Capsule Notes
Capsule Notes
5. Components of LT Switchgear:
SFU, MCB, ELCB, MCCB.
5.1 Miniature Circuit Breaker
The MCB has some advantages compared to fuse.
1. It automatically switches off the electrical circuit during abnormal condition of the network
means in over load condition as well as faulty condition. The fuse does not sense but
miniature circuit breaker does it in more reliable way. MCB is much more sensitive to over
current than fuse.
2. Another advantage is, as the switch operating knob comes at its off position during tripping,
the faulty zone of the electrical circuit can easily be identified. But in case of fuse, fuse wire
should be checked by opening fuse grip or cutout from fuse base, for confirming the blow of
fuse wire.
3. Quick restoration of supply can not be possible in case of fuse as because fuses have to be
rewirable or replaced for restoring the supply. But in the case of MCB, quick restoration is
possible by just switching on operation.
4. Handling MCB is more electrically safe than fuse. Because of to many advantages of MCB
over fuse units, in modern low voltage electrical network, miniature circuit breaker is mostly
used instead of backdated fuse unit. Only one disadvantage of MCB over fuse is that this
system is more costlier than fuse unit system.
If circuit is overloaded for long time, the bi - metallic strip becomes over heated and
deformed. This deformation of bi metallic strip causes, displacement of latch point. The moving
contact of the MCB is so arranged by means of spring pressure, with this latch point, that a little
displacement of latch causes, release of spring and makes the moving contact to move for
opening the MCB. The current coil or trip coil is placed such a manner, that during short circuit
fault the mmf of that coil causes its plunger to hit the same latch point and make the latch to be
displaced. Hence the MCB will open in same manner.
Again when operating lever of the miniature circuit breaker is operated by hand, that
means when we make the MCB at off position manually, the same latch point is displaced as a
result moving contact separated from fixed contact in same manner. So, whatever may be the
operating mechanism, that means, may be due to deformation of bi - metallic strip, due to
increased mmf of trip coil or may due to manual operation, actually the same latch point is
displaced and same deformed spring is released, which ultimately responsible for movement of
the moving contact. When the the moving contact separated from fixed contact, there may be a
high chance of arc. This arc then goes up through the arc runner and enters into arc splitters and
is finally quenched. When we switch on an MCB, we actually reset the displaced operating latch
to its previous on position and make the MCB ready for another switch off or trip operation.
If the voltage difference crosses, a predetermined limit, the current through the relay
becomes sufficient to actuate the relay for tripping the associated circuit breaker to disconnect
the power supply to the equipment. The typicality of this device is, it can detect and protect only
that equipment or installation with which it is attached. It cannot detect any leakage of insulation
in other installation of the system.
Single Phase Residual Current ELCB. The polarity of the phase winding and neutral
winding on the core is so chosen that, in normal condition mmf of one winding opposes that of
another. As it is assumed that, in normal operating conditions the current goes through the phase
wire will be returned via neutral wire if there's no leakage in between. As both currents are same,
the resultant mmf produced by these two currents is also zero-ideally. The relay coil is connected
with another third winding wound on the CT core as secondary. The terminals of this winding
are connected to a relay system.
In normal operating condition there would not be any current circulating in the third
winding as here is no flux in the core due to equal phase and neutral current. When any earth
leakage occurs in the equipment, there may be part of phase current passes to the earth, through
the leakage path instead of returning via mental wire. Hence the magnitude of the neutral current
passing through the RCCB is not equal to phase current passing through it.
Three Phase Residual Current Circuit Breaker or Current ELCB. When this difference
crosses a predetermined value, the current in the third secondary winding of the core becomes
sufficiently high to actuate the electromagnetic relay attached to it. This relay causes tripping of
the associated circuit breaker to disconnect the power supply to the equipment under protection.
Residual current circuit breaker is sometimes also referred as residual current device (RCD)
when we consider the device by disassociating the circuit breaker attached to RCCB. That
means, the entire parts of RCCB except circuit breaker are referred as RCD.
MCCBs are available with protection range from 50% to 100% of rated MCCB.
