FMDS0776
FMDS0776
Table of Contents
Page
©2008-2017 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
7-76 Combustible Dust Explosion
Page 2 FM Global Property Loss Prevention Data Sheets
List of Figures
Fig. 1. Preferred locations for processes or equipment handling combustible dusts ................................... 6
Fig. 2. Schematic of rooftop explosion vents that project above the roof line ............................................. 8
Fig. 3. Rotary Air Lock ................................................................................................................................. 14
Fig. 4. Rapid-action valve (gate type) ......................................................................................................... 15
Fig. 5. Rapid action float valve (Ventix ESI ®) ............................................................................................ 15
Fig. 6. Explosion diverter .............................................................................................................................. 16
Fig. 7. Indoor installation of explosion diverter ............................................................................................ 16
Fig. 8. High-speed abort gate ...................................................................................................................... 16
Fig. 9. Example of duct explosion venting at an elbow .............................................................................. 22
Fig. 10. FM Approved flameless venting device (Photo courtesy of Rembe GmbH) ................................ 30
Fig. 11. Example of an enclosureless collector ........................................................................................... 37
Fig. 12. Powder bed processes ................................................................................................................... 40
Fig. 13. Material deposition processes ........................................................................................................ 40
Fig. 14. 3D printing and liquid processes .................................................................................................... 41
Fig. 15. SLS design concept (Chemical Engineering Progress, May 2014) ............................................... 41
Fig. 16. Industrial-scale 3D systems: ProX300 and Concept M2 Laser printers ........................................ 41
List of Tables
Table 1. Construction for Dust Handling Occupancies ................................................................................... 6
Table 2. Bucket Elevator Explosion Venting ................................................................................................. 24
Table 3. Typical Dust Bulk Density .............................................................................................................. 27
1.0 SCOPE
This data sheet describes recommended preventive measures to reduce the frequency of combustible dust
explosions, and protection features to minimize damage from a combustible dust explosion. The hazards
of dust fires can be found in other data sheets containing detailed occupancy specific recommendations.
However, an overview of loss history related to dust fires is included in this document.
This data sheet does not include dust explosion prevention and protection schemes unique to grain handling,
storage, and processing. Loss prevention recommendations for these occupancies are covered in Data Sheet
7-75, Grain Storage and Milling. However, recommendations in this data sheet do apply to hazards at grain
handling facilities that are not unique to those facilities.
The technology of dust explosion hazard evaluation is primarily discussed in metric (SI) units and those are
the units used in this data sheet.
This data sheet references software called DustCalc. DustCalc iproprietary software that has been developed
for use by FM Global engineers to size explosion vents for buildings and equipment where there is a
combustible dust explosion hazard. There are other vent sizing methodologies available but they are not used
by FM Global.
1.1 Changes
April 2017. Interim Revision. Recommendation 2.7.2.3 on protection of bucket elevators was modified for
clarity.
2.1 General
2.1.1 Treat all equipment that handles combustible dusts, as well as any rooms or buildings where combustible
dusts can be present and might be put into suspension, as having a dust explosion hazard.
2.1.2 Implement a management-of-change process in all facilities handling combustible dusts to be certain
that no changes occur that could increase the severity or consequence of an existing dust hazard or introduce
a dust hazard where none previously existed. Examples of such changes include the following:
• Adding new equipment such as blenders, grinders, cutting tools, dust collectors, cyclones, etc.
• Increasing temperatures in the process that could result in drier material being handled
• Adding new materials
• Changing product formulation by adding combustible materials or reducing the proportion of inert materials
• Making process changes that reduce the particle size of in-process materials
2.1.3 Where process, equipment, raw material, or product changes are planned that could significantly change
the dust properties, retest the dust for its explosibility.
2.1.4. Ensure your management-of-change process has the following minimum characteristics:
a) Provides a method for identification of changes that should be subject to the management-of-change
process
b) Provides documentation of the proposed change
c) Provides a formal analysis of the loss prevention considerations involved in the proposed change
d) Identifies the need for updated personnel training
e) Provides for communication of the change and the loss prevention consequences to appropriate
personnel such as maintenance, operators, safety, and emergency responders
f) Establishes any administrative procedures needed (documentation, checklists that cover hazards,
training, etc.)
g) Identifies any required authorizations
2.1.5 Where potential for a dust explosion exists, eliminate the potential or minimize the consequences using
one of the following methods:
a) Control fugitive dust releases using enclosures, collection systems and equipment design.
b) Locate dust producing operations in areas separated from different hazard occupancies by construction
(dust-tight and explosion-resistant barriers) or distance.
c) Minimize chances for dust accumulation by arranging building elements and equipment to reduce the
likelihood of dust accumulations. Employ features such as smooth, easily cleaned walls, boxed in or
covered horizontal surfaces (beams, joists, etc.), and surfaces sloped a minimum of 60° from the
horizontal.
d) Where fugitive dust release and accumulation exist in buildings, design the structure to safely vent
the potential explosion using damage-limiting construction.
e) Locate dust collection and transfer equipment outside, away from important buildings and utilities.
f) Construct equipment that processes or transfers combustible particles to contain or safely vent a
potential explosion.
g) Where explosion venting or containment in equipment is not possible, eliminate the oxygen in the system
by inerting, or install an explosion-suppression system.
2.1.6 Practice effective maintenance of production and protection equipment. An effective maintenance
program will:
a) Identify and eliminate fugitive dust sources continually.
b) Inspect, test and maintain spark detection and extinguishing systems, explosion isolation devices, and
relief vents to ensure they are in working order per manufacturer’s guidelines, or at least monthly.
c) Test and maintain metal and non-metal detection and extraction equipment to ensure they are in working
order, at least quarterly.
d) Check belts and rotating equipment for alignment at least quarterly to prevent these becoming a source
of friction heating.
e) Lubricate bearings and rotating equipment (fans, blowers, size-reduction equipment) in accordance
with manufacturer’s guidelines, or at least quarterly
f) Remove accumulated dust on rotating equipment bearings and components to ensure free movement
and prevent friction heating, at least quarterly.
g) Assign accountability and keep accurate records.
2.1.7 Ensure a comprehensive dust fire and explosion awareness program exists at all sites where
combustible dust exists either within closed processing systems or as fugitive dust within buildings. Include
the following:
a) Basic education to promote awareness and understanding of the hazards of combustible dusts
b) Instruction of new employees on the particular hazards and on precautions relevant to their departments
c) A minimum of annual instruction, drill, and familiarization of the local public fire service and/or internal
firefighting teams
d) Periodic refresher training for all facility personnel
2.1.8 Strictly control potential dust ignition sources where combustible dusts may be present.
a) Ensure all electrical equipment is rated Class II, Division 1 or 2, or Zone 20, 21, or 22 per NFPA 70,
the National Electric Code, Articles 500, 502, and 506, as appropriate, or international equivalent. (Refer
to Data Sheet 5-1, Electrical Equipment in Hazardous Locations, for additional details regarding area
classification and equipment selection.)
b) Use a hot work permit system to manage all hot work operations. (See DS 10-3, Hot Work Management,
and Hot Work Management Kit, P9601)
c) Prohibit smoking and open flames.
d) Provide grounding and bonding of metal components with a resistance of less than 1 x 106 ohms to
ground. (See DS 5-8, Static Electricity.) At least annually, check for continuity of the metal components and
security of any bonding connections.
