100% found this document useful (1 vote)
988 views

Anchor Bolt Calculation For Sign Post

This document summarizes the design of anchor bolts for a sign board foundation. It includes calculations of: 1) The weight of the sign board and supporting members totaling 13.6 kN. 2) The maximum wind speed and wind loads on the vertical pole and sign board of 5 kN and 27.1 kN respectively. 3) The maximum tension force on the anchor bolts under combined weight and wind loads, determined to be 710 kN, requiring bolts to withstand a tension of 177.5 kN each.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
988 views

Anchor Bolt Calculation For Sign Post

This document summarizes the design of anchor bolts for a sign board foundation. It includes calculations of: 1) The weight of the sign board and supporting members totaling 13.6 kN. 2) The maximum wind speed and wind loads on the vertical pole and sign board of 5 kN and 27.1 kN respectively. 3) The maximum tension force on the anchor bolts under combined weight and wind loads, determined to be 710 kN, requiring bolts to withstand a tension of 177.5 kN each.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Central Expressway Project -Section 2 – Package D Designed By : Asela

P06 VD1
Foundation Anchor Bolt Design of Sign Board for P14-VD4
Reference Calculations Output

3
Unit Weight of Steel = 7850 kg/m

900 7000

3000 1770 3000

∅ (mm) t (mm)
500.0 12.0
267.4 7.0
8550 89.1 3.2
- 3.0

1000

Weight of Elements
Vertical Post = ( 8550 + 3000 ) x ( pi() / 4) x (
500^2 - 488^2 ) x (1 / 10^9) x
7850 x (10 / 1000)
= 8.4 kN

Horizontal Beam - 2Nos =


2 x ( 900 + 7000 ) x ( pi() / 4)
x ( 267.4^2 - 260.4^2 ) x (1 /
10^9) x 7850 x (10 / 1000)

= 3.6 kN

Connection Beam - 2Nos =


2 x 1770 x ( pi() / 4) x (
89.1^2 - 85.9^2 ) x (1 / 10^9)
x 7850 x (10 / 1000)

= 0.1 kN

Sign Board = 2 x 7000 x 3000 x 3 x 7850 x


(1 / 10^9 ) x ( 10 /1000 )
= 9.9 kN

Page 1 of 5
Central Expressway Project -Section 2 – Package D Designed By : Asela
P06 VD1
Foundation Anchor Bolt Design of Sign Board for P14-VD4
Reference Calculations Output
Weight of Sign Board & Supporting
Members = 9.9 + 0.1 + 3.6
= 13.6 kN

Wind Load Calculation


Description Symbol Value Note
Unit

Basic hourly mean wind speed V b m/s 22.2 Ref. RDA Bridge Design Manual 2.2.6 Zone 3

Probability factor S p - 1.05 Ref. BS 5400 part-2 2006 5.3.2.2.2


Altitude in meters above mean Δ m Highest point on ground
125
sea level
S a =1+0.001Δ Ref. BS 5400 part-2 2006
Altitude factor S a - 1.125
5.3.2.2.3
Direction factor S d - 1.00 Ref. BS 5400 part-2 2006 5.3.2.2.4
V s =V b S p S a S d Ref. BS 5400 part-2
Site hourly mean wind speed V s m/s 26.2
2006 5.3.2.2
Bridge and terrain factor S b ' - 1.810 Ref. BS 5400 part-2 2006 Table3
Fetch correction factor K F - 0.921 Ref. BS 5400 part-2 2006 Table3
S b =S b 'K F Ref. BS 5400 part-2 2006
- S b - 1.667
5.3.2.3
Town reduction factor for sites
T g - 1.00 Ref. BS 5400 part-2 2006 5.3.2.3.2
in towns
Topography factor S h ' - 1.00 Ref. BS 5400 part-2 2006 5.3.2.3.3
S g =S b T g S h ' Ref. BS 5400 part-2 2006
Gust factor S g - 1.667
5.3.2.3
V d =S g V s Ref. BS 5400 part-2 2006
Maximum wind gust speed V d m/s 43.7
5.3.2.1
Dynamic pressure head q N/m2 1171 0.613xV d 2 Ref. BS 5400 part-2 2006 5.3.3
Drag coefficient for Vertical DvVd= 11>6 Ref. BS 5400 part-2
C dv - 0.70
Pole 2006 Table8
Drag coefficient for Sign Board C dsb - 1.1 Ref. BS 5400 part-2 2006 5.3.3.5 Table8