Ex –200A, TP MCCB can be used from 100A load to 200A in steps of 10% e.g. 110A, 120A,
130A, 140A, 150A, 160A, 170A, 180A, 190A & 200A. On every stage MCCB will provide
overload & short circuit protection.
Selection of MCCB –
It should be capable to carry the rated current of load, (Note: Rating of MCCB should not
be much higher than rated/full load current otherwise MCCB will not trip on fault).
Check number of poles – TP, TPN & 4P where
TP (for 3 phase load) = TP stands for Triple pole which means three phases (R,Y,B) & these
phases will be part of MCCB & neutral is not required for load. These 3 phases are opened &
closed with the operation of MCCB.
TPN (for 3-phase load) = TPN stands for Triple pole with neutral where three phases will be part
of MCCB & will be closed or opened with the operation of MCCB but neutral will be connected
directly with load & neutral will remain connected with load ,
4P (for 3-phase load) = 4P means Fore pole which means 3 phases & a neutral and all will be
part of MCCB. In this case, 3-phases &neutral will be part of MCCB &opened & closed with
MCCB operation.
Type of protection–According to Time Curve protection.
Fault current rating which should be in kA (thousand amperes) which means that a
MCCB can withstand the fault current of short circuit,
With operating Handle or without handle
Ex – 200A TP MCCB with 35kA fault current& operating handle.
CURRENT RATING OF MCCBs –
A typical range of Three phase MCCB – 100A, 125A, 150A, 200A, 250A, 315A, 400A, 630A,
(Note: MCCBs are available with 25-50KA fault level.)
As we can see it says AA LR6 1.5V. Now let us understand what does this name or code means.
Here
LR6 here is IEC size code as L stands for electrochemical series system i.e. for
alkaline/MnO2 battery and R6 stands for physical dimensions. An R6 configuration
means R-round battery with a maximum overall height of 50.5 mm and a maximum
diameter of 14.5mm.
AA is an ANSI designation for LR6 configuration batteries.
Consider another example of a button cell as shown below
It says CR2025. It is the IEC code in which C stands for Lithium system R for round-cylindrical
20 means 20mm diameter of battery and 25 represents the height of 2.5mm. For more
information refer to the ANSI and IEC codes for batteries.
5.4.1 Primary Cells or Primary Batteries
These cannot be recharged once decayed. The advantages of primary cells are compact
size and availability in various shapes like cylindrical, button, rectangular and prismatic, and
these have high power-density, long shelf life, low level of discharging and portability. Its
countless number of applications include watches, clocks, medical devices, radio and other
communication devices, nano applications, memory chips and many more.
If the primary cell does not contain liquid electrolyte then it is known as ‘dry cell’. A dry cell
contains moisten paste electrolyte. The figure above shows the cross-section of a Zinc Carbon
Battery.
Some of the different types of primary batteries and their applications have been discussed
below:
Zinc-Carbon/Alkaline/MnO2 Cell or Battery
One of the earliest forms of dry cell i.e. Zinc-carbon or Leclanche cell had been in use for almost
a century. But its now outdated with the commercial use of new primary batteries such as having
alkaline/MnO2 as a cathode which has higher capacity and higher energy density and longer
shelf life.
Mercuric Oxide Batteries
The usage of mercuric oxide batteries is very limited due to the hazardous implications of the
mercury to the environment. These batteries come as Zinc/cadmium anodes with mercuric oxide
as a cathode. It comes in cylindrical, small flat button forms. It finds applications as low power
sources in calculators, portable radios, watches, camera etc.
Zinc Silver Oxide Batteries
These are similar in design to mercuric batteries but have higher energy density. It works better
at low temperatures. Used mainly as button cell batteries and finds applications in photographic
equipment, electronic watches, hearing aids etc.
Zinc Air Batteries
Metal-air batteries have got attention in the battery industry due to its high energy density. Also,
no active cathode is required. However, its poor shelf life and sensitivity to external factors like
temperature, humidity etc limits its use. Its uses are in electronics, signalling and navigational
applications.
Lithium Batteries
The advantages of lithium batteries are the highest energy density, long shelf life and can be
operated over a wide temperature range. Its applications include cameras, watches, clocks,
calculators and other low power applications.