2.1.9 Prohibit recycling of air material separator exhaust to buildings or rooms, except where either “a” or
all of “b through h” apply:
a) The return air duct discharges into an area that does not contain fugitive dust, combustible equipment
or storage, combustible construction, high-value equipment, or equipment that is critical to production,
OR
b) Install a filter downstream of the dust air separators that prevents return of dust to the enclosure with
a minimum efficiency of 99.9% at 10 microns AND
c) Install a device to measure pressure-drop across the filter with an alarm to indicate when the filter needs
to be cleaned or replaced AND
d) Provide support for the filter with a wire mesh screen or other method that allows the filter to withstand
a pressure equal to or exceeding the value of Pred for the piece of equipment directly upstream from it
AND
e) Provide explosion isolation between the building and the last dust collector in the system (the one
furthest downstream) AND
f) On explosion-isolation system activation, shut down any connected dust- collection equipment AND
g) Flammable vapors, gases, or hybrid mixtures are not involved AND
h) The dust-collection system meets the protection requirements in other sections of this data sheet.
Where these features are present, the recycling of air material separator exhaust would not cause the
building/room to require explosion protection features such as venting, etc. (other factors present in the
building/room could create that need, however).
2.2.1.3 Construct buildings in which a combustible dust hazard exists of noncombustible or FM Approved
Class 1 materials.
2.2.1.4 Ensure physical barriers that isolate dust hazard areas are sealed dust tight using noncombustible
materials. Where the barriers have a fire resistance, ensure the seals maintain that rating.
2.2.1.5 Use door seals, window seals, positive room pressurization, etc. to prevent dust from entering and
accumulating in adjacent areas that otherwise do not have their own sources of fugitive dust.
2.2.1.6 Ensure physical barriers that isolate dust hazard areas have explosion resistance sufficient to prevent
failure before the pressure can be safely vented.
2.2.1.7 Do not allow openings in explosion-resistant walls. Where openings cannot be avoided, keep all doors
in these walls normally closed and make sure they have the same explosion-resistance as the walls
themselves. (See DS 1-44, Damage-Limiting Construction, for design and installation of explosion resistant
doors and windows.)
2.2.1.8 Provide pressure resistance and vent area in accordance with calculations conducted using FM Global
DustCalc software.
2.2.1.9 In buildings where some fugitive dust is likely despite process design and equipment upkeep, arrange
building elements and equipment to reduce the likelihood and amount of dust accumulation by any or all
of the following, as appropriate:
a) Provide smooth interior walls with minimal ledges.
b) To the extent practical, provide horizontal surfaces such as girders, beams, ledges, and equipment
tops with a sloped cover having a smooth finish, to shed dust settling out of the air.
c) Slope covers at an angle of 60° from horizontal, unless a lesser slope is known to be sufficient.
d) Box in overhead structural steel that is out of the reach of normal vacuuming or sweeping operations
and that has horizontal ledges (such as Ibeams or Ushaped channels in the up or sideways position)
with a noncombustible material to eliminate pockets for dust accumulation.
2.2.2 Occupancy
2.2.2.1 Buildings can be considered as not having a combustible dust hazard if they contain combustible
dust-handling equipment that is designed and protected to control or safely vent an internal explosion, in
accordance with the pertinent sections of this data sheet.
2.2.2.2 Take any or all of the following steps, as needed, where quantities of fugitive dust could be expected
in new operations or are excessive in existing operations:
a) Survey process equipment to identify the sources of dust release.
b) Modify, repair, or replace equipment to eliminate or at least reduce dust escape.
c) Provide permanent vacuum pickup points at the locations that release dust, such as grinding, buffing,
bag dumping, open transfer points in conveying systems, and other equipment/locations where large
quantities of dust are liberated frequently. In some cases this may require construction of a ventilated hood
or containment enclosure for existing equipment.
d) Operate closed dust-handling systems under a slight negative pressure to reduce dust escape.
e) Conduct extra housekeeping in existing operations while equipment is being modified (see Section
2.2.4).
2.2.2.3 Existing buildings containing small, localized amounts (less than 5% of the building area and in no
case exceeding 1,000 ft2 [93 m2]) of fugitive combustible dust can be considered tolerable without explosion
damage-limiting construction, if the following conditions exist:
a) The fugitive dust escape and accumulation rate is very low, i.e., less than 1⁄16 in. (2 mm) for a dust
with an approximate bulk density of about 36 lb/ft3 (580 kg/m3) per three month period AND
b) The cleaning frequency is high enough to permit one scheduled cleaning to be missed without allowing
dust accumulations to reach the unacceptable level of 1⁄16 in. (2 mm) noted above.
2.2.3 Protection
2.2.3.1 Construct pressure-relieving and resistant walls in accordance with Data Sheet 1-44, Damage-Limiting
Construction.
a) Design the explosion vent relief pressure (Pstat) as low as the wind-resistance design will permit. In a
low-wind area, Pstat can be as low as 20 psf (0.01 bar), whereas in higher wind areas 30 to 40 psf (0.015
bar) is more typical.
b) Provide pressure resistance and vent area in accordance with calculations conducted using FM Global
DustCalc software.
2.2.3.2 Do not use explosion vents in the roof to provide explosion relief.
2.2.3.3 Where a thorough engineering study shows that explosion-venting walls alone cannot provide the
needed explosion venting area, roof vents may be used to provide a portion of the needed vent area if snow
and ice are not allowed to build up on the vent. Any of the following are acceptable methods:
a) Position the explosion vents at a minimum 60° angle, either on a roof pitched at that angle or as a
projection above the roof line (see Figure 2). For vents projected above the roof line, the effective vent
relief area to be used in vent sizing calculations is the smallest cross sectional area the combustion gases
would have to flow through.
b) Provide heat tracing along the perimeter and across the surface area of the explosion vent.
1. Leave heat tracing on permanently, or automatically actuate the system whenever the outside
temperature drops to 0°C (32°F) or lower.
2. Ensure the wiring for the heat trace cabling incorporates enough slack to allow the explosion vent
to deploy as intended.
3. Use FM Approved heat-tracing equipment.
c) Provide explosion venting panels without insulation to allow building heat to melt away snow or ice.
Expect condensation under the explosion vent and take measures to ensure condensation does not cause
problems.
