SIPROTEC 7SA82

Distance protection relay

www.siemens.com/siprotec

Description
The SIPROTEC 7SA82 distance protection has been designe
particularly for the cost-optimized and compact protection
of lines in medium-voltage and high-voltage systems. With
its flexibility and the powerful DIGSI 5 engineering tool,
the SIPROTEC 7SA82 device offers future-oriented system
solutions with high investment security and low operating
costs.
Main function Distance protection for medium-voltage
and high voltage applications

Tripping 3-pole, minimum tripping time: 19 ms


SIPROTEC 7SA82
Inputs and 4 current transformers, 4 voltage trans-
outputs formers, 11 or 23 binary inputs, 9 or 16 Functions
binary outputs DIGSI 5 permits all functions to be configured and com-
bined as required.
Hardware Different hardware quantity structures
flexibility for binary inputs and outputs are availa- • Minimum tripping time: 19 ms
ble in the 1/3 base module. Adding 1/6
expansion modules is not possible; • 6 independent measuring loops (6-system distance
available with large or small display. protection)
• Several distance-protection functions can be selected:
Applications
Classic,
• Detection and selective 3-pole tripping of short cir-
• reactance method (RMD), impedance protection for
cuits in electrical equipment of star networks, lines
transformers
with infeed at one or two ends, parallel lines and
open-circuited or closed ring systems of all voltage • Directional backup protection and various additional
levels functions
• Detection of ground faults in isolated or arc- • Detection of ground faults of any type in compen-
suppression-coilground power systems in star, ring, or sated or isolated electrical power systems using the
meshed arrangement following functions: 3I0>, V0>, fleeting contact,
• Backup protection for differential protection devices cos φ, sin φ, harmonic, dir. Detection of intermittent
of all kind for lines, transformers, generators, motors, ground faults and admittance
and busbars • Ground fault detection using the pulse detection
• Phasor Measurement Unit (PMU) method
Compact and reliable

• Adaptive power-swing blocking • Reliable data transmission via PRP and HSR redundan-
cy protocols
• Detection of current-transformer saturation for fast
tripping with high accuracy • Extensive cyber security functionality, such as role-
based access control (RBAC), protocolling security-
• Arc protection
related events or signed firmware
• Automatic frequency relief for underfrequency load
• Simple, quick and secure access to device data via a
shedding, taking changed infeed conditions due to
standard Web browser – without additional software
decentralized power generation into consideration
• Power protection, configurable as active or reactive • Phasor measurement unit (PMU) for synchrophasor
power protection measured values and IEEE C37.118 protocol
• Directional reactive power undervoltage protection • Time synchronization using IEEE 1588
(QU protection)
• Powerful fault recording (buffer for a max. record
• Detection of current and voltage signals up to the time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
50th harmonic with high accuracy for selected protec-
tion functions (such as thermal overload protection) • Auxiliary functions for simple tests and commission-
and operational measured values ing

• Ground fault detection using the pulse detection Benefits


method • Compact and low-cost distance protection
• Control, synchrocheck and switchgear interlocking • Safety due to powerful protection functions
protection
• Data security and transparency over the entire lifecy-
• Graphical logic editor to create powerful automation cle of the plant, saving time and money
functions in the device
• Purposeful and easy handling of devices and software
• Single-line representation in small or large display thanks to a user-friendly design
• Integrated electrical Ethernet RJ45 for DIGSI 5 and • Increased reliability and quality of the engineering
IEC 61850 (reporting and GOOSE) process
• 2 optional, pluggable communication modules, usable • Highest availability even under extreme environmen-
for different and redundant protocols (IEC 61850, tal conditions by “conformal coating“ (coating) of
IEC 60870-5-103, IEC 60870-5-104, Modbus TCP, the modular assemblies
DNP3 serial and TCP, PROFINET IO)
• Powerful communication components warrant safe
• Serial protection data communication via optical fi- and effective solutions
bers, two wire connections and communication net-
works (IEEE C37.94, and others), including automatic • Full compatibility between IEC 61850 Editions 1 and 2
switchover between ring and chain topology

For all products using


security features of
OpenSSL, the
Siemens AG following shall apply:
Energy Management Division This product includes
Freyeslebenstraße 1 software developed
91058 Erlangen, Germany by the OpenSSL
Project for use in the
SIPROTEC 7SA82 Profile E7.8.docx OpenSSL Toolkit
(www.openssl.org),
Printed in Germany | © 09.18 Siemens AG cryptographic soft-
ware written by Eric
E-Mail: [email protected] Young
Tel: +49 180 524 70 00 ([email protected])
and software devel-
oped by Bodo
Moeller.