Fire Risk Assessment
Fire Risk Assessment
This proforma is one of many alternatives methods that may be used to assist in the
completion of a fire risk assessment. It provides a series of questions that should, if answered
fully and honestly and the necessary remedial action taken, assist you to comply with the
relevant legislation.
It is recommended that the proforma is used in conjunction with the Home Office publication
"Fire Safety - An Employer's Guide" published by HM Stationery Office Reference: ISBN 0-
11-341229-0 (available to view in full at http://www.archive.official-
documents.co.uk/document/fire/index.htm)
The proforma is written in terms that are intended to be simple to understand, but may take a
considerable amount of time to gather all information required and complete fully. If you do
not understand a particular element please seek advice from a competent person.
It may be that you have little or no knowledge of fire safety matters, it is recommended in
such cases that you seek assistance from a person competent to give advice in fire safety
matters.
The proforma provides space for a general statement of Policy, this is not a requirement of
the Workplace Fire Precautions Legislation but is required by other legislation. (Health and
Safety at Work Act 1974 Section 2(3)). If you already have a statement of policy recorded
elsewhere then this may be omitted.
A safety policy is a written statement of an employer's intent to ensure the safety of their
employees. The purpose of the safety policy is to give a clear unequivocal commitment to
comply with the relevant Regulations.
Example:
The company will provide and maintain safe and healthy working conditions, equipment and
systems of work for all employees and to provide such information, training and supervision
as they need for this purpose.
The company will give a high level of commitment to health and safety and will comply with
all statutory requirements".
Answer all questions in each section, making an entry in the appropriate column. Any
question attracting a NO response will require recording as a 'significant finding' on the
significant findings form.
1
SIGNIFICANT FINDINGS
Where significant findings are recorded, it will be necessary to take some form of remedial
action the proposed remedial action should be recorded on the significant findings form.
This form allows you to record the remedial action when completed.
PREMISES PLAN
Whilst there is no legal requirement to provide a plan of the premises you are encouraged to
do so. Drawing a plan of your premises will assist you to identify the fire precautions in
place and make a determination as to whether they are adequate, it will also allow the
assessor to identify whether any changes have been made since the last assessment.
• Escape routes, number of exits, number of stairs, fire resisting walls and
partitions, places of safety etc
• Fire safety signs and notices (ie pictographic fire exit signs, fire action notices
etc)
• The location of fire warning devices (ie break-glass alarm points, sounders, rotary
gongs)
• The location of emergency lights (to include hand held torches if provided)
• The location and type of firefighting equipment (ie water extinguishers, foam
extinguishers etc)
Furthermore, in case of fire, such a plan will be invaluable to the attending fire crews and
could as a result lead to reduced fire damage.
The purpose of this plan is to graphically demonstrate your emergency procedures. This Plan
may provide details of emergency shut off valves, high risk materials and processes, safe
evacuation routes, assembly points or any other information relevant in an emergency
situation. It may be satisfactory in the case of small and low risk premises to produce one
plan for both purposes.
The completed fire risk assessment should be reviewed regularly and when there is reason to
believe that the risk assessment is no longer valid.
2
BUILDING REGULATIONS AND OTHER ENFORCING AUTHORITIES
If, following your risk assessment there is a need to carry out structural alterations to your
premises or make changes that will affect the means of escape, you may need building
regulation approval.
Should this be the case, enquiries should be made to the Local Authority Building Control
Officer or an Approved Inspector prior to commencement of the work.
Other Enforcing Authorities may also require notification of changes to your premises eg for
residential care homes or the Fire Authority for premises having a Fire Certificate etc.
FURTHER ADVICE
If you intend to seek or are offered advice from a third party regarding the carrying out of a
fire risk assessment, you should remember that even after obtaining and considering that
advice, it is entirely your responsibility, based on your perception of any risks, whether or not
to act on it.
A copy of the fire risk assessment should be kept in the workplace and available for the
permanent workforce and their official representatives, and for the employees of other
employers who have access to the workplace.
Sources of ignition cannot be completely eliminated. Materials and substances that can be
ignited should therefore be controlled whilst in storage and use.
The following list should help you identify potential hazards in the workplace.