5.4.2 Secondary Batteries
These batteries are recharged again and again electrically once discharged. For example charging
of mobile or laptop batteries. Today secondary or rechargeable batteries are omnipresent. These
used as a standby power sources as in UPS, inverters and stationary energy sources on one hand,
and as a primary source for countless consumer applications like mobile, laptop, flashlight,
emergency lamps etc. Some of the types of rechargeable batteries and their applications can be
discussed below:
5.4.2.1 Lead Acid Batteries
These are the batteries commonly used in inverters, electric vehicles, engine ignition, emergency
power, and solar battery applications. It constitutes about 40-45% of the battery sale all over the
world. Given below are some of the types of lead-acid batteries based on the construction and
applications:
5.4.2.2 Starting Batteries
These are used to start engines, as they provide large impulse currents for a short period of time.
These have slow discharge rates. Applications are in aircraft, ships, diesel engine vehicles, etc.
5.4.2.3 Deep Cycle Batteries
Contrary to stationary batteries which have very low discharged, the deep cycle batteries go for
deep discharging up to 80% before recharging. There are three types of deep cycle batteries
namely flooded type, gelled electrolyte type and absorbed gas mat (AGM) type. Its applications
are in industrial trucks, golf carts, electric vehicles, mine cars, etc.
5.4.2.4 Submarine Batteries
Used in submarines. Its discharging fall between starting and deep cycle batteries, about 50%.
5.4.2.5 Stationary Batteries
It includes energy storage type batteries used in UPS, inverters, load levelling, and solar
Batteries, etc.
Static transfer switches when switching from mains to inverter power, will typically do this in
less than 5 mS. The battery is always kept at full charge by the rectifier and immediately
available for supplying power. Often a filter provides some power conditioning when supply
mains power to the load. A surge arrestor protects the UPS and loads from over voltage
conditions.
5.5.2 On-line (Double Conversion) UPS
In on-line mode, the load is always supplied via the inverter. The inverter normally takes it's
input from the mains, but will switch to the battery when the mains supply goes out of
tolerance. The static bypass will supply power directly from the mains in the event the inverter
is turned off or develops a fault.
A big advantage of on-line UPS is that the load is always supplied by the inverter and many
power quality issues on the mains are eliminated.
Single phase
The single phase requires two wires for completing the circuit, i.e., the conductor and the neutral.
The conductor carries the current and the neutral is the return path of the current. The single
phase supplies the voltage up to 230 volts. It is mostly used for running the small appliances like
a fan, cooler, grinder, heater, etc.
Three Phase
The three phase system consist four wires, three conductors and one neutral. The conductors are
out of phase and space 120º apart from each other. The three phase system is also used as a
single phase system. For the low load, one phase and neutral can be taken from the three phase
supply.
The three phase supply is continuous and never completely drops to zero. In three phase system
power can be drawn either in a star or delta configuration. The star connection is used for long
distance transmission because it has neutral for the fault current.
1. In single phase supply, the power flows through one conductor whereas the three phase
supply consists three conductors for power supply.
2. The single phase supply requires two wires (one phase and one neutral) for completing
the circuit. The three phase requires three phase wires and one neutral wire for
completing the circuit.
3. The single phase supplies the voltage up to 230V whereas the three phase supply carries
the voltage up to 415V.
4. The maximum power is transferred through three phases as compared to single phase
supply.
5. The single phase has two wire which makes the network simple whereas the three phase
network is complicated as it consists four wires.
6. The single phase system has only one phase wire, and if the fault occurs on the network,
then the power supply completely fails. But in three phase system the network has three
phases, and if the fault occurs on any one of the phases, the other two will continuously
supply the power.
7. The efficiency of the single phase supply is less as compared to three phase supply.
Because the three phase supply requires less conductor as compared to single phase
supply for the equivalent circuit.
8. The single phase supply requires more maintenance and become costly as compared to
three phase supply.
9. The single phase supply is mostly used in the house and for running the small loads. The
three phase supply is used in large industries and for running the heavy loads.
The star connection of the three phase allows the use of two different voltages (i.e., the 230 volts
and the 415 volts). The 230V is supplied by using the one phase and one neutral wire, and the
three phase is supply between any two phases.
