Time Phase Over Current Protection
67N Directional Instantaneous & Inverse Time Earth Fault Protection
27 Instantaneous & Inverse Time Phase Under Voltage Protection
59 Instantaneous & Inverse Time Phase Over Voltage Protection
59N Neutral Displacement Protection
46 Negative Phase Sequence Overcurrent Protection
50BF Circuit Breaker Failure Protection
46BC Broken Conductor Detection Protection
68 Inrush Detection (2nd & 5th Harmonics Blocking)
50S Sensitive /Standby Earth Fault Protection
64N Restricted Earth Fault Protection
81O/U Over & Under Frequency Protection
51V Voltage Controlled Over Current Protection
49 Thermal Overload Protection
47 Negative Phase Sequence Over Voltage Protection
32 Reverse Power Protection
79 Auto Recloser
60CTS CT Supervision
60VTS VT Fuse Failure
Three Phase Current, Neutral Current
Phase to Earth, Phase to Phase Voltage, Phase Angle, Frequency
Sequence Components of Voltages & Currents
55 Power factor
Active, Reactive, Apparent Power & Energy Measurement
Average & Maximum Demand Measurement
CB Control
2nd to 15th harmonics and THD of Voltages & Currents
Phasor Diagram of Voltages & Currents
Single Line Diagram
MODBUS
IEC 60870-5-103
IEC 61850
- Feeder Protection 10
11 - Feeder Protection
Three Phase O/C & E/F (50, 51, 50N, 51N, 50G, 51G)
Negative Phase Sequence O/C (46)
Sensitive / Standby Earth fault (50S)
Restricted Earth Fault (64N)
Inrush Detection (68)
CBFP (50BF), Broken Conductor (46BC)
Thermal Overload (49)
CT Supervision (60 CTS)
Auto Recloser (79)
Three Phase O/C & E/F (50, 51, 50N, 51N, 50G, 51G)
Three Phase Directional O/C & E/F (67/67N)
Negative Phase Sequence O/C (46)
Inrush Detection (68)
CBFP (50BF), Broken Conductor (46BC)
Three Phase O/V, U/V & NDR (27, 59, 59N)
Thermal Overload (49)
Voltage Controlled Overcurrent (51V)
Negative Sequence Overvoltage (47)
Reverse Power (32)
Over Frequency (81O)
Under Frequency (81U)
CT Supervision (60 CTS)
VT Fuse Failure (60 VTS)
Auto Recloser (79)
Power Measurement (P)
Energy KWH, KVAH, KVARH
Non-Communicable 0
IEC 60870-5-103 & MODBUS-RTU on RS-485 Port 1
IEC 61850 on Single Ethernet RJ45 Port 6
IEC 61850 on Single Fiber Optic Port 7
IEC 61850 on Dual Ethernet RJ45 Port 8
IEC 61850 on Dual Fiber Optic Port 9
IEC 61850 on Dual Ethernet RJ45 Port + IEC 60870-5-103 & MODBUS on RS-485 Port A
4 DI + 8 DO
8 DI + 12 DO
10 DI + 10 DO*
12 DI + 8 DO
4 DI + 16 DO
12 DI + 10 DO*
16 DI + 10 DO*
8 DI + 8 DO
16 DI + 8 DO
24 DI + 12 DO*
Reserved
Note: The models marked '*' are available in only in drawout casing.
- Feeder Protection 12
Ordering Example :
13 - Transformer Protection
Functional Overview - Aegis - T
ANSI No. Function Name
87 Biased Differential Protection - Two Winding
87 HS High-Set Differential Protection
64 High Impedance REF Protection
87N Biased EF Protection (Low Impedance REF)
50/51 Instantaneous & Inverse Time Phase Over Current Protection
50N/51N Instantaneous & Inverse Time Derived Earth Fault Protection
50G/51G Instantaneous & Inverse Time Measured Earth Fault Protection
PROTECTION FUNCTION
Function
nication
IEC 60870-5-103
IEC 61850
- Transformer Protection 14
- Aegis - Transformer
- Aegis - Transformer
15 - Transformer Protection
Ordering Information for AEGIS Series Transformer Protection Relays
T
PROTECTION FUNCTIONS
Three Phase O/C & Derived E/F (50, 51, 50N, 51N)
Biased Differential (87) - 2 winding
Thermal Overload (49)
Negative Phase Sequence O/C (46) I
Under Current (37)
2nd,4th & 5th Harmonic Restraint
CBFP (50BF)
Model I + Following Functions = Model A
Measured E/F (50G, 51G)
Restricted Earth fault (64N) A
Over Fluxing (24)
One Phase O/V, U/V & NDR (27, 59, 59N)
Over & Under Frequency (81)
Model A + Following Functions = Model B
Biased Earth fault (Low Impedance REF) (87N)
Three Phase O/V, U/V & NDR (27, 59, 59N)
CT Supervision (60 CTS)
VT Fuse Failure (60 VTS) B
Directional O/PWR, U/PWR (32)
Auto Reclose (79)
Power Measurement (P)
Energy KWH, KVAH, KVARH
COMMUNICATION
Non-Communicable 0
IEC 60870-5-103 on RS-485 Port 1
MODBUS on RS-485 Port 3
IEC 61850 on Single Ethernet RJ45 Port 6
IEC 61850 on Single Fiber Optic Port 7
IEC 61850 on Dual Ethernet RJ45 Port 8
IEC 61850 on Dual Fiber Optic Port 9
4 DI + 6 DO
8 DI + 10 DO
10 DI + 8 DO
12 DI + 6 DO*
4 DI + 14 DO
12 DI + 10 DO*
16 DI + 10 DO + 4 RTD Inputs*
8 DI + 8 DO
16 DI + 10 DO*
Reserved A
Note: The models marked '*' are available in only in drawout casing.