• Electrical wiring, plugs and sockets that are in poor condition, overloaded or
inadequately protected by fuses or other devices
3
COMMON CAUSES OF FIRE - Continued
• Carelessness by contractors
4
DETAILS
Name and Address of
Premises:
Postcode:
Use of Premises Factory/Office/Shop/Other:
Owner/Employer/Person in
Control of Workplace:
Telephone Number:
Date(s) of Fire Risk
Assessment:
SIGNED:
PRINT NAME:
DATE:
5
GENERAL DESCRIPTION OF THE PREMISES
Total number employed to work within the premises at any one time:
Total number of persons who may be on the premises at any one time:
Number of Floors:
Number of Stairs:
Fire Warning Systems (ie Break-Glass Systems, Automatic Fire Detection Systems to British Standard 5839, Rotary
Gongs)
Emergency Lighting (ie Non-Maintained, Maintained, 1 hour/3 hour Duration British Standard 5266, Hand-Held
Torches.)
6
FIRE RISK ASSESSMENT
N/A YES NO
(a) Is the entire electrical installation in good working order?
(b) Have all electrical systems and equipment been tested in
accordance with the Provisions of the Electricity at Work
Regulations?
(c) If the latest inspection shows work is necessary to make
systems and equipment safe, has this been carried out?
(d) Are records regarding regular testing of installation,
equipment and portable appliances up to date?
7
2 FIRE SAFETY - ELECTRICAL INSTALATIONS, APPLIANCES ETC
(Continued)
N/A YES NO
e) Is flexible electrical cable used safely (eg use kept to a
minimum and only in short lengths)?
(f) Are the electrical circuits free of any evidence of
overloading?
(g) Is electrical equipment (eg light bulbs/fittings and any
electrical heating appliances) kept well away from
combustible materials?
(h) Are staff aware that only trained personnel authorised by
management can make repairs or alterations to electrical
systems and equipment?
N/A YES NO
(a) Are all heating appliances safe (eg securely fixed in position,
suitably guarded and with an adequate clear space free from
storage of any kind)?
(b) Is the entire heating installation in good order?
(c) Are all cooking appliances safe (eg securely fixed in
position, properly maintained and used only for their original
intended purpose)?
(d) Are arrangements for liquid/gaseous fuel supplies for heating
and cooking equipment adequate (eg easily accessible with
well marked shut-off valves)?
(e) Are appropriately qualified/registered engineers used to carry
out all installation and maintenance of liquid/gaseous fuel
supply equipment?
(f) Are staff aware that only trained personnel authorised by
management can make repairs or alterations to liquid/gaseous
fuel-fired equipment and fuel supply systems?
N/A YES NO
(a) Are all fire/smoke barriers in good condition (eg with any
openings for pipes, ducts etc properly protected by provision
of fire-resisting materials or fire dampers)?
(b) Are fire dampers tested regularly for correct operation and
results recorded?
(c) Are there proper systems and procedures in place to control
work on new buildings and/or alterations, repairs and
decorations of premises, such that no fire hazards are
introduced?
(d) Are legal or other requirements for testing, maintenance and
record keeping complied with for such equipment such as
lifts, hoists, escalators, air handling systems, heating boilers,
pressure vessels etc?
8
5 MEANS OF ESCAPE
N/A YES NO
(a) Are fire exits sufficient (eg a sufficient number of adequate
width) to enable the number of people likely to be present in
all areas to evacuate safely?
(b) Do all final exits lead to a place of safety, such as a street,
passageway, walkway or open space? (not an enclosed yard)
(c) Are all final exits sited so that persons can disperse safely
from the vicinity of the building and the effects of fire?
(d) Are all fire exits readily available?
(e) Are all final exits and intermediate doors easily operable
from the inside without the use of a key?
(f) Are all corridors, gangways and stairways forming part of an
escape route free from obstruction and not used for storage?
(g) Are floor and stairway surfaces in good condition and free
from tripping and slipping hazards (including any external
stairs and pathways)?
(h) Are fire-resisting and smoke-stop doors in good condition,
with fully operating self-closing devices allowing the doors
to close fully onto their rebates and overcome the pressure of
the latching device? (which should extend at least 10mm into
the catch plate)
(i) Do all doors on escape routes open in the direction of escape?
