Local Control Panel AC System
Local Control Panel AC System
04/01/18
1 OF 16
PANEL PANEL
DOOR LOCKS MTG. LUGS
(4Nos.) (4Nos.)
DEGREE OF PROTECTION IP-54
INDOOR TYPE APPLICATION
FABRICATION MATERIAL:- CRCA SHEET-2mm THICK
BUSBAR :- 100A TPN ALUMINIUM BUSBAR-50KA-1SEC.
TIC HIC
30 x 5mm AL. PHASE
30 x 5mm AL. NEUTRAL
30 x 5mm AL. EARTHING
COLOUR:- POWDER COATED RAL-7035
V A CABLE ENTRY:- BOTTOM
100A, TPN
MCCB
INCOMER
CHANGE OVER
SWITCH
100A TPN
04/01/18
BOTTOM VIEW
2 OF 16
R
Y
4.H.11
B
N
S1
S3 A
S5
S A
CT S
100/5A
CTS
CL-1
SHUNT
100A, TPN MCCB
TRIP
INCOMER
240V. AC
M1
CF-1-3 M2 M3
R 2A
R Y B
3 OF 16
R
Y
3.H.4 5.H.11
B
N
AS PER ANNEXURE-A
ATTACHED
C1 C2
32A 32A
TO HEATER
PANEL
PAC-1 PAC-2
11 TR/5.5 TR 11 TR/5.5 TR
14.2 kW/9.7kW 14.2 kW/9.7kW
4 OF 16
4.H.2 9.H.11
C5 C6 C7 C8
25A 25A 25A 25A
5 OF 16
PHASE
PLC
INTERLOCK
R
Y
B
N
PLC
STOP
MPCB-1 MPCB-2
24-32A 24-32A
C1 C2
32A 32A
PAC-1 PAC-2
11 TR/5.5 TR 11 TR/5.5 TR
14.2 kW/9.7kW 14.2 kW/9.7kW
TO
HEATER
PANEL
PAC-1 PAC-2
11 TR/ 11 TR/
5.5TR 5.5TR
6 OF 16
6.H.6
PHASE
PLC PLC C5 C6 C7 C8
PLC 25A 25A 25A 25A
STOP STOP STOP
COOLING COOLING
TOWER-1 TOWER-2
6.C.6
NEUTRAL
04/01/18
CONTROL CIRCUIT DIAGRAM
PUMP & COOLING TOWER FAN
7 OF 16
FLOW FLOW LEVEL LEVEL
SWITCH SWITCH SWITCH SWITCH
PACKAGE PACKAGE C/T-1 C/T-2
UNIT-1 UNIT-2
04/01/18
8 OF 16
5.H.2 11.H.10
DC POWER DC POWER
PS1 SUPPLY PS2 SUPPLY
24V. DC 24V. DC
9 OF 16
SIGNAL
FROM
FIRE
SYSTEM
TIC HIC
4 TO 20mA
TEMPERATURE
& RH SENSOR
04/01/18
10 OF 16
MCB-10A-3P
9.H.2
04/01/18
11 OF 16
PHASE
10.H.3
CONTROL SUPPLY
220V. AC
NEUTRAL
10.C.3
NL-1
04/01/18
12 OF 16
TERMINAL
220V.AC TO FIRE
TO C9 PANEL
C-1 PAC-1
+24V DC
PAC-1 FS
TO R3
+24V DC SPARE
C-5 PUMP-1 PAC-2 FS TERMINALS
TO R4
+24V DC
CT-1 LS
TO R5
+24V DC
C-6 PUMP-2 CT-2 LS
TO R6
PAC-PLC
INTERLOCK
C-7 COOLING PAC-PLC STOP
TOWER-1
PAC-PLC START
13 OF 16
LEGEND :-
- NC CONTACT
A - AMMETER
- CONTACTOR COIL
V - VOLTMETER
- PUSH BUTTON
- INDICATING LAMP LED TYPE
WITH NO LEMENT
- PUSH BUTTON
- PUSH BUTTON
WITH NC LEMENT
- CURRENT TRANSFORMER
- CT SHORTLINK TERMINALS
- AUTO / MANUAL
SELECTOR SWITCH
- AUX RELAY
- TPN MCCB
- HUMIDITY IND. CONTROLLER
HIC
- CONTROL FUSE
- TEMP. IND. CONTROLLER
TIC
- O/L RELAY
04/01/18
- NEUTRAL LINK
- NO CONTACT
14 OF 16
NMDC ELECTRICAL BOQ FOR AC BUILDINGS
S. NO. ITEM DESCRIPTION RATING MAKE QTY .
CHANGE OVER SWITCH TPN/4POLE 100 Amp. C&S/SCHNEIDER/L&T
1 1
WITH ROTARY HANDLE
MCCB TPN- (50KA FOR1Sce.) WITH 1C/O AUX.