Phase sequence:
It is the order in which the phase voltages will attain their maximum values. From the fig it is
seen that the voltage in A phase will attain maximum value first and followed by B and C
phases. Hence three phase sequence is ABC. This is also evident from phasor diagram in which
the phasors with its +ve direction of anti-clockwise rotation passes a fixed point is the order
ABC, ABC and so on. The phase sequence depends on the direction of rotation of the coils in the
magnetic field. If the coils rotate in the opposite direction then the phase voltages attains
maximum value in the order ACB. The phase sequence gets reversed with direction of rotation.
Then the voltage for this sequence can be represented as
Star connection:
the finishing ends or starting ends of the three phase windings are connected to a common point
as shown in. A’, B’, C’ are connected to a common point called neutral point. The other ends A,
B, C are called line terminals and the common terminal neutral are brought outside. Then it is
called a 3 phase 4 wire star connected systems. If neutral point is not available, then it is called 3
phase, 3 wire star connection.
Delta connection:
in this form of interconnection the dissimilar ends of the three coils i.e A and B’, B and C’, and
C and A’ are connected to form a closed Δ circuit (starting end of one phase is connected to
finishing end of the next phase). The three junction are brought outside as line terminal A, B, C.
the three phase windings are connected in series and form a closed path. The sum of the voltages
in the closed path for balanced system of voltages at any instant will be zero fig.
The main advantage of star connection is that we can have two different 3phase voltages. The
voltage that was the line terminals between A & B, B&C, and C & A are called line voltages and
form a balanced three phase voltage. Another voltage is between the terminals A & N, B& N,
and C &N are called phase voltage and form another balanced three phase voltage (line to neutral
voltage or wye voltage).
Relation between line and phase voltage and currents in balanced systems:
Star Connection
Delta Connection
IL = √3 Iph
House Wiring:
Introduction
Home wiring started when electric lights and telephone were first installed in homes
towards the end of the 19th century. By the end of the 20th century an increased variety of
systems were available for installation in homes. Therefore, Electrical service is considered
essential in modern homes.
The Figure 7.1 shows the typical electrical distribution to home at the service end.
Service Entrance: That portion of a home’s electrical system from the utility pole to the home’s
main electrical disconnect. The main electrical service disconnect is the circuit breaker that turns
all of the house’s electrical power off at one point.
Mast Head: The upper part of the metal conduit pipe, at the outside of the house, above the
electric meter, where the electrical service wires from the street attach to the house.
Neutral: The return conductor (white wire) of a circuit connected ultimately to the earth to
receive flow “back” from a light or appliance. Contact with neutral wire should not give you a
shock.
Drip Loop (at the service entrance): Slack in the overhead electrical entrance wires (at the
masthead) which prevents water from running down the service entrance wires and into the
electrical panel.
Conduit: A metal or plastic pipe through which electrical wires are run. Conduit protects wires
from damage and are usually used in exposed locations, such as along the outer surface of a
exterior house wall.
Busbar: A piece of rigid metal found in an electrical panel. A busbar distributes electricity from
the service entry cable to the various circuits by means of their connection to the busbar.
Breaker or Circuit Breaker: An automatic safety device that shuts off the electrical power
when the current (or amount of electricity or heat) becomes a greater volume of electricity
than the breaker is designed to handle.
Grounding: The process of connecting all home electrical devices, appliances and wiring,
whether intentional or accidental, so that they are connected to the earth, at the outside of the
house. This interconnected grid means that excess electrical current will seek and be absorbed by
the ground.
Distribution board
It is a safe system designed for house or building that included protective devices, isolator
switches, circuit breaker and fuses to connect safely the cables and wires to the sub circuits and
final sub circuits including their associated Live (Phase) Neutral and Earth conductors.
Distribution board is also known as “Fuse Board“, “Panel Board” or “Consumer Unit“. following
are the types of Distribution boards.
A distribution board unit installed in the buildings which firstly receive the incoming single
phase electric supply (AC low voltage (LV) (230V AC or 120V AC in US) from transformer
secondary through electric pole and energy meter or the distribution company’s electric service
provider outlets is known as Main Distribution Board.