Solid area (Vertical Pole) A v m2 5.78 A v =D v (d +g )


A =S S
Solid area (sign board) A sb m2 21.00 sb w h

Wind load vertical pole P kN 5


yv qA v C dv Ref. BS 5400 part-2 2006 5.3.3
Wind load sign board P 27 qA C Ref. BS 5400 part-2 2006 5.3.6
ys sb dsb
kN

Page 2 of 5
Central Expressway Project -Section 2 – Package D Designed By : Asela
P06 VD1
Foundation Anchor Bolt Design of Sign Board for P14-VD4
Reference Calculations Output
Case 1 - Weight of Sign Board + Wind on Vertical Post

3.95 P=
13.6

650

W = 4.7 r=
650
11.60

M 24 Bolt Arrangement

Moment at Base M = 1.16 x 13.6 x 3.95 + 1.54 x 4.7


x 0.5 x 11.6
= 104.3 kNm

Tension Force of Bolt T = M/r


= 104.3 / 0.65
= 160 kN

Case 2 - Wind On Sign Board + Wind on Vertical Post

P = 27.1 650

r=
W = 4.7
650

11.60 10.05

M 24 Bolt Arrangement

Moment at Base M = 1.54 x 27.1 x 10.05 + 1.54 x


4.7 x 0.5 x 11.6
= 461.41 kNm

Page 3 of 5
Central Expressway Project -Section 2 – Package D Designed By : Asela
P06 VD1
Foundation Anchor Bolt Design of Sign Board for P14-VD4
Reference Calculations Output
Tension Force of Bolt T = M/r
= 461.41 / 0.65
= 710 kN

Maximum Tension Force on Bolts = MAX ( 160 , 710 )


= 710 kN
Maximum Tension Force Per Bolts = 177.5 kN
(Assume 4 no of bolts undergo tension)

Maximum Shear Force on Bolts, V = 1.54 x 27.1 + 1.54 x 4.7


= 49 kN
Maximum Shear Force Per Bolts = 49/12 kN
= 4.08 kN

2
Strength Py = 275 N/mm
Bolt Diameter d = 42 mm
BS 5950-1 No of Bolts = 4
:2000 Bolt Grade = 8.8
2
Table 32 Shear Strength Ps = 375 N/mm
Pbb 2
Bearing Strength = 1000 N/mm
Pt 2
Tension Strength = 560 N/mm

Maximum Tension Force = 710 kN


Maximum Shear Force = 49 kN

BS 5950-1 Tension Capacity (Per Bolt)


:2000 Pc = 0.8Pt * At
6.3.4.2
Tensile Stress Area At = pi() x (42 / 2)^2
= 1385.44 mm2

Pc = 0.8x560 x 1385.44 /1000


= 620.7 kN
> 177.5 kN
Hence OK

BS 5950-1 Shear Capacity (Per Bolt) P = Ps * As


:2000
2
6.3.2.1 Shear Area As = 1385.44 mm

P = 375 x 1385.44 /1000


= 519.5 kN
> 4.1 kN
Hence OK

Page 4 of 5
Central Expressway Project -Section 2 – Package D Designed By : Asela
P06 VD1
Foundation Anchor Bolt Design of Sign Board for P14-VD4
Reference Calculations Output
BS 5950-1 Bearing Capacity
:2000 Pbb = d*t*Pbb
6.3.3.2
Thickness of the Connected ply = 44 mm

Pbb = 42 x 44 x 1000 / 1000


= 1848 kN
> 177.5 kN
Hence OK

BS 5950-1 Bolts Subjected to Combined Shear & Tension


:2000
6.3.4.4 (Fs/Ps) + (Ft/Pt) < 1.4

( 49 / 519.54 x 4 ) + ( 710 / 620.68 x 4 )

0.31 < 1.4


Hence OK

Anchorage Length of Bolts


2
Concrete Grade = 30 N/mm
Provided Length = 900 mm
BS 5400-4 fb = 177.5 x 1000 / ( pi() x 42 x 900 )
2
:1990 = 1.49 N/mm
5.8.6.3
fbu = 0.28 √fcu
= 0.28 x sqrt ( 30 )
2
= 1.53 N/mm

fb < fbu

Hence provided Anchorage Length is Sufficient

Page 5 of 5