(j) Are all escape routes clearly and properly marked with 'fire
exit' signage and where necessary are internal doors, not
forming part of an escape route suitably marked?
(k) Are all escape routes provided with adequate lighting at all
times when the premises are in use?
(l) Is adequate emergency lighting provided and is it fully
serviceable?
(m) Have appropriate provisions been made for the safety of
persons with disabilities eg assistance, refuges etc?
9
6 FIRE ACTION PLAN AND EMERGENCY EVACUATION (Continued)
N/A YES NO
(f) Have appropriate arrangements been made for ensuring safe
evacuation of those who are not normally on the premises (eg
visitors and contractors)?
(g) Are the fire evacuation assembly areas in safe locations, clear
of the building, in an open space, away from fire service
vehicular access and parking?
(h) Are there alternative evacuation areas available in the event
that the nominated ones are not available?
(i) Are emergency evacuation drills carried out at least once per
year?
NA YES NO
(a) Can a fire alarm be raised without placing anyone in danger?
(b) Is the fire alarm system in full working order?
(c) Are there fire alarm call points located near to every exit
from each floor and from each building?
(d) Are all alarm call points unobstructed and clearly visible?
(e) Are the audible signals from the fire alarm operated weekly
and clearly audible throughout the building?
(f) Have adequate arrangements been made to warn occupants in
the parts of the building(s) not under your control, but at risk
in case of fire?
8 FIREFIGHTING EQUIPMENT
NA YES NO
(a) Is there adequate provision of portable fire extinguishers
suitable for the risks present in the areas that they are
located?
(b) Are ALL portable fire extinguishers and fire blankets
suitably located, on securely fixed brackets and available for
immediate use? (not obstructed, hidden etc)
(c) Are the locations of ALL portable fire extinguishers and fire
blankets clearly identifiable?
10
10 FIRE SERVICE FACILITIES AND LIAISON
NA YES NO
(a) Is there adequate access to the site and all buildings to enable
Fire Service vehicles to get close enough for firefighting and
rescue purposes?
(b) Are all fire hydrants in the vicinity clearly indicated and
accessible?
(c) Is the Fire Service familiar with the premises?
11 ARSON
NA YES NO
(a) Are waste materials stored well away from any buildings?
(b) Has the premises been free from attacks by fire setters or
vandals?
(c) Have adequate security measures been taken to prevent
unauthorised entry to the premises and the site?
(d) Have appropriate measures been taken to reduce the risk of
arson?
N/A YES NO
(a) Are copies of the Fire Risk Assessment and the Emergency
Action Plan available on the premises?
(b) Are there procedures in place to ensure that the risk
assessment is reviewed periodically (sooner if alterations are
made to premises, processes etc)?
(c) Where the workplace is shared by more than one employer,
are you liasing in respect of fire precautions with other
employers?
(d) Are arrangements in place to ensure that other employer's
personnel working on the premises are provided with
adequate information on the fire risks within the premises?
11
14 FIRE PRECAUTIONS ACT 1971 (If your premises require a Fire Certificate)
N/A YES NO
(a) Where a Fire Certificate is in force, are the conditions of the
Fire Certificate being complied with?
(b) Is the Fire Certificate kept on the premises in a safe place?
(c) Where changes have been made to the building or its fire
precautions since the certificate was issued or last amended,
have the Fire Authority been advised?
If all answers to the questions above are either 'YES' or 'NA', your fire safety procedures are
likely to be adequate. Sign and date the form in the spaces below.
If one or more answers to the questions above are 'NO', your current fire safety procedures
may be inadequate. Sign and date the form in the spaces provided below and record all
deficiencies and proposed remedial action on the form entitled 'Significant Findings'.
Carry out any remedial action and enter details on the form entitled 'Review of Significant
Findings'.
Signature: ……………………………………………….
Date: …………………………………………………….
12
FIRE RISK ASSESSMENT
SIGNIFICANT FINDINGS
Item Section and Description of Unsatisfactory Persons at Risk Existing Control Measures (if any) Proposed Remedial Action
No Sub Paragraph Condition
13
Date Item Section and Remedial Action Date of Action Signature of Person
No Sub Paragraph Carrying Out Action
14
PREMISES PLAN
15