Fig. 2. Schematic of rooftop explosion vents that project above the roof line
2.2.3.4 Where explosion venting devices swing out of the way rather than rupture, use gravity or mechanical
devices to ensure they cannot reclose. (3.1.9)
2.2.3.5 To prevent uncontrolled release of explosion vent panels where they could become missile hazards,
take the following steps:
a) Provide tethering cables to limit the vent movement.
b) Attach tethering cables to no more than two corners, making sure the tethered corners are adjacent.
c) To prevent the tethered panels from swinging back into the vent opening after the explosion, make
connections at the side or bottom of the panel rather than the top. This allows the panels to completely
swing out of the way of the vent opening, leaving an unobstructed path for the combustion gases to flow
along during the explosion, and for fresh air to flow into the protected enclosure after the explosion.
d) Set minimum tether length to that determined by the following equation:
l≥ axb
2 x (a+b)
where
l = length of tethering cables
a, b = side dimensions of explosion vent
e) Where the tether length is less than that determined above, consider the explosion vent as a hinged
panel when performing calculations to determine the vent area and vented explosion pressure (Pred). This
will account for the hindrance to the venting process created by the short tethers.
f) Where tethers are located at all four corners, this can be considered tolerable where the cable length
exceeds the minimum set in d, above. Any less and the vent area is restricted to the annular space
determined by the cable length and the dimensions of the panel, rather than on the size of the panel itself.
2.2.3.6 Do not attach sprinkler system piping to any wall, ceiling, or roof that could be displaced by the
pressure of a room or building explosion.
Any of these can increase effective vent-relief pressure (Pstat) and cause explosion-resisting walls to fail
and/or damage the building structure during an explosion.
2.3.1 General
2.3.1.1 Locate all equipment having an explosion hazard outdoors whenever practical (3.1.2).
2.3.1.2 Where equipment has an explosion hazard, take one of the following steps:
a) Eliminate the explosion hazard using any of the techniques detailed in Section 2.3.2,
OR
b) Mitigate the explosion hazard using explosion venting, suppression, containment, or vacuum operation,
or a suitable combination of these, as detailed in Section 2.3.3.
2.3.2.5 As an alternative to an inert atmosphere for handling freshly manufactured light metal powder
(aluminum, magnesium, titanium, zirconium) take the following steps:
a) Use wet collectors (water wash) rather than dry type.
b) Remove the accumulated sludge and dispose of it in a safe manner before shutting down the collection
system.
c) Continue collector ventilation at all times until the metal/water sludge is removed from the collector.
Aluminum particularly has a very low MIE (as low as 0.1 mJ) making it easily ignitable and metal powders
in general can have high Kst and be very difficult to provide adequate explosion venting. Aluminum powder
when damp with water can form small amounts of hydrogen so it needs to be kept wet at all times.
2.3.3.1 Venting
2.3.3.1.1 Provide a vent area in accordance with calculations conducted using FM Global DustCalc software
(3.1.4).
2.3.3.1.2 Where indoor equipment with an explosion hazard cannot be relocated outside, provide explosion
venting in one of the following ways:
a) Locate the vessel next to an exterior wall and vent the explosion to the outdoors via a short vent duct.
b) Vent the explosion to the surrounding area through an FM Approved flameless venting device into an
area without fugitive dust (3.1.5).
1. A vent area increase (compared to an open or unobstructed vent) will be needed to accommodate
reduced venting efficiency caused by the flameless venting device.
2. Use the venting efficiency for FM Approved flameless venting device as listed in the Approval Guide,
a publication of FM Approvals.
Where the above is not practical, implement other explosion hazard mitigation methods described in 2.3.1.2.b.
2.3.3.1.3 For calculations of vent area where equipment design strength data is not available, use the
following values of Pred (maximum allowable pressure) for normally constructed equipment with an
assumption that some vessel deformation may occur in a safely vented explosion:
a) Weak rectangular vessels (e.g., bag-type dust collector): 0.2 barg (2.9 psig)
b) Cylindrical vessels (e.g., cyclone) or strong (reinforced) rectangular vessels: 0.3 barg (4.4 psig) (3.1.6)
2.3.3.1.3.1 For vessels where deformation is not acceptable, obtain the design strength of the equipment
or assume 1⁄2 the values given above for Pred.
2.3.3.1.4 Set the explosion vent relief pressure (Pstat) as low as possible in accordance with the following
criteria:
a) Not exceeding 0.05 barg (0.7 psig) when vessel operates below this pressure, OR
b) At least 0.1 barg (1.4 psig) below the assumed Pred for higher operating pressure
2.3.3.1.5 For calculations of vent area where equipment design strength data is available, set the value of
Pred according to the following criteria:
a) Where vessel deformation is acceptable, use a value equal to twice the design strength.
b) Where vessel deformation is to be prevented, use a value equal to the design strength (3.1.6).
2.3.3.1.6 Construct explosion vents of material that is as light in weight (mass per unit area) as possible to
minimize the vent area required. Explosion vents that are rupture membranes (e.g., prefabricated rupture
disks, aluminum foil, etc.) have virtually no inertia, and require no adjustment to the required explosion vent
area (3.1.7).
2.3.3.1.6.1 Where venting devices are heavier than light-weight membranes, calculate the effect on the vent
area using FM Global DustCalc software.
2.3.3.1.7 Install vent ducts that redirect the combustion products from the vent to a safe area in accordance
with the following:
a) Route the vent to a safe outdoor area.
b) Permit no bends in the duct.
c) Limit the length to diameter ratio (L/D*) of the duct to 1.
d) Ensure the vent duct is at least as strong as the Pred design of the vessel.
e) Permit no closures on the discharge end of the duct that obstruct the free venting of the discharged
material.
f) When the above conditions cannot be met, quantify the effect on the vent area using FM Global DustCalc
software (3.1.8).
* calculate the equivalent diameter (Deff) of a non-circular duct as follows:
√
4Ad
Deff =
π
2.3.3.1.8 Where a wire mesh screen or other obstruction is to be provided between an explosion vent and
the free atmosphere, adjust the effective area of the explosion vent for the reduction in venting efficiency
as follows:
a) If the screen or obstruction is less than 15% of the explosion vent area, no adjustment is required.
b) If the screen or obstruction is between 15% and 40% of the explosion vent area, calculate the effective
explosion venting area using:
a) If there is a distance of at least one explosion vent diameter between the end of the duct and the weather
cover, there is no effect on efficiency.
b) If the distance is between 1⁄4 and 1 explosion vent diameter, consider the weather cover as a 90° bend
in the vented flow when calculating the effect of the vent duct.
c) A distance of less than 1⁄4 explosion vent diameter away from the vent duct is unacceptable unless it
is designed to fly off in the event of an explosion.
For non-circular ducts, use the hydraulic diameter for these calculations (2.3.3.1.12).
2.3.3.1.14 Do not provide explosion venting if the dust or its combustion products are poisonous, radioactive,
corrosive to nearby equipment or structures, or for any other reason should not be released from an otherwise
closed system. Use alternatives to venting, such as explosion hazard elimination, explosion suppression,
explosion containment, or high vacuum operation.
2.3.3.1.15 Where a vessel requiring explosion venting contains significant obstructions to the free flow of
gases, provide several distributed vents at different places on the vessel rather than one large vent of the
same area (3.1.12).