2 CONTACT, TRIP CONTACT (LV510487) WITH OC 100 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 1
AND SC. THE EF IS AS ON S.No. 4.
3 SUNT TRIP 240V AC 240V. AC SCHNEIDER/L&T/BCH/ SIEMENS 1
EARTH FAULT RELAY WITH CBCT 100 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 1
5 ROTARY HANDLE FOR MCCB - SCHNEIDER/L&T/BCH/ SIEMENS 1
6 SPREADER TERMINALS FOR MCCB - SCHNEIDER/L&T/BCH/ SIEMENS 2-SET
7 MPCB, WITH 1NO+1NC FRONT CONTACT 24-32 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
8 MPCB, WITH 1NO+1NC FRONT CONTACT 4-6.3 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
9 MPCB, WITH 1NO+1NC FRONT CONTACT 1-1.6 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
10 MCB, 3-POLE 40/20 Amp. SCHNEIDER/L&T/SIEMENS 1
11 MCB, 3-POLE 10 Amp. SCHNEIDER/L&T/SIEMENS 1
12 MCB, 2-POLE 10 Amp. SCHNEIDER/L&T/SIEMENS 1
13 MCB, 2-POLE 6 Amp. SCHNEIDER/L&T/SIEMENS 2
14 MCB, 2-POLE 4 Amp. SCHNEIDER/L&T/SIEMENS 1
15 MCB, 2-POLE 2 Amp. SCHNEIDER/L&T/SIEMENS 3
CONTACTOR, 3-POLE (AC-3 DUTY) COIL 240V AC 32 Amp. SCHNEIDER/L&T/SIEMENS/BCH
16 2
WITH 2NO+2NC AUX. CONTACT
CONTACTOR, 3-POLE (AC-3 DUTY) COIL 240V AC 25 Amp.