- Transformer Protection 16
† Exclusive storage of:
Ÿ 500 sequences of Events
Ÿ Latest 10 Fault Records
P Ÿ Latest 15 Disturbance Records
with time stamping.
† Closing & Tripping command to
breaker from the relay.
Motor Protection Relay † Configurable & Programmable
digital outputs & digital inputs.
† Supports IEC 61850 Standard for
communication & interoperability of
substation automation devices
including GOOSE Messaging using
CGL 61850 IED Configuration Tool,
so as to meet application specific
requirements.
† Front USB port for local
communication and for ConAegis
Relay Communication Software
interaction with the PC.
† Display of the used Thermal
capacity.
† Indication of motor time to trip
and time to start.
† Thermal Overload protection † Monitoring of sequence
settings are available for the components of voltage and current
flexibility of customer operation for and protection based on sequence
the range of Medium Voltage components such and phase
motors. reversal.
† Independently settable Non † Motor protection functions are
directional overcurrent / earthfault based on motor full load current
setting stages are available for the which is easily settable.
flexibility of customer operation. † Assigning of closing contact for
† Four independent setting groups frequent start protection to
are provided for easy adoption to safeguard the motor from
varying system operating exceeding the maximum number of
conditions. starts.
† Suitable for both 1A & 5A CT
configuration on same terminals.
† LCD with 20x4 character /
Graphical backlit display to view
the measurements, configuring the
relay settings, etc.
† Three phase current & Voltage
phasor representation along with
Single Line Diagram on graphical
display.
† Total Harmonic Distortion for
fundamental and 2nd to 15th
Harmonics monitoring.
† Self Monitoring / Watch-dog
feature & User Configurable Logic.
17 - Motor Protection
50/51 Instantaneous & Inverse Time Phase Over Current Protection
50G/51G Instantaneous & Inverse Time Measured Earth Fault Protection
50N/51N Instantaneous & Inverse Time Earth Fault Protection
49 Thermal Overload Protection
51LR Stall Protection
27 Instantaneous & Inverse Time Phase Under Voltage Protection
59 Instantaneous & Inverse Time Phase Over Voltage Protection
59N Neutral Displacement Protection
46 Negative Phase Sequence Overcurrent Protection
50BF Circuit Breaker Failure Protection
46R Phase Reversal Protection
66 Frequent Start Protection (No. of Starts)
50S Sensitive /Standby Earth Fault Protection
64N Restricted Earth Fault
81O/U Over And Under Frequency
37 Under Current Protection
47 Negative Sequence Over Voltage
32 Reverse Power Protection
60CTS CT Supervision
60VTS VT Fuse Failure
Three Phase Current, Neutral Current
Phase to Earth, Phase to Phase Voltage, Phase Angle, Frequency
Sequence Components of Voltages & Currents
Power factor
Active, Reactive, Apparent Power & Energy Measurement
CB Control
Average & Maximum Demand Measurement
2nd to 15th harmonic and THD of Voltages & Currents
Phasor diagram of Voltages & Currents
Motor Start up Supervision
- Motor Protection 18
19 - Motor Protection
Ordering Information for AEGIS Series Motor Protection Relays
M
PROTECTION FUNCTIONS
Three Phase O/C & Derived E/F (50, 51, 50N, 51N, 50G, 51G)
Thermal Overload Protection (49)
Stall Protection (51 LR)
Frequent Start Protection (No. of Starts) (66) I
Under Current Protection (37)
Negative Phase Sequence O/C (46)
Sensitive / Standby Earth fault (50S)
CBFP (50BF)
CT Supervision (60 CTS)
Three Phase O/C & E/F (50, 51, 50N, 51N)
Thermal Overload Protection (49)
Stall Protection (51 LR)
Frequent Start Protection (No. of Starts) (66)
Under Current Protection (37)
Negative Phase Sequence O/C (46)
CBFP (50BF), Phase Reversal (46R)
Three Phase O/V, U/V & NDR (27, 59, 59N) G
Negative Sequence Overvoltage (47)
Reverse Power (32)
Over Frequency (81O)
Under Frequency (81U)
CT Supervision (60 CTS)
VT Supervision (60 VTS)
Power Measurement (P)
Energy KWH, KVAH, KVARH
Model G + Following Protections = H
Sensitive / Standby Earth fault (50S) H
Restricted Earth fault (64N)
COMMUNICATION
Non-Communicable 0
IEC 60870-5-103 &/ OR MODBUS on RS-485 Port 1
IEC 61850 on Single Ethernet RJ45 Port 6
IEC 61850 on Single Fiber Optic Port 7
IEC 61850 on Dual Ethernet RJ45 Port 8
IEC 61850 on Dual Fiber Optic Port 9
4 DI + 8 DO 1
8 DI + 12 DO 2
10 DI + 10 DO* 3
12 DI + 8 DO* 4
4 DI + 16 DO 5
12 DI + 10 DO* 6
16 DI + 10 DO* 7
8 DI + 8 DO 8
16 DI + 8 DO 9
24DI + 12 DO* A
Reserved B
Note: The models marked '*' are available in only in drawout casing.