2.3.3.1.16 Where a vessel contains both suspended combustible dust and ignitable liquid vapors or flammable
gases (a hybrid mixture), the reactivity of the mixture will require larger vent areas than the combustible dust
on its own.
a) The presence of a flammable vapor or gas can be ignored if the concentration is at or below 5% of
its Lower Explosive Limit (LEL).
b) Where the gas concentration exceeds 5% of its LEL, determine the reactivity of the mixture by testing.
2.3.3.1.17 The required explosion venting area for a vessel with a dust explosion hazard operating at
pressures exceeding 0.1 barg (1.5 psig) requires special consideration and needs to be carefully analyzed.
FM Global DustCalc software can handle initial pressure up to 4 barg (58 psig) for full-volume explosions.
a) Set the vent-relief pressure, Pstat above the normal maximum operating pressure by at least 0.1 barg
(1.5 psig) (3.1.13).
b) Obtain vent sizing criteria from experts familiar with high initial pressure venting.
2.3.3.1.18 Recoil forces from the venting of an explosion can dislodge even large vessels that are not properly
anchored. Implement one of the following to control recoil forces:
a) Provide equal-sized vents at opposite sides of the vessel.
b) Calculate the magnitude and duration of the dynamic recoil force (or an equivalent static force) from
a vent, and provide anchorage to resist those forces (3.1.10.3).
2.3.3.2 Isolation
Avoid multiple pieces of interconnected equipment containing a dust explosion hazard. Properly protected
equipment can fail when an explosion propagates from another piece of equipment. Isolation systems can
prevent that condition (3.1.14).
2.3.3.2.1 Provide explosion isolation on all connections of vessels (or vessel groups) designed to contain
the explosion pressure (explosion-resistant design).
2.3.3.2.2 Provide explosion isolation on all connections between vessels (or vessel groups) individually
protected by explosion venting (or other mitigation method) but subject to unacceptable property damage
or business interruption by a propagating event.
2.3.3.2.3 Design mechanical isolation devices on equipment designed to contain the explosion based on
the vessel design pressure and isolation devices on equipment protected by explosion venting to resist the
design reduced pressure (Pred). This includes rotary air locks, rapid action valves, flame front/explosion
diverters, high speed abort gates, double-dump valves and back-blast dampers
2.3.3.2.4 Ensure active isolation devices requiring detection for mechanically activating the device are
sufficiently separated that the device will close before the flame arrival.
2.3.3.2.5 Piping used for dense phase pneumatic conveying of combustible dusts usually presents no hazard
of explosion propagation. Piping can be installed without explosion isolation devices if the conveyed material
is not metal dust or a hybrid mixture.
2.3.3.4 Suppression
2.3.3.4.1 Where explosion suppression is the chosen explosion hazard mitigation method:
a) Install explosion suppression systems in accordance with Data Sheet 7-17, Explosion Protection
Systems.
b) Install FM Approved equipment in accordance with its listed limits of application.
2.3.3.5 Containment
2.3.3.5.1 Where explosion containment is the chosen explosion hazard mitigation method, use the explosion-
resistant-design method. Existing, shock-resistant vessels are tolerable for providing explosion containment.
a) Explosion-resistant design is any vessel with a design pressure of 6 barg (87 psig) or more that would
not be deformed by a dust explosion that occurs at an initial (pre-explosion) pressure of less than 0.1
barg (1.5 psig).
b) Shock-resistant design is any vessel having 3 barg (43 psig) design pressure or more when designed
in accordance with ASME Boiler and Pressure Vessel Code, Section VIII, or yield strength of 6 barg (87
psig) or more according to other codes. With this design, the vessel may deform but not rupture in the
event of a dust explosion that occurs at an initial (pre-explosion) pressure of less than 0.1 barg (1.5 psig).
c) To prevent damage to other equipment connected upstream and downstream of the vessels protected
by explosion containment, provide explosion isolation.
b) Any mechanical milling equipment with connected equipment such as a downstream cyclone
(exceptions: coal pulverizers and human food-product milling are not considered to have a high frequency
of explosions for the purposes of this recommendation.)
c) Processes that routinely produce sparks or glowing embers (e.g., due to grinding or friction) that can
enter a dust-collection system
d) Any process or system that has experienced two or more explosions within a 10 year period
2.3.4.2 To minimize dust-cloud ignition due to static electricity accumulation and discharge, implement the
following:
a) Apply all applicable recommendations in Data Sheet 5-8, Static Electricity, to minimize the probability
of ignition.
b) If possible, use metal piping and ductwork, properly grounded and bonded, to transfer combustible
dust.
c) If plastic piping or ductwork is used to transfer material, grounding and bonding is ineffective because
of the insulating properties of plastic. However, if conductive or metal components are present in such
systems, for example plastic pipe or hose connected to metal piping, these conductive components do
need to be provided with proper grounding and bonding.
d) If materials are very easily ignitable (minimum ignition energy less than 10 mJ), consider the following
options to reduce the chance of static ignition:
1. Operate any equipment that presents an explosion hazard under an inert environment (see 2.3.2.4)
(3.1.19).
2. Operate at a pressure of less than 0.1 bara (1.5 psia).
3. Eliminate the ignitable mixture by operating at no more than 50% of the MEC.
4. Reduce charge generation or accumulation with process changes such as reducing the flow rate
of the transferred material.
5. Provide static eliminators or neutralizers. Ensure they are firmly fixed, well grounded, properly
adjusted, and kept clean of foreign accumulations.
6. Have someone with special expertise evaluate the situation and develop an appropriate course of
action.
2.3.4.3 Provide magnetic separators upstream of all size-reduction equipment e.g., grinders, pulverizers,
hammer mills, or other equipment involving mechanical impact with the process material (3.1.20).
2.3.4.3.1 Separators other than magnetic (e.g., air separators, grates, coarse screens) may be used if
nonferrous metal or other objects (e.g., rocks) could enter the product stream and cause an ignition hazard.
2.3.4.4 Fans and blowers in the fugitive dust-air stream can become an ignition source. Install these devices
as recommended below:
2.3.4.4.1 In negative pressure systems, locate the fan on the discharge side (i.e., clean side) of the dust
collector.
2.3.4.4.2 In positive pressure systems, locate the blower upstream of the dust injection point.
2.3.4.4.3 Where, for design reasons, the fan must be located in the dirty air stream, and the dust/air stream
concentration is higher than the 25% of the MEC:
a) install fans and blowers of Type A or B spark-resistant construction per AMCA 99-0401-86,
Classifications for Spark Resistant Construction
b) Ordinary fans and blowers may be used in a dust-air stream of unlimited concentration if the dust has
been shown by test to be hard-to-ignite.
2.3.4.4.4 Ordinary fans and blowers may be used in a dust-air stream of unlimited concentration if the dust
has been shown by test to be hard-to-ignite.
2.3.4.4.5 Systems handling wood dust can use ordinary fans upstream of bagtype dust collectors if a cyclone
collector (primary dust collector) is upstream of the fan.
2.3.4.4.6 Ordinary fans and blowers may be used if a high-speed abort gate or FM Approved spark-
extinguishing system is provided between the fan and any important or valuable downstream equipment.
