Measuring & Removing Moisture in Concrete
Measuring & Removing Moisture in Concrete
Before you coat concrete, you need to know how much moisture it contains
and how to remove the excess moisture.
By Don J. Schnell, Munters Corporation, Moisture Control Services
When protective coatings are applied to a steel substrate, there are a few basic rules to follow while preparing
the surface to assure good adhesion of the coating throughout its expected service life. Our industry has
clearly defined cleanliness standards and standards for the surface profile required for various coating types.
When these very measurable parameters have been met and the surface is free of contaminants, the coating
can be applied with predictable results.
With concrete surfaces, however, what is occurring below the surface is also a consideration. Excess moisture
is the cause for a large percentage of the coating failures on concrete. The configuration and structural integrity
of the concrete slab must also be considered. Cracks, control joints, and expansion joints must be addressed
properly. The potential for corrosion of the reinforcing steel must be considered and the designers and builders
must assure that moisture is not allowed to penetrate the concrete structure from the ground side.
Some of the characteristics of the concrete itself should be considered when choosing a coating type, scheduling
the project, and planning the pour and application. These considerations include cement ratio, pH, compressive
strength, permeability, contaminants below the surface, surface moisture, and moisture content.
This article will focus on the issues of moisture content. It will discuss the methods that are used to measure
the moisture found in a concrete structure and how excess moisture can be removed.
In this test, an 18-inch x 18-inch (450 millimeter x 450 millimeter) square of clear plastic sheet is sealed to the
surface with tape on all 4 sides. If, after 16 hours, any condensation is found on the underside of the plastic or
if the surface of the concrete is darkened, the concrete is considered too wet for coating application. In cooler
conditions, the concrete may retain its moisture and fail to condense on the plastic. However, an obvious
appearance of moisture in this method almost always indicates excessive moisture.
The standard also warns against allowing the sheet to come in contact with direct sunlight or excessive heat.
It is recommended that the surface temperatures and ambient conditions be within the established parameters
for application of the coating system. The reliability of the results of this test can be influenced by differences
in the temperature of the plastic sheet.
The plastic sheet method of measuring moisture is a quick, easy, non-destructive, and inexpensive way to
indicate excess moisture. It does not, however, provide any quantitative results, and it can easily result in a
“false positive” impression, failing to alert the applicator of an excess moisture condition.
data sheet
Montgomeryville, PA 18936
Ph 800-825-6566
Fx 215-855-4688
www.itwresintech.com
MEASURING AND REMOVING
Bulletin #312 moisture in concrete
The test is performed by sealing an insulated box to the concrete and measuring the relative humidity inside the box with a calibrated
capacitance-based humidity gauge. If the concrete is at 5 percent moisture content, it will neither absorb nor desorb moisture if the air
above it is 70º F (21º C) and 75 percent RH. Therefore, if the air inside the box measures less than 75 percent, it can be assumed that
the moisture content of the concrete is less than 5 percent. With the use of an insulated box, the air inside will assume a relatively stable
dry bulb temperature close to the temperature of the concrete. It is necessary to let the air in the box stabilize for 16 to 24 hours before
taking a reading.
Using relative humidity above the surface offers another non-destructive method of measurement at a relatively low cost. This method
is also easy to use and, unlike the sheet method, the results are quantified. When performed properly with calibrated instruments, the
test can yield accurate, repeatable readings. When a coating manufacturer specifies a maximum moisture content in a percentage, this
method will allow an applicator to insure that the concrete is within tolerance.
A variation of this method has been used to measure the content deeper in the concrete. A hole is drilled and a plastic plug is placed
in it. The probe of the humidity gauge is inserted into the plug and left to stabilize. RH readings are then taken as they would be in the
insulated box. The advantage is that the measurement is not affected by surface sealers, curing agents, or coatings on the concrete.
Heat generated by the drilling will dry the concrete around the hole. Therefore, the concrete around the hole must reach equilibrium
with the rest of the concrete before an accurate reading can be taken. The many hours that this could take can present a limitation on
this variation.
The common method for measuring vapor transmission uses a small dish of calcium chloride placed on the surface and covered with
a larger impermeable cover. The known quantity of salt is weighed after 72 hours and compared to its original weight to determine the
moisture gain. The results reflect the rate at which the moisture is desorbed from the concrete, expressed in pounds of water per 1000
sq. ft. (kilograms of water per 90 sq. m) per 24 hours.