The Distribution Board which is used to distribute electrical wiring and circuits within a selected
area in a building or house, i.e. floor in a multi storey building. The Sub distribution board is
connected and supplied from the Main Distribution Board through different wires and cables
rated according to the load requirement.
FDB = Final Distribution Board
The Distribution Board which provide electric supply to the Final and Sub Final Circuits is
known as Final Distribution Board. FDB (Final Distribution Board) directly connected through
SDB (Sub Distribution Board) and the final switches are used to control the connected electrical
devices and appliances such as light, air-conditioner, fan etc.
Below is old-school staircase wiring circuit diagram. Here we can control a bulb from two
different places by using two 2-way switches.
Working & Operation of Staircase Wiring – 2-Way Light Switching
Consider the above 2-way switch wiring diagram which has been used to control a bulb in
staircase. The schematic shows that circuit is completed and bulb is ON. Suppose you want to
OFF the bulb from the upper switch at top of stair ( (upper portion of staircase) ) simply Switch
OFF the switch then circuit will break and the bulb will be OFF. To switch ON the bulb again,
just switch ON the same switch at upper portion of staircase. In other words you can OFF and
ON bulb from upper switch at the top of stair. Obviously; you can perform the same operation
from the bottom switches installed in staircase.
Now, let’s see how we can do that from the other switch installed at the bottom of stair.Staircase
wiring diagram - How to control a lamp from two different places by two 2 way switches
For this purpose, consider the figure given above. In this case, you can see that circuit is
complete and bulb is ON. Suppose you want to OFF the bulb from the lower switch at bottom of
stair. Simply OFF the switch, then again circuit will break and the bulb will be OFF. You can
switch ON the bulb again to switch ON the same switch installed at the bottom or downstairs as
shown in the fig.
To get the switching position in ON condition for light bulb, the above operation is same as the
Exclusive-NOR (EX-NOR) logic gate truth table which is given below.
0 = OFF 0 = OFF 1 = ON
0 = OFF 1 = ON 0 = OFF
1 = ON 0 = OFF 0 = OFF
1 = ON 1 = ON 1 = ON
The starter is like a key of fluorescent light because it is used to light up the tube. When we
connect the AC supply voltage to the circuit, then the starter act like short circuited and current
flow through those filament (located at the first and second end of the tube light) and the
filament generate heat and it ionized the gas (mercury vapor) in the fluorescent tube lamp. So the
gas becomes electrically conductive medium. At the same time when the starter opened the
circuit path of two filaments from series connected, then the ballast release its stored voltage.
And it makes the fluorescent tube fully lighten. Now the starter has no job in the circuit, if you
open it from the circuit the fluorescent tube light will be still lighten, until you release the main
supply.
Tube light is not connected in the supply main directly. Although it operates at 230 V, 50 Hz,
some auxiliary electrical components are used to insert in this installation to support the tube
light operational principle. The total electrical components for single tube light installation are
Main parts of Fluorescent Tube Light:
1.Fluorescent Tube
2.Ballast
3.Starter
We need tube light, ballast, starter and fluorescent light holders to make wiring connection. The
fluorescent tube has two filaments with four terminals the starter is connected between two
filaments, the ballast is connected between main Ac supply and one filament in tube light.
Here another terminal in tube light is directly connected to the AC supply, to ionize the mercury
atoms in the tube light starter element is used, after the ionization operation of starter is does not
need for fluorescent lamp. the ballast employed to convert the AC supply frequency to high
frequency and the ballast regulates the supply given to the tube light.
This is a simple illustrated circuit diagram of ceiling fan. To be noted that the wiring diagram is
for AC 220V single phase line with single phase ceiling fan motor. Here a simple SPST switch is
used to supply power or not to the fan motor and a Regulator is used to controlling the fan speed.
Though it is very simple, but one thing to be noted that Switch and Regulator should be
connected with the phase line of main power, not neutral.
Ceiling fan has a “capacitor start motor” in its inside. AC single phase capacitor start motor has
two winding; one is starting winding and another is running winding.
As it is a capacitor start-capacitor run type motor; there a capacitor is used in series with
Starting Winding, It defines the direction of rotation. It is an electrolytic capacitor.