2.3.4.5 Prevent materials subject to spontaneous heating from becoming an explosion initiation source by
implementing the following:
a) Prevent accumulation in ductwork by maintaining sufficient transport velocity.
b) Prevent accumulation in equipment by performing frequent cleaning.
c) Do not allow moisture to contact such material; however, automatic sprinklers or spark-extinguishing
systems can be used in ducts, when needed.
d) Clean collectors handling residues subject to spontaneous heating daily or as needed to prevent heating
and hazardous accumulations.
2.3.4.6 Avoid using mechanical drives with high rpm or power as they can cause dust ignition due to heat
generated by friction or sparks.
2.3.4.6.1 Use the following guidelines to determine the potential for hazardous conditions based on the
tangential velocity (v) of the rotating component:
a) When v < 1 m/s (3.3 ft/s): there is no danger for ignition.
b) When 1 < v < 10 m/s, (3.3 < v < 33 ft/s): judge each case separately considering the product and material
specific characteristics such as MIE and particle size (for each, the lower value will tend to be more
susceptible to ignition).
c) When v > 10 m/s (33 ft/s): there is always an ignition potential.
Note: To convert rpm to tangential velocity, use v = rpm x 2πr x 1/60, where
v = length (same units as r) per second
r = length of the rotating part, from shaft center to outer tip
2.3.4.6.2 Where low-velocity, high-power equipment is used, usually in grinding operations or screw
conveyors and blenders, the potential for uncontrolled heating due to excessive residence time,
accumulations at bearings, foreign objects, etc., needs to be considered and protected against by using shear
pins, overload detection and alarm, proper maintenance and cleaning, and screens and separators.
where:
m) Fans or blowers located in the dirty air stream are installed per Section 2.3.4.4
n) Ordinary electrical equipment is not present within 10 ft (3 m) of the collector system
o) The fan or blower motor, not located in the dirty air stream, is suitable for Class II, Division 2, or Class
III, (Zone 22) as appropriate.
2.5.1 Occupancy
2.5.1.1 Control the dust concentration in a fugitive-dustcollection system to prevent a continuous, explosible
atmosphere from developing in the duct using the following methods:
a) When the dust-generation rate is variable, keep the dust below an average concentration of 25% of
the minimum explosible concentration (MEC). Limit peak dust-emission rates above 100% of the MEC for
only a few seconds at any time.
b) When the dust-generation rate is steady without significant peaks, keep the dust concentration to no
more than 90% of the MEC.
2.5.1.2 Where the concentration in a duct regularly exceeds the MEC, provide protection for the additional
in-duct explosion hazard (2.5.2.3).
2.5.1.3 In ducts transporting combustible dusts, maintain an air velocity that exceeds the settling velocity
for the material being transported.
Note: The velocity for typical industrial dusts (e.g., saw dust) can be from 3500 to 4000 ft/min (1070 to 1220
m/min). Where the settling velocity of a material is unknown, consult Data sheet 7-78, Industrial Exhaust
Systems, for generic transport velocity recommendations.
2.5.2 Protection
2.5.2.1 On ducts containing combustible dust in concentrations that are always less than the MEC and that
carry dust at velocities where dust settling out is unlikely, provide explosion-isolation devices as follows:
a) On connections to important pieces of equipment
b) On duct running back to buildings that contain expensive equipment or important processes that could
be damaged, that might contain fugitive dust.
If the value of MEC is not available, an estimate of 30 grams/m3 (0.03 oz/ft3) can be used.
2.5.2.2 Arrange ducts containing combustible dust in concentrations that always or frequently exceed the
MEC, or that carry dust at velocities where dust settling out might be expected, as follows:
a) Route the ducts outside.
b) Provide an explosion-isolation device at each point of connection between the duct and a piece of
equipment.
c) Protect the duct from an explosion propagating in the explosible mixture by one of the following:
1. Provide venting for the duct in accordance with 2.5.2.3.
2. Design the duct to fail at pressures as low as practical but not more than 0.3 barg (4.4 psig).
2.5.2.2.1 Where the duct containing dust above the MEC or conveyed at less than the dust-settling velocity
must be located indoors, take the following precautions:
a) Provide an explosion-isolation device at each point of connection between the duct and a piece of
equipment, AND
b) design the duct to contain the explosion (shock resistant), OR
c) provide venting for the duct in accordance with 2.5.2.3 but route the vents outdoors.
2.5.2.3 Provide explosion venting along the length of a duct on the following basis:
a) Compute the maximum distance between explosion vents (Lmax) as follows:
√
4Ad
Deff =
π
2.6.1 Protection
2.6.1.1 When a dust storage silo has a dust collector (other than a simple vent sock) on the breather vent,
provide explosion protection as follows:
a) Treat the collector/silo combination as a single unit if either of the following conditions exist:
1. The duct connecting the silo to the dust collector has an L/D ratio less than 2, OR
2. The cross-sectional area of the connecting duct is at least as large as the explosion-venting area
needed to protect the volume of the dust collector alone.
b) Provide explosion venting for the silo/collector combination based on the total volume of the two units.
c) Install part of the explosion venting on the dust collector if possible, not to exceed the cross sectional
area of the connecting pipe, although all of the explosion venting can be on the silo.
2.6.1.2 Where the dust collector/silo combination does not meet the criteria of a single unit:
a) Provide explosion venting for each component based on their individual volumes.
b) Provide explosion venting for the connecting duct itself in accordance with 2.5.2.3.
2.6.1.3 Ensure the explosion venting area provided for a silo does not exceed its cross- sectional area (Ax-sect).
Any explosion venting in excess of this value will not help to decrease the explosion pressure.
2.6.1.3.1 If calculations show the explosion venting area required is more than the cross-sectional area, use
an explosion-suppression system or reinforce the silo so it can withstand the value of Pred corresponding
to Av = Ax-sect.
2.7.2 Protection
2.7.2.1 For enclosed bucket elevators handling dusts with a Kst of less than 200, provide explosion venting
based on the following:
A. Locate explosion vents along the height of the bucket elevator at a center to center spacing in
accordance with Table 2 based on the elevator type, Kst and the Pred of the enclosure.
B. Route explosion venting for indoor elevators to the outside by short (less than 3 ft [1 m]) straight ducts
or provide FM approved flameless vents.
C. Explosion vents can be installed on the sides or face of the casing.
D. Install explosion venting in the head section (top) equivalent to the cross sectional area of the casing
leg
E. Install the first casing vent as close as practical to the boot (bottom) of the bucket elevator but not to
exceed the spacing specified in Table 2.
F. Size explosion vent equivalent to the cross sectional area of the elevator leg enclosure. The vent area
can be installed as separate half-sized vents located on opposite sides of the enclosure.
G. Install explosion venting for the up and downside leg on double casing designs.
H. Set the explosion vent relief pressure (Pstat) to 0.1 barg (1.5 psig) or less and construct vents of
lightweight material.