After it has spent its allotted time absorbing moisture from the floor, the calcium chloride is normally purchased in a sealed container
and returned to the lab for weighing. This method offers excellent documentation at the cost of time and overnight mail.
Extremely wet floors can exhibit vapor transmission readings over 10 lbs./1000 sq. ft./24 hours (4.5 kg/90 sq. m/24 hours), and values
up to 22 lbs./1000 sq. ft./24 hours (9.9 kg/90 sq. m/24 hours) have been found. A value of 3 lbs./1000 sq. ft./24 hours (1.4 kg/90 sq.
m/24 hours) or less is believed to be acceptable to most coating and flooring manufacturers.
Two common instruments are used for spot readings to determine patterns in drying progress or relative readings throughout a structure.
These instruments are used in several ways. The most accurate test involves drilling holes into the concrete and filling them with
conductive gel. Two metal pins or nails are then set in the holes. Electrical conductivity is measured through the concrete bridge
between the gel, acquiring its name-gel bridge test. More often, two sharp spikes mounted on a single probe are driven into the surface
to get the conductivity reading at the surface.
Although this is a fairly accurate method of measurement for drywall or known species of wood, where the exact makeup of the material
is known, poured concrete is not nearly as consistent. Concrete’s conductivity is affected by voids, concrete mix ratios, aggregate type,
and aggregate size between the pins or spikes. Because it is impossible to know what is actually between the pins, the readings
obtained from these instruments are relative, rather than absolute, determinations of moisture content.
MEASURING AND REMOVING
Bulletin #312 moisture in concrete
Radio frequency instruments can be very useful as a reference to locate areas that wetter than others or to determine relative moisture
content. For example, many surface readings can be taken quickly to compare other areas of a structure to a sample of a known
moisture content.
It is important to distinguish between vapor transmission and moisture content. You may have an acceptable moisture content in the
concrete and encounter a failure later due to a continued vapor transmission through the slab. With a cold slab, you may experience
a low level of vapor transmission from a moisture-laden concrete structure. Both scenarios would warrant the application of 2 types
of testing to determine whether the concrete is ready to be coated.
For effective and accurate documented results, at least 2 measurement techniques should be used. The results can then be compared
for accuracy. Two methods that complement each other well are the radio frequency method and the calcium chloride method to verify
accuracy and provide documentation. As an added benefit, both are non-destructive.
When moisture in the concrete migrates to the surface or tries to escape after the coating has been applied, it can cause bubbling or
“fish eyes” in the coating. This is a form of what is called outgassing and normally occurs as the concrete is warming. After the coating
has cured, trapped moisture can cause coating disbondment as the moisture migrates to the surface and out of the concrete. These
vapor drive forces are very strong and can exceed the adhesion strength of the coating and the tensile strength of the concrete.
Water will migrate to the surface when there is a higher vapor pressure in the concrete than in the air above the surface. This condition
is common when a flooring is applied in a new building before the air conditioning is activated. As the building stabilizes, the air
conditioning lowers the vapor pressure in the building while moisture condenses out of the air.
Coating manufacturers have discovered effective methods of overcoming adhesion problems on damp concrete surfaces with the use
of various penetrating primers. Most manufacturers will agree, however, that a dry surface will certainly improve adhesion. There is no
question that excessive moisture in the concrete can create serious problems when it begins to migrate out of the concrete after the
coating is applied.
Coating application instructions often specify that the surface must be dry; sometimes they specify an allowable moisture content,
expressed in a percentage. What they fail to mention is how deep this dryness must be or if there is a maximum vapor transmission
rate allowable. There is an increasing awareness in the industry of these parameters. The flooring industry has shown a great deal of
concern over vapor transmission, generally agreeing that 3 lbs./1000 sq. ft./24 hours (1.4kg/90 sq. m/24 hours) Is an acceptable rate.
MEASURING AND REMOVING
Bulletin #312 moisture in concrete
Cutting a core sample completely through the slab will indicate if there is a vapor barrier and if the soil is saturated or immersed. In a
mature structure, a high reading or positive results from any of the tests mentioned above are good indications of chronic moisture
migration problems. Other good indicators of chronic moisture migration problems are ineffectiveness of continued drying processes
and resaturation of the concrete after drying. Conditions inside the building must always be considered. A cold floor with a temperature
below the dew point in the space will continue to take on moisture until it is saturated.