- Motor Protection 20
21 -
PROTECTION † Password protection to guard against
unauthorized access & editing of
The Aegis relay platform provides cost settings.
RELAYS & IED effective, integrated Numerical Protection,
Control, Monitoring & Measuring
† Front USB port for ConAegis Relay
Communication Software interaction
functions with Communication with the PC.
functionality The 'Aegis µ' Numerical † User Programmable Logic
Feeder Protection Protection Relay is a fully digital relay
based on microprocessor technology with †
Application.
Exclusive storage of latest 10
Relay - Aegis µ analog to digital conversion of the disturbance records with time
measured values and subsequent stamping.
numerical processing. It uses specialized † Exclusive storage of latest 10 fault
digital signal processor (DSP) as the records with time stamping.
computational hardware, along with † Exclusive storage of latest 1000 event
associated software. records with time stamping.
The relay can be programmed as 3O/C +
1E/F or RE/F or SE/F (optional), or 2 O/C + Applications
1E/F + 1SE/F or 1RE/F (optional). The front
panel features 8 LEDs, 8-button keypad & a † P r i m a r y c i rc u i t p r o t e c t i o n o n
16x2 LCD backlit display to view the relay distribution networks at any voltage
features that provides an easy user level.
interface.
† Backup/auxiliary protection for
Features transformers, generators and motors.
† Rated input current: 1A or 5A on
separate terminals. † Auto reclosing function (4 shots).
† 4 independent setting groups for easy
adoption to var ying operating
conditions.
† Inrush Detection with 2nd & 5th
harmonic restraint.
† Closing & Tripping command to
breaker from the relay.
Configurable & Programmable digital
inputs & digital outputs.
† Communication Protocols: MODBUS-
RTU & IEC 60870-5-103 on RS 485
port.
Aegis - µ † Relay programming through local
keypad.
† Selectable Definite Time or IDMT
curves as per IEC, IAC & IEEE
standards.
- Feeder Protection 22
- AEGIS µ
CB Control
2nd to 5th harmonics and THD of Currents
Frequency
Actual RMS value of Currents
COMMUNICATION MODBUS - RTU
PROTOCOLS IEC 60870-5-103
23 - Feeder Protection
Wiring Diagram
The following figure shows the Typical Wiring Diagram for AEGIS Feeder Protection Relay
PROTECTION FUNCTIONS
3 O/C+1 E/F: (51/50), (51N/50N), (51G/50G), 46, 46BC, 68, 50BF, 60CTS, 79 A
3 O/C+SE/F: (51/50), (50S), (51N/50N), 46, 46BC, 68, 50BF, 60CTS, 79 B
3 O/C+RE/F: (51/50), (64N), (51N/50N), 46, 46BC, 68, 50BF, 60CTS, 79 C
2 O/C+1 E/F+SE/F: (51/50), (51G/50G), (50S), 46, 46BC, 68, 50BF, 60CTS, 79 D
2 O/C+1 E/F+RE/F: (51/50), (51G/50G), (64N), 46, 46BC, 68, 50BF, 60CTS, 79 E
COMMUNICATION
Non-Communicable 0
IEC 60870-5-103 & MODBUS on RS-485 Port 1
DIGITAL INPUT & OUTPUT CONFIGURATION
4 DI + 5 DO 1
10 DI + 10 DO 2
AUXILIARY POWER SUPPLY
18-52VDC 1
75-250VDC 2
CASE
Drawout D
OPERATING VOLTAGE FOR DIGITAL INPUT
30V DC 1
110V DC 2
220V DC 3
- Feeder Protection 24
Typical Uses
CG - Switchgear is safe, Reliable & Efficient for
all Medium Voltage Applications
25 Typical Uses
E S
Protection Relay IEC 60255
26
a
27
CG POWER AND INDUSTRIAL SOLUTIONS LTD