Chapter 1 Overview
1. Description
RC902- FE4E1, 10/100M auto-sensing Ethernet interface converter of Ethernet
to 4E1, is one product of RC series converters made by Beijing Raisecom Science &
Technology Co. ltd. It provides a simple solution to enable Ethernet access by using 4
E1 links for signal transmissions.
RC902-FE4E1 is modular device. It can provide central SNMP management
solution, when it is plugged in RC002-16 that is 16 slot chassis.
It can support remote management when it works in pair with RC901-FE4E1.
2. Specification
1)E1 interface:
RJ-45 (120 Ω, balanced)
Bit rate: 2048Kbps±50ppm
Line code: HDB3
Compliance: ITU-T G.703,
ITU-T G.823
Other features:
Real-time BER detecting and E1links auto protection auto-reset
Resistance for drift of 512UI, the ability of counteraction of jitter and drift
Selectable BER threshold of link auto-reset: 10-6 (default) or 10-5
3. Features
3
1)forward features
Maximum forward speed in each E1 link supports up to 1920Kbps
Maximum forward speed for 4 E1 link supports up to 1920×4=7680Kbps when fully
loaded
The forward bit rate is auto allocated, depending on the real-time status of E1 links.
2)Bandwidth auto-adjustment
RC902-FE4E1 supports 1~4 E1 links bandwidth auto-adjustment. If any of the E1
links disconnected, or when it is just back to normal from disconnecting, transmission
can be automatic achieved trough connecting E1 link and bandwidth can be adjusted
automatically, but at least 1 E1 link has to connect.
B D
LNK 100M
Indicator of
B D ACT Ethernet
Bolt
A C FDX
A C ETH
4
Red flash(RF): Port is receiving alarm indication signal (AIS) and ERR from the
sending device.
Yellow(Y): Link is disconnected due to the receiving of the error bits.
(CUT)
Yellow flash(YF): alarm due to remote device(RAL)but local port.
Off: Link is not in use
Note: If A,B,C and D all don’t be connected, four links are all red. If A link has been
connected, A link is green. Other link indicators are off. Then B link is
connected, B link is green automatically. Green means that normal status. And
so on.
5
Chapter 2 Connection features
1. Equipment interconnection
6
Chapter 3 Installation and test
1.Make sure the E1-link cables are compatible with the RC901-FE4E1
If the E1 links with which you want to connect RC901-FE4E1 are combined with
PDH or SDH equipments, please check the interface type of E1, definition and
impedance of interface in relevant manuals.
4. Environment
Temp: 0-45℃
Humidity: 5%~90% no condensing
5. Power supply
AC: 220v/50Hz Voltage 165~265V
DC: -48v Voltage -36~ -72V
Power consumption ≤ 3W
7
OFF
Chapter 4 Introduction of DIP-Switch
Remote loopback:
If any of E1 is linking with remote equipment (the indicator is green ),
network administrator can run the remote loop-back testing function (turn on the
switch no.1), enabling network operators to diagnose the E1 links though a Bit Error
Tester at a central location without sending a technician to the remote site. Ethernet
packets of both Local and remote site are isolated, can’t be forward to E1 interface.
8
E link Remote
Local A link A link
Ethernet Converter Ethernet
B link B link
Converter
C link C link
D link D link
Error tester
Error tester
Error tester
Local loop-back:
Local loop-back testing makes both local E1 and Ethernet signal loop-back
outward, this function is designed for testing equipment interface. Connecting E1 误
码仪 is for testing E1 interface; Sniffer is for diagnosing Ethernet interface. Note,
Ethernet data also loop-back during local loop-back, it easy to make broadcast storm
which occurred in Ethernet switches connected with local equipment. In case to avoid
broadcast storm, disconnect with switch before loop-back.
E1 link
A port
B port E1 误码仪
Sniffer
C port
D port
9
Ethernet operation mode
The Ethernet port is default as auto-sensing and provides auto MDI/MDIX
crossover function. If need change the status of port, please refer to the table shown
below for setting.
Connecting
equipment (NIC, Setting of Ethernet port of converter
switch etc.)
a. Enable auto-sensing (default) function, 100M full duplex
(common mode) will be obtained.
b. Disable auto-sensing function, force port to 10M half duplex
10/100M
mode. 10M half-duplex will be obtained.
Auto-sensing
c. Disable auto-sensing function, force port to 10M full duplex
port
mode. 10M full-duplex will be obtained.
d. Disable auto-sensing, force port to 100M half duplex mode.
100M half-duplex will be obtained .
10M
a. Disable auto-sensing function, force port to 10M half duplex.
Half duplex
10M half duplex will be obtained.
port
10M
Disable auto-sensing function, force port to 10M full duplex. 10M
Full duplex
full duplex will be obtained.
port
10M a. Enable auto-sensing (default) function, 100M full duplex will be
Auto-sensing obtained.
port
100M
a. Disable auto-sensing function, force port to 100M half duplex
Half duplex
mode. 100M half-duplex will be obtained.
port
100M
Full duplex a. ex-factory default function, 100M full duplex will be obtained.
port
a. Enable auto-sensing function (default), 100M half-duplex will
100M
be obtained.
Auto-sensing
b. Disable auto-sensing function, force port to 100M half duplex
port
mode. 100M half-duplex will be obtained.
Setting as shown:
OFF Ex-factory default
th th
setting 6 、 7 are
ON
67 OFF
OFF 10M half duplex OFF 10M full duplex
6th: ON 6th: ON
ON ON
67 7th: ON 67 7th: OFF
11
Chapter 5 Troubleshooting
If you meet some problem during installing and employing, please deal with
them by the following proposals. If there is no answering for the question, please
contact with distributors for technical support.
1.PWR indicator is down
Answering: PWR line is not connected or there is any error in the PS system.
5.No alarm show, LNK is light, ACT indicator keep winking. But the connection is
not working.
Please check work status of Ethernet port and networking device matching or not,
according to switch of front panel.
12