It is important to be aware of changing water tables. A slab that shows no sign of moisture migration can undergo total failure at any
point during its service life as a result of rising water tables or saturated soil. Obviously, the first line of defense against vapor
transmission from the soil is the placement of an effective and continuous vapor barrier under the slab. Although this is normally
required and installed, too often, the plastic membrane used is inadvertently punctured during the pour. If the integrity of the vapor
barrier is compromised, moisture migration into the slab can arise from heavy rains, higher than average seasonal rainfall, or altered
drainage patterns.
Solutions for chronic moisture transmission are controversial and expensive, and they have limited success. The most effective
method is always to remove the source of the water by improving drainage. In cases where the source cannot be eliminated, success
becomes difficult to achieve. Some solutions for which success has been claimed include the following.
PENETRATING SEALERS
This approach uses fluid-applied primers or sealants that create a vapor barrier at the surface. The moisture is not permitted to escape.
The challenged faced by the sealant is to withstand the force exerted by the moisture as it tries to leave the concrete. The adhesion
strength should be as great as the tensile strength of the concrete, and the permeability must be low enough to stop the water from
passing through the film. Some products, particularly in the flooring industry, are designed to allow limited amounts of vapor to pass
through the surface, maintaining transmission levels below 3 lbs./1000 sq. ft./24 hours (1.4kg/90 sq. m/24 hours). Often the hydrostatic
pressure or vapor drive will exceed the strength or adhesion of sealer products, limiting their effectiveness.
BREATHABLE COATINGS
On non-immersed surfaces when chemical or abrasion resistance is not a factor, breathable coatings can be a good option. Some
coating products will allow moisture to pass through freely without affecting adhesion or long term performance.
VENTILATION
It is important to ensure adequate air circulation in all drying applications. As moisture comes to the surface, air movement at the
surface will carry it away and promote further evaporation.
Evaporation rates will triple with a 5 mph (8 kph) wind velocity and increase another 60 percent at 10 mph (16 kph). A 20 mph (32 kph)
wind velocity at the surface of the drying concrete will promote evaporation at a rate 8.5 times that of a dead air space.4
MEASURING AND REMOVING
Bulletin #312 moisture in concrete
Most often, forced air heating is used to heat the space above the concrete and, through convection, heat the concrete. Good air
circulation will also aid in convection. A common mistake is to use direct-fired heaters to heat the space. Since moisture is a product
of combustion, and a direct-fired heater introduces the combustion product into the heated air stream, the dew point temperature in
the space is increased. This increase can be counter productive, causing condensation on the concrete surface or the ceiling above.
Radiant heat can be useful to raise the temperature of the concrete in small applications. In Europe, small microwave heaters have
also been used to spot dry concrete surfaces by warming the material.5
DEHUMIDIFICATION
For significant drying, the dew point temperature above the surface must be low enough for the water to migrate from the concrete
into the drier air.
In many instances, displacing the moisture-laden air with drier, outside air will be very effective in lowering the dew point temperature.
Colder climates offer an opportunity to utilize this option. In freezing temperatures, dew point temperatures are also very low. For
example, if the outside air is 30° F (-1° C) dry bulb and 70 percent relative humidity, the dew point temperature is just above 22° F (-
6° C). The cost of heating this air would have to be considered; however, heating could be useful in lowering the dew point in the space.
Bringing in outside air can be effective if one or more of the following conditions exist.
• The dew point temperature of the outside air is lower than the dew point temperature of the air in the building and lower than the
temperature of the concrete.
• The outside dry bulb air temperature is below 40° F (4° C), and the outside air can be heated.
• A longer period of time is available for drying.
Using outside air to dry concrete becomes less effective when ambient dew point temperatures are very high (above 50° F [10° C]), if
dry bulb temperatures are low and cannot be heated, or if air flow and air circulation are limited.
When ambient conditions are not present for the effective use of ventilation, the moisture in the space will have to be removed.
Dehumidification equipment has been used to remove the moisture from the air space.6
Desiccant dehumidifiers will return air to the space at a very low dew point and a higher temperature. When combined with good air
movement across the concrete surface, this equipment can provide the right combination of circulation, heat, and dry air needed for
the fastest practical drying combination.