2.7.2.2 Where the elevator head or boot feeds into equipment or areas that have an explosion hazard, provide
an explosion-blocking system using explosion-suppression devices or other types of physical barriers, such
as a rotary air lock between the head or boot and adjacent areas or equipment.
2.7.2.3 Protect bucket elevators using automatic sprinklers as follows:
a) At the top of the vertical bucket elevator shaft where the enclosure is noncombustible. If the enclosure
is constructed from combustible materials, provide additional automatic sprinkler protection along the shaft
(i.e., treat it as a vertical shaft with combustible sides), spaced every 10 to 12 ft (3 to 3.7 m).
b) Design the automatic sprinkler to deliver a minimum flow of 25 gpm (95 L/min) from the most remote
sprinkler.
c) Where sprinklers are in areas subject to freezing, be sure the installation is suitable for the temperatures
expected.
2.8.1 Protection
2.8.1.1 Spray dryers often operate with much of the dryer at less than the MEC. Provide explosion protection
in accordance with the following:
a) Obtain accurate calculations to confirm the average dust concentration within the cylindrically shaped
portion is below the MEC of the material being handled. On this basis, only the conical section at the
bottom of the dryer and any downstream equipment (e.g., cyclones, bag collectors) have an explosible
mixture.
b) Use FM Global’s DustCalc software for determining the explosion venting area required where a
combustible cloud exists in only a fraction of the total vessel volume.
c) Distribute explosion vents uniformly throughout the dryer surface although vents only near the conical
section are recommended.
2.8.1.2 For protection against fire, see DS 6-9, Industrial Ovens and Dryers, in the section “spray dryers
handling dust.”
2.10.2 Locate additive manufacturing equipment in areas segregated from other manufacturing or storage
by either a clear space, walls, or in a separate building.
2.10.3 Store, handle, and transport powders in closed, conductive containers.
2.10.4 Where powders with an MIE of less than 10 mJ are stored or handled in nonconductive containers,
use static-dissipative containers. Materials considered to be static dissipative have a surface resistance
between 105 and 109 ohms/square (NFPA 77).
2.10.5 Where powders are handled or transferred, control the unintended release of powders, the formation
of suspended clouds, and maintain a high level of housekeeping.
2.10.6 Where piping systems are used to transfer powder, control static accumulation using grounding and
bonding to a ground connection with a maximum resistance of 1 megohm.
2.10.7 If operating AM equipment under an inert atmosphere, do the following:
A. Operate at less than the LOC of the powder measured with the gas being used.
1. Where the LOC is greater than or equal to 5%, maintain a safety margin of at least 2 volume percent
below the LOC.
2. Where the LOC is less than 5%, operate the equipment at no more than 60% of the LOC.
B. Monitor the inert gas or oxygen concentration.
C. Interlock to system to prevent startup without an acceptable level of inerting.
D. Shut down the system when safe inert gas or oxygen levels are exceeded.
2.10.8 Process the completed product (harvesting) in a manner that minimizes or controls the release of
the entrained powders as follows:
A. Ensure operators are properly grounded prior to opening the print enclosure.
B. Conduct cleaning of excess dust from the product in a suitably ventilated hood or enclosure with a
properly designed dust collection system.
2.10.9 Ensure portable vacuums used for cleanup of excess powder are rated for use in a Class II, Division
2 or Zone 22 area, and components located within enclosures containing collected combustible dust are
rated for Class II, Division 1 or Zone 20.
2.10.9.1 Use portable vacuums that are certified by a reliable third-party agency.
2.10.10 For manufacturing and storage areas containing combustible construction or occupancy, provide
automatic sprinkler protection designed for a metal-working occupancy, HC2.
2.10.11 Where combustible metal dusts are handled or stored, install Class D portable extinguishers and
train personnel in their proper use.
ordinary construction, any area of dust accumulations exceeding about 1,000 ft2 (93 m2) is considered
unacceptable.
Any dust that is elevated above floor level in joists, beams, equipment tops, etc., should be considered as
being capable of being thrown into suspension. Dust that has agglomerated by age, heat, moisture, etc.,
should not be considered as capable of being thrown into suspension but may suggest an ongoing
housekeeping problem or source of uncontrolled release. Dust on the floor could be suspended but is less
of a risk than elevated accumulations.
Pay close attention to dust adhering to walls since this is easily dislodged. Also consider other projections,
such as light fixtures, that can provide surfaces for dust accumulation.
The available surface area for dust deposits on bar joists or steel beams can be roughly estimated at 5%
of floor area. However, some steel beams might have an equivalent surface area as high as 10% of floor area,
such as when spans between columns are longer than average for a given geographical area, or when a
large building elevation difference requires a stronger roof structure due to anticipated snow drift loadings.
For reference, the following represents typical bulk density data.
condensation on the inside of the vent. Additional insulation does not have to be applied over such a vent,
thus ensuring insulation does not hinder vent deployment.
The DustCalc software program can also provide solutions based on the NFPA or VDI methods and will
indicate where, and often why, there are differences with the FM Global method.
an explosion to the indoors without the fear of igniting nearby combustibles or creating damaging pressure
in the room. However, the exit gases are hot (approximately 212°F [100°C]).
The actual pressure effect of the released gases can be conservatively estimated based on an approximate
gas-exit temperature of 212°F (100°C) and the following equation:
∆p = 1.74 p0 V1
V0
where:
V0 is the building volume (m3 or ft3)
V1 is the vented equipment volume (m3 or ft3)
p0 is the absolute ambient pressure (14.7 psia or 1.01 bara)
∆p is the pressure increase created by the vented gases (psi or bar)
For example, where the equipment volume is 1/100 of the building volume, V1/V0 is 1/100, the pressure
increase is about 0.26 psi (18 mbar, 1.8 kPa). This would not cause any significant building damage.
The listing of all FM Approved devices includes their vent efficiency, which is the factor by which the effective
vent area of the device is reduced. This is different than the pressure effect calculation above.
Fig. 10. FM Approved flameless venting device (Photo courtesy of Rembe GmbH)
An extensive review of experimental data generated by numerous organizations worldwide has allowed
FM Global to correlate the data along a theoretical framework to produce an effective predictive tool.
FR = 119 Av Pred
Units: FR (kN), Av (m2), Pred (barg)
FR = 1.2 Av Pred
Units: FR (lb), Av (in2), Pred (psig)
b) For duration of this recoil force, use the following formula (applies only to enclosures without vent ducts):
Fs = 0.52 FR
Units: kN or lb as in the original equation
FM Global’s DustCalc software readily calculates the effects caused by pressure and fireballs.
is generally greater than the speed of the flame front. Therefore, at the moment when a dust explosion is
ignited within the second vessel, the initial pressure will be well above the normal (ambient) pressure.
For a given fuel-to-air ratio, the final, unvented pressure of an explosion is directly proportional to the initial
pressure. For example, if the first explosion prepressurizes the second vessel to 3 bar (44 psi) absolute,
then the final pressure of the explosion in the second vessel would increase by a factor of 3. For a dust with
a Pmax value of 9 bara, the final unvented pressure in this example would be 27 bara, well above the strength
of even the most sturdy vessel designed for dust explosion pressure containment. Thus, where explosion
containment is used as a protection method, it is important to provide explosion isolation to prevent
pre-pressurizing a vessel by another explosion.