17 SCHNEIDER/L&T/SIEMENS/BCH 5
WITH 2NO+2NC AUX. CONTACT
CONTROL (AUX.) CONTACTOR COIL 240V AC WITH 10 Amp. SCHNEIDER/L&T/SIEMENS/BCH
18 3
2NO+2NC CONTACT
19 SELECTOR SWITCH 2POLE, 2-WAY SALZER/KAYCEE 4
20 VOLT METER SELECTOR SWITCH SALZER/KAYCEE 1
21 AMP. METER SELECTOR SWITCH SALZER/KAYCEE 1
22 INDICATION LAMP CLUSTER TYPE-LED RED TECNIC/L&T/SIEMENS/BCH 10
23 INDICATION LAMP CLUSTER TYPE-LED YELLOW TECNIC/L&T/SIEMENS/BCH 6
24 INDICATION LAMP CLUSTER TYPE-LED GREEN TECNIC/L&T/SIEMENS/BCH 7
25 INDICATION LAMP CLUSTER TYPE-LED BLUE TECNIC/L&T/SIEMENS/BCH 1
26 PUSH BUTTON (SHROUDED) START -2NO SCHNEIDER/L&T/SIEMENS/BCH 4
27 EMERGENCY STOP PB (MUSHROOM HEAD) -2NC SCHNEIDER/L&T/SIEMENS/BCH 4
28 RELAY MODULE, 24V, 6-WAY/2C/O REPUTED MAKE 1
29 AMMETER ANALOGUE TYPE 100 Amp. AE/MECO 1
30 VOLTMETER ANALOGUE TYPE 0-500 V AE/MECO 1
1200 x 1250
31 PANEL VENUS 1
x 300
32 BUS BAR ALUMINIUM 50KA FOR 1Sec. 30 x 5 mm REPUTED MAKE 1-Lot
33 220 V. AC TO 24 V. DC SUPPLY 2 Amp. SCHNEIDER/SIEMENS 2
34 CT, CL-1 100/5 Amp. KAPPA/PRAGATI/REPUTED 3
35 CONTROL FUSE WITH BASE 2 Amp. CONNECT WELL/REPUTED 4
36 CT SHORTING TERMINAL REPUTED MAKE 4
37 FIRE DAMPER CONTROLLER SYSTEM AIR 2
38
TEMP./RH CONTROLLER WITH 4-20mA
96x96mm MASIBUS/PEPL/HONEYWELL/CHINO 2 04/01/18
RETRANSMISSION SIGNAL
39 NEUTRAL LINK REPUTED MAKE 4
40 WIRE FOR CONTROL CIRCUIT WIRING POLYCAB/KEI/BCH 200Mtr.
41 WIRE FOR POWER CIRCUIT WIRING POLYCAB/KEI/BCH 100Mtr.
42 TERMINALS CONNECT WELL/ WAGO/ELMEX 36
43 TERMINALS CONNECT WELL/ WAGO/ELMEX 69
44 LUG TERMINAL, INSULATOR PANEL HARDWARE - REPUTED 1-LOT
15 OF 16
NOTES:-
1. THE PANEL SHALL BE SINGLE FRONT, OPERATION & MAINTENANCE ON FRONT SIDE.
2. THE PANEL SHALL BE DUST & VERMIN PROOF. (DEGREE OF PROTECTION IP-54)
3. THE LOAD BEARING SECTION, FRAME SHALL BE FABRICATED OUT OF 2.0MM, NON LOAD
BEARING SECTION DOORS, COVERS & PARTITIONS SHALL BE FABRICATED OUT OF 2MM
THICK & GLAND PLATES SHALL BE FABRICATED OUT OF 3.0MM THICK MS. CRCA SHEET.
4. THE PANEL SHALL BE POWDER COATED RAL-7035
5. ALL DOOR & COVER WILL BE FULLY GASKET WITH NEOPRENE RUBBER.
6. ALL THE DOORS SHALL BE EARTHING WITH 2.5 SSQ.MM Cu. WIRE.
7. THE SIZES FOR THE WIRING SHALL BE AS FOLLOWS:-
(a) AC POWER WIRING (415V AC) - BLACK - AS PER RATING.
(b) AC CONTROL WIRING (230V AC.) -PHASE-GREY, NEUTRAL - BLACK - 2.5 SQ.MM. ,1100V.
(c) CT WIRING - GREY - 2.5 SQ.MM.
(d) EARTHING WIRING - GREEN - 2.5 SQ.MM.
8. ALL TERMINATING WIRE ENDS OF CONTROL WIRING SHALL BE PROVIDED WITH THE
SLEEVE AND FERRULE NUMBER ON IT FOR WIRE IDENTIFICATION.
9. INSPECTION & TESTING:- AS PER APPROVED QAP.
10. AREAS COVERED FOR ELECTRICAL PANELS BF,HM1,HM2,
LD,CH,OP,SP,SM,CO & RM BUILDING.
12. MPCB & CONTACTOR RATING SHALL BE AS PER TYPE 2 COORDINATION CHART.
13. 30% SPARE TERMINAL TO BE PROVIDED
04/01/18
16 OF 16
Contractor’s Order No. & Date: - HO(CONTRACTS)/NISP/PPDS-32/328/08/574, 10/09/14
Project Name: - NMDC/PPDS For 3.0 MTPA, Integrated Steel Plant, Nagarnar, Dist. - Baster.
ANNEXURE-A
MCB Rating For
S.No. Building/Area Heater Capacity Quantity
Feeder
1. BF Substation 10.0 kW 1 No. 40 Amp.
2. CH Substation 15.0 kW 1 No. 40 Amp.
3. CO Substation 8.0 kW 1 No. 20 Amp.
4. HM1 Substation 10.0 kW 1 No. 40 Amp.
5. HM2 Substation 16.0 kW 1 No. 40 Amp.
6. LD Substation 5.0 kW 1 No. 20 Amp.
7. OP Substation 5.0 kW 1 No. 20 Amp.
8. RM Substation 10.0 kW 1 No. 40 Amp.
9. SM Substation 8.0 kW 1 No. 20 Amp.
10. SP Substation 15.0 kW 1 No. 40 Amp.
Contactor
Item Description Capacity MPCB Rating
Rating
PACKAGE AC UNIT 11.0 TR 24 to 32 Amp. 32 Amp.
04/01/18