Through the process of drying the air above the concrete, the moisture is removed as a vapor, not a liquid. Therefore, this technique
will be effective at any dry bulb temperature, achieving consistent results regardless of weather conditions.
This technology is used extensively and very effectively in the water damage restoration industry. Buildings of all types of construction
are completely dried with desiccant dehumidifiers after they have been flooded. These machines will lower the dew point temperature
in the building to a point where the moisture in the walls and insulation migrates readily to the surrounding air.
Combinations of desiccant dehumidification and cooling equipment are used to provide temperature control for occupied buildings
during the drying process.
To summarize, the drying process includes 4 major components, listed below in order of importance.
• Lower the dew point temperature of the air above the concrete.
• Promote rapid air movement across the surface.
• Raise the temperature of the concrete.
• Raise the temperature of the air around the concrete.
These components can be used alone or in combination, however, application of all 4 components will result in the fastest drying.
MEASURING AND REMOVING
moisture in concrete
The rates of extraction will vary as the concrete dries and moisture becomes less available. A monograph published by the
American Concrete Institute show a rough approximation of the relationships of the different conditions and their impact on the
drying rate of concrete.4
SUMMARY
Moisture continues to create application and performance difficulties for concrete coatings, and successful concrete applications rely
on an acceptable level of residual moisture. Several methods are available to measure moisture content, with a wide range of prices,
speeds, and qualitative results. A combination of 2 or more methods makes possible accurate, documentable results along with spot
readings for speed and confirmation of readings. Concrete dries most quickly when the dew point temperature is low, the concrete is
warm, and the wind velocity is high. Dehumidification has proven to be useful in promoting accelerated drying on projects requiring
high performance coatings for concrete.
REFERENCES
1. ASTM D 4263-83, Standard Test for Indicating Moisture in Concrete by the Plastic Sheet Method (Philadelphia, PA. ASTM, 1993
2. Lewis G. Harriman, "Drying Concrete" Construction Specifier (March 1995)
3. T. Kyle Greenfield, "Dehumidification Equipment Reduces Moisture in Concrete During Coating Application" Materials
Performance (March 1994)
4. Standard Practice for Curing Concrete (Farmington Hills, MI: American Concrete Institute, 1992
5. Private conversation with David Clifton, Munters Rotaire, Ltd., Huntingdon, Great Britain, 1997
6. Lewis G. Harriman, The Dehumidification Handbook (Amesbury, MA: Munters Cargocaire Engineering, 1990)
General: Every reasonable effort is made to insure the technical Information and recommendations on these data pages are true and the responsibility for determining suitability of products and appropriate use. ITW Resin Technologies’ sole liability, for breach of warranty,
accurate to the best of our knowledge at the date of issuance and are subject to change without notice. Products and information are negligence or otherwise, shall be replacement of product or refund of the purchase price, at ITW Resin Technologies’ election. Under no
intended for use by qualified applicators that have the required background, technical knowledge, and equipment to perform said tasks circumstances shall ITW Resin Technologies be liable for any indirect, incidental or consequential damages, even if advised of the
in a satisfactory manner. possibility of such damages.
Warranty:ITW Resin Technologies, a division of Illinois Tool Works Inc., warrants that its products meet their printed specifications. This is Modification of Warranty: No distributor or sales representative has the authority to change the above provisions. No change in the above
the sole warranty. This warranty expires one year after the shipment. provisions will be valid unless in writing and signed by an officer or the Technical Director of ITW Resin Technologies. No term of any
Warranty Claims: If any product fails to meet the above, ITW Resin Technologies will, at its option, either replace the product or refund purchase order shall serve to modify any provision of this document.
the purchase price. ITW Resin Technologies will have no other liability for breach of warranty, negligence or otherwise. All warranty Mediation and Arbitration: If any dispute arises relating to products or product warranties, either the purchaser or ITW Resin
claims must be made in writing within one year of date of shipment. No other claims will be considered. Technologies may a) initiate mediation under the then current Center for Public Resources ("CPR") Model Procedure for Mediation of
Disclaimer: ITW Resin Technologies makes no other warranty, express or implied, and specifically disclaims any warranty of Business Disputes, or b) initiate non-binding arbitration under the rules of the American Arbitration Association for the resolution of
merchantability or fitness for a particular purpose. Suggestions concerning use of products are not warranties. The purchaser assumes commercial disputes.