When one vessel protected by explosion containment is connected to a second vessel protected with
explosion venting, a protection problem exists that is not related to pre-pressurization, but rather to the
turbulence created by the pressure front and a very strong ignition source from the flame front. The result
is a more rapid explosion in the second vessel, unaccounted for in the vent design, with failure of the second
vessel likely.
These effects occur to a lesser extent if the connected vessels are both protected with explosion venting.
Thus, where explosion venting is used as a protection method, it is important to provide explosion isolation
to separate the vented vessel from any connected vessels protected by explosion containment.
Dense phase pneumatic conveying systems operate at comparatively low transport velocity (200 to 1,000
fpm; 1 to 5 m/s), high solids loading rate, and high pressure (up to 125 psig; 8.6 barg). Because of the high
dust loading (well above the MEC), they are unlikely to be able to propagate the flame front from an explosion.
Dilute phase pneumatic conveying systems operate at high velocity (3,000 to 8,000 fpm; 25 to 40 m/s), low
solids loading rate, and low pressure (less then 15 psig; 1 barg).
Incendive electrostatic charges can be developed when insulative powders are transferred into silos or bins,
or where insulating linings (e.g., plastic) cover metal surfaces (lined metal ductwork). Charges on the surface
of an insulative powder pile can create brush discharges that are usually limited to 20 mJ and not likely to
ignite typical combustible dusts. Charges developed on lined surfaces can result in propagating brush
discharges that can release sufficient energy (hundreds of mJ) to ignite combustible dusts. If these
conditions exist, an evaluation should be performed by an expert in electrostatics.
surface could suddenly release enough static electricity to ignite a dust cloud. The repeated shaking or air
blasts to clean the bags could cause one or more ground straps to break or disconnect. Maintenance and
inspection activities are needed to prevent this from happening.
sufficient airflow typically on the order of 3500–4000 ft/min (1070–1220 m/min). Dust that has accumulated
can be re-entrained by the pressure wave from an explosion and create localized combustible concentrations,
moving with the pressure wave and ignited by the trailing flame front. After considerable propagation, this
turbulent jet flame becomes a very strong ignition source that destroys seemingly properly protected
equipment.
A remarkably small amount of deposited dust can propagate an explosion. For a circular duct of diameter
“D” with a dust layer of thickness “h” settled on 1⁄4 of its inner circumference (i.e., at the bottom), the
concentration of dust dispersed homogeneously throughout the cross section of the duct would be C = ρbulk
h/D. As an example, a dust with a bulk density of 31 lb/ft3 (500 kg/m3), a layer thickness of only 1/125 in.
(0.2 mm), and a duct of 8 in. (0.2 m) diameter, could generate a dust concentration of 500 g/m3. This
concentration is well above the MEC of virtually any dust, and therefore can propagate an explosion.
The settled dust is most likely not homogenously dispersed throughout the duct, but research by the US
Bureau of Mines has shown that explosions can propagate through ducts even at average dust concentrations
that are as little as half the MEC. All that is required for propagation is a continuous path of mixture that is
above the MEC. This condition can be satisfied even though there is not enough dust to fill the entire volume
of the duct with a mixture above the MEC. Thus, even very small amounts of dust can be sufficient to create
a propagating explosion so the air velocity through the duct should be sufficient to prevent any settling of
the transferred dust.
Explosion venting in duct work is not provided to save the duct, usually of low value and easily replaced,
but to reduce the violence of a potential explosion propagating down its length. This would not stop the
explosion propagation but would expose connected equipment containing suspended dust to a less energetic
ignition source. Designing the duct to fail at low pressure rather than installing explosion vents could be an
acceptable alternative approach where there is no exposure to equipment.
Explosion isolation systems may be needed for connecting ducts where the consequence of an unprotected
event in equipment or flash-back to a building is unacceptable. For example, a large panel sander might
have six dust pickup points, three on the top and three on the bottom, all joining into a common duct. Each
pickup pipe would not need an isolation device. Explosion isolation would best be provided on the main duct
after it leaves the building to prevent an explosion in the dust collector from propagating back towards the
sander.
Alternative solutions to air cannons include using vibratory wands inserted temporarily or permanently into
the bottom portion of the silo or using acoustic horns and lances.
Powder
AM Category bed
processes
Material
AM Category deposition
processes
The build material can be fine powdered metal, plastic, ceramic, or glass. Metal alloy powders in common
use include cobalt-chromium, aluminum-titanium, magnesium, stainless steel (iron and chromium plus other,
lesser additives) and Inconel (nickel and chromium with iron and other metals as lesser additives). Material
explosibility (Kst) varies with the particular metal or alloy and should generally be considered combustible
dust until proven otherwise by test.
Figure 16 shows examples of typical industrial printers. The ProX 300 and the Concept M2 have a build
envelope (chamber for the printing part) of about 250 x 250 x 300 mm (10 x 10 x 12 in.). The industrial-scale
printer can be US$0.5 million or more per machine.
3D Printing Liquid
AM Category
Sterolitho
Process Type graphy (SL)
Thermosets
Elastomer
Graphite
Lenses
Scanning mirror
Laser beam
Leveling roller
Sintered part
Powder
feed supply Powder bed
Fig. 15. SLS design concept (Chemical Engineering Progress, May 2014)
Fig. 16. Industrial-scale 3D systems: ProX300 and Concept M2 Laser printers (Source: manufacturers’ brochures)
The primary property hazards involve combustible dust handled in fine powder form (often 50 microns or
less), and ignitable liquid used by some systems. Only hazards associated with powder operations are
addressed here, with a focus on metal powders.
The metal-based processes run under low oxygen atmosphere (less than 1% oxygen) for product-quality
purposes and therefore don’t present an explosion hazard in the build chamber or the inert atmosphere
recirculation system. This system can include cartridge or panel filters that are primarily or completely
combustible construction. Most filters are used for two or three build cycles and then replaced. Some systems
identify the fumes from the laser process as a “highly flammable metal condensate,” requiring special
handling and precautions to prevent ignition, which could result in spontaneous smoldering events in the filters
as they are removed and exposed to air.
Since most current industrial machines only require small amounts of material (up to several hundred
pounds/kilograms in the largest) the process powders are handled in heavy fiberboard containers or plastic
bottles of no more than about 2 gal (7.6 L) in size. Static accumulation when transferring these powders
is possible and manufacturers typically recommend bonding and grounding of personnel, the containers, and
the machines during these operations. On the material handling side, given the current scale at which these
systems are used, controlling ignition sources by grounding, bonding, etc. is more practical than inerting
the operation.
Production-scale equipment will likely require other material-handling methods and will need to be evaluated
based on the properties of the powders involved, as with other combustible dusts.
The cleanup process for the build chamber would typically use portable vacuums, which need to be rated
for hazardous operations involving combustible metal or plastic dusts.
