ECP 11-0512d Schneider CE6 With Vip 300 Test Form
ECP 11-0512d Schneider CE6 With Vip 300 Test Form
Version: 3.0
Date: 09/07/2013
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Substation Name
Substation Number
Voltage
Switchgear
Switchboard Number Manufacturer Schneider
Serial Number Type CE6
Protection CTs
CT Ratio (400/1 or 800/1)
Relay
Serial Number Setting Range (x2 or x4)
HV Insulation Tests using Test Voltage from using Test Voltage from EOS 09-0001
For switchgear with dual ratio protection CTs select the appropriate ratio (see appendix A.4) to ()
give the required protection settings and record CT ratio on the front of the form
CT Ratio Terminal Block Connections
C112 - 2
400/1 C132 - 6 ()
C152 - 10
C112 - 3
800/1 C132 - 7 ()
C152 - 11
Relay CT Connections
Reconnect the CT wiring to the relay - use the x2 range unless the required setting current is greater than that
available within the range (Appendix A.5) and record the range on the front of the form
Range Relay Connections 200/1 CTs 400/1 CTs 800/1 CTs
C11 - 8
C31 - 6
x2 20-100A 40-200A 80-400A ()
C51 - 4
C71 - 2&9
C11 - 7
C31 - 5
x4 40-200A 80-400A 160A-800A ()
C51 - 3
C71 - 1&9
Ensure the reversible scale label matches the CT ratio and selected range ()
Measure the earth resistance between the relay case and the switchgear earth
Apply the following temporary settings to the relay (refer to Appendix A for guidance) ()
Overcurrent Settings Earth Fault Settings
Is 72A or 80A* Ios 60A or 64A*
I> curve SI Io> curve SI
DT only 3 DT only 3
t> 0.6 x10 to> 0.6 x10
I>> off Io>> off
t>> 0.03 to>> 0.03
* Available setting will depend on the CT ratio and the range being used. Note: It is not possible to carryout
the pickup test below for 800/1 CTs on the x4 range.
Increase current until the LED starts to flash and record the current value. Reset the relay and, if necessary,
close the circuit breaker before each test
Apply the in-service protection settings as specified by the planner/designer to the relay and
()
record them below – refer to Appendix A for guidance
Overcurrent Settings Earth Fault Settings
Is Ios
I> curve Io> curve
DT only DT only
t> Select from table to> Select from table
x10 / x1 on relay x10 / x1 on relay
CT Ratio
Primary Setting Current (Is) (Ios)
Secondary Setting Current
(Primary Setting Current ÷ CT Ratio)
2 x Secondary Setting Current
5 x Secondary Setting Current
I>>, Io>> x Secondary Setting Current (highset)*
DT x Secondary Setting Current (SEF)*
Connect timer circuit to auxiliary contacts L3 and L4 - contact closed when CB open ()
Overcurrent Test
2x A s s s s
5x A s s s s
Instantaneous A s s s s
2x A s s s s
5x A s s s s
Instantaneous A s s s s
SEF* A s s s s
* The trip current may have to be increased to operate the circuit breaker if the current is below the minimum
operating current.
Test Equipment
Certification ()
Comments
Commissioning
Signature Date
Engineer
This test form should be left on-site in a plastic wallet and in a secure location.
The VIP 300 is a self powered three phase overcurrent and earth fault protection relay. Protection
settings are displayed on the relay front panel (see section A.2) along with manual reset and trip
flags.
The CTs are connected to one of two sets of inputs to the relay, to give two different setting current
ranges. It is important to ensure that the correct scale label (see section A.3) is in place (either x4 or
x2) depending on the inputs and the CT ratio used.
Settings are applied by adjusting the dial selectors to the correct location using a screwdriver. Care
should be taken when applying the time settings as the VIP 300 does not use the time multiplier as
the time input for IDMT curves (t> or to>). Instead the table on the top right of the front panel
should be used to convert the required time multiplier to the VIP 300 setting depending on the IDMT
characteristic being applied. For definite time settings (DT, I>>, Io>>) the dials give the relay
operating time.
For example, to apply the following typical settings to a VIP 300 relay with 400/1 CTs:
OC 200A VI 0.1TM
SEF 32A DT 3s
Looking at the range cards for 400/1 CTs it can be seen that the x2 range provides the option for a
phase overcurrent setting (Is) of 200A and an earth fault setting current (Ios) of 32A, the x2 range
inputs should be used.
Warning
64 96 128 0.15 0.2
160 0.2 0.4
48 0.1 0.3 0.6
0.1
Io> 32 200
0.07 0.4 x 10 not time 0.05 0.9
16 240 multiplier
0.05 0.6 x1 0.03 1.5
8 320 280
(s) (s)
(A)
earth fault Ios to > see table to >> VAP6 test plug
Reversible scale label for Reversible scale label for Reversible scale label for
Ringmaster fitted with 200/1CTs Ringmaster fitted with 400/1CTs Ringmaster fitted with 800/1CTs
400/1
Ratio
800/1