Illumination Computation: N 10

The document provides illumination requirements and calculations for various areas across 11 floors of a building. It lists the lux requirement, area, and calculated number of lamps needed for each space. Key areas include bank offices, food courts, stores, administrative offices, and a cinema requiring between 50-300 lux depending on the space. In total, it evaluates over 50 individual areas across the 11 floors.

Uploaded by

Jun Ry
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views2 pages

Illumination Computation: N 10

The document provides illumination requirements and calculations for various areas across 11 floors of a building. It lists the lux requirement, area, and calculated number of lamps needed for each space. Key areas include bank offices, food courts, stores, administrative offices, and a cinema requiring between 50-300 lux depending on the space. In total, it evaluates over 50 individual areas across the 11 floors.

Uploaded by

Jun Ry
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Illumination Computation: 1.

6 Foodcourt
Lux requirement: 200 lux
𝐸𝑥𝐴
N= Area: 16 m x 10 m = 160 m^2
∅ 𝑥 𝐶𝑢
200 𝑥 160
where: N = no. of lamps N= = = 10
3960 𝑥 0.6
E = desired illumination
A = area in m^2
2. 1ST FLOOR
∅ = luminous flux
2.1 Bank Office
1. GROUND FLOOR
Lux requirement: 250 lux
Area: 8 m x 10 m = 80 m^2
1.1 Bank Offices, Clinic, Server Room
Lux Requirement: 250 lux 250 𝑥 80
N= ==9
Area: 8 m x 10 m = 80 m^2 3960 𝑥 0.6

250 𝑥 80 2.2 Electrical Room


N= ==9
3960 𝑥 0.6 Lux requirement: 200 lux
Area: 8 m x 10 m = 80 m^2
1.2 Electrical Room, Maintenance Room
Lux requirement: 200 lux 200 𝑥 80
Area: 8 m x 10 m = 80 m^2 N= ==8
3960 𝑥 0.6

200 𝑥 80
N= ==8 2.3 Pharmacy 1 & 2
3960 𝑥 0.6
Lux requirement: 200 lux
Area: 8 m x 10 m = 80 m^2
1.3 Elevator Lobby
Lux requirement: 200 lux 250 𝑥 80
Area: 8 m x 8m = 64 m^2 N= ==9
3960 𝑥 0.6

200 𝑥 64
N= ==5 2.4 Conference Room
3960 𝑥 0.6
Lux requirement: 300 lux
Area: 16 m x 10 m = 160 m^2
1.4 Comfort Room
Lux requirement: 200 lux 300 𝑥 160
Area: 4 m x 8 m = 32 m^2 N= = = 20
3960 𝑥 0.6

200 𝑥 32
N= == 3 2.5 Admin Office
3960 𝑥 0.6
Lux requirement: 200 lux
Area: 14 m x 10 m = 140 m^2
1.5 Hallway (per 16 m^2 basis)
Lux requirement: 100 lux 200 𝑥 140
Area: 2 m x 8 m = 16 m^2 N= = = 10
3960 𝑥 0.6

100 𝑥 16
N= == 1
3960 𝑥 0.6
3. 2ND-4TH FLOOR & 6TH -10TH FLOOR 5. 11TH FLOOR

3.1 Store Rooms 1 – 10 5.1 Cinema


Lux requirement: 200 lux Lux requirement: 50 lux
Area: 8 m x 10 m = 80 m^2 Area: 16 m x 10 m = 160 m^2

200 𝑥 80
N= ==8
3960 𝑥 0.6 50 𝑥 160
N= ==4
3960 𝑥 0.6

4. 5TH FLOOR 5.2 Ticketing Booth


Lux requirement: 200 lux
4.1 Foodcourt Area: 8 m x 10 m = 80 m^2
Lux requirement: 200 lux
Area: 24 m x 10 m = 240 m^2 200 𝑥 80
N= ==8
3960 𝑥 0.6
200 𝑥 240
N= = = 20
3960 𝑥 0.6 5.3 Entertainment Area
Lux requirement: 300 lux
4.2 Foodstation 1 Area: 24 m x 10 m = 240 m^2
Lux requirement: 200 lux
Area: 14 m x 10 m = 140 m^2
300 𝑥 240
200 𝑥 140 N= = = 30
3960 𝑥 0.6
N= = = 12
3960 𝑥 0.6
5.4 Store Room 1-3
4.3 Foodstation 2-4 Lux requirement: 200 lux
Lux requirement: 200 lux Area: 8 m x 10 m = 80 m^2
Area: 8 m x 10 m = 80 m^2
200 𝑥 80
200 𝑥 80 N= ==8
3960 𝑥 0.6
N= ==8
3960 𝑥 0.6
5.5 Electrical Room
4.4 Staff’s Closet Lux requirement: 200 lux
Lux requirement: 200 lux Area: 8 m x 10 m = 80 m^2
Area: 8 m x 10 m = 80 m^2
200 𝑥 80
200 𝑥 80 N= ==8
N= ==8 3960 𝑥 0.6
3960 𝑥 0.6
4.5 Stockroom
Lux requirement: 200 lux
Area: 2 m x 10 m = 20 m^2

200 𝑥 20
N= ==2
3960 𝑥 0.6