The completed parts are taken outside the equipment and excess powder is manually or mechanically shaken
off, or blown off using plant air, and then moved to other finishing processes. Some plastics are cleaned
using high-pressure water jets in a glove box enclosure. The air blowdown could create a small local dust
flash fire hazard, or an associated dust collection system could present a dust explosion hazard.
3.1.29.2 Protection
As noted previously, the machines handling combustible metal powders operate under inert atmospheres
and present no dust explosion hazard. Machines using other combustible powders would need to be
evaluated to understand how the process is operated and if significant clouds of combustible dust could be
created.
Machine enclosures completely contain the combustible powders and therefore create no need for hazardous
location electrical equipment for the surroundings.
If powder recovery operations are conducted using sieving or other methods, they should be conducted in
properly ventilated hoods. Similarly, cleanup of the product to remove powder from the interior spaces also
should be conducted within proper hoods or enclosures.
Conduct powder cleanup using portable vacuums properly designed for the service. There are no clear
standards for certification of vacuums for collecting metal or any other combustible dust. It appears that most
are rated for use in dust hazardous areas the same as other electrical equipment.
There is a standard, EN 60335 Part 2-69, Particular Requirements for Wet and Dry Vacuum Cleaners, that
broadly addresses the issue of certification of equipment for operation in zone 22 areas. Annex CC of that
document specifically addresses modifications to the main standard needed to qualify for use in zone 22.
Clause 24.1 of Annex CC states that “Components located within enclosures containing collected combustible
dust shall be suitable for zone 20.”
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-44, Damage Limiting Construction
Data Sheet 5-1, Electrical Equipment in Hazardous Locations
Data Sheet 5-8, Static Electricity
Data Sheet 5-20, Electrical Testing
Data Sheet 6-9, Industrial Ovens and Dryers
Data Sheet 7-10, Wood Processing and Woodworking Facilities
Data Sheet 7-17, Explosion Protection Systems
Data Sheet 7-32, Ignitable Liquid Operations
Data Sheet 7-59, Inerting and Purging of Tanks, Process Vessels and Equipment
Data Sheet 7-73, Dust Collectors and Collection Systems
Data Sheet 7-75, Grain Storage and Milling
Data Sheet 7-78, Industrial Exhaust Systems
Data Sheet 10-3, Hot Work Management
Hot Work Management Kit (P9601)
4.2 Other
Air Movement and Control Association (AMCA). Classifications for Spark Resistant Construction. AMCA
99040186, latest edition.
American Society for Testing and Materials (ASTM). Standard Test Method for Limiting Oxygen (Oxidant)
Concentration of Combustible Dust Clouds. E2931.
American Society for Testing and Materials (ASTM). Standard Test Method for Minimum Explosible
Concentration of Combustible Dusts. Standard E1515, latest edition.
American Society for Testing and Materials (ASTM). Standard Test Method for Minimum Ignition Energy of
a Dust Cloud in Air. ASTM E2019, latest edition.
American Society for Testing and Materials (ASTM). Standard Test Method for Pressure and Rate of Pressure
Rise of Combustible Dusts. Standard E1226, latest edition.
Bhatia, S. K. and S. Sharma. “3D Printed Prosthetics Roll off the Presses.” Chemical Engineering Progress,
May 2014.
European Committee for Standardization (CEN). Determination of Explosion Characteristics of Dust Clouds
- Part 1: Determination of the Maximum Explosion Pressure Pmax of Dust Clouds. EN 14034-1.
European Committee for Standardization (CEN). Determination of Explosion Characteristics of Dust Clouds
- Part 2: Determination of the Maximum Rate of Explosion Pressure Rise (dP/dt)max) of Dust Clouds. EN
14034-2.
European Committee for Standardization (CEN). Determination of Explosion Characteristics of Dust Clouds.
Part 3: Determination of the Lower Explosion Limit (LEL) of Dust Clouds. (Also called minimum explosible
concentration, MEC). EN 14034-3.
European Committee for Standardization (CEN). Determination of Explosion Characteristics of Dust Clouds.
Part 4: Determination of the Limiting Oxygen Concentration (LOC) of Dust Clouds. EN 14034-4.
European Committee for Standardization (CEN). Fire and Explosion Prevention and Protection for Bucket
Elevators. TR16829 (preliminary).
European Committee for Standardization (CEN). Household and Similar Electrical Appliances - Safety, Part
2-69: Particular Requirements for Wet and Dry Vacuum Cleaners, Including Power Brush for Commercial
Use. EN 60335-2-69.
European Committee for Standardization (CEN). Potentially Explosive Atmospheres - Explosion Prevention
and Protection - Determination of Minimum Ignition Energy of Dust/Air Mixtures. EN 13821.
Holbrow, P., G. A. Lunn, and A. Tyldesley. “Explosion Venting of Bucket Elevators.” Journal of Loss Prevention
in the Process Industries. Vol. 15, No. 5, 2002.
International Organization for Standardization (ISO). Explosion Protection Systems – Part 1: Determination
of Explosion Indices of Combustible Dusts in Air. ISO 6184/1, latest edition.
National Fire Protection Association (NFPA). Recommended Practice for the Classification of Combustible
Dusts and of Hazardous (Classified) Locations for Electrical Installation in Chemical Process Areas. NFPA
499, latest edition.
National Fire Protection Association (NFPA). Recommended Practice on Static Electricity. NFPA 77, latest
edition.
National Fire Protection Association (NFPA). Standard on Explosion Prevention Systems. NFPA 69, latest
edition.
National Fire Protection Association (NFPA). Standard on Explosion Protection by Deflagration Venting. NFPA
68, latest edition.
University of Exeter, Centre for Additive Layer Manufacturing. What is additive layer manufacturing?
http://emps.exeter.ac.uk/engineering/research/calm/whatis. Accessed October 16, 2016.
Verein Deutscher Ingenieure (VDI). VDI Guideline 2263 Part 8.1, Dust Fires and Dust Explosions; Hazards,
Assessment, Protective Measures; Fire and Explosion Protection on Elevators. 2011.
Verein Deutscher Ingenieure (VDI). VDI Guideline 3673, Part 1, ‘‘Pressure Venting of Dust Explosions.” Latest
edition.
Enclosureless Dust Collector: A device designed and used to remove dust from the transport air where the
filter media is not enclosed or in a container.
Explosion isolation: System or single device that prevents the propagation of explosion effects from one
volume to an adjacent volume.
Explosion mitigation: Methods used to reduce damage from the explosion after the explosion has started.
Explosion prevention: Methods used to prevent an explosion by controlling either the air, fuel, ignition source,
or a combination of these.
FM Approved: References to ’’FM Approved‘‘ in this data sheet mean the product or service has satisfied
the criteria for FM Approval. Refer to the Approval Guide for a complete listing of products and services that
are FM Approved.
Grounding: Electrical connection between a conductive object and the ground that minimizes the difference
in the electrical potential between the object and ground.
Ignitable Liquid: Any liquid or liquid mixture that is capable of fueling a fire, including flammable liquids,
combustible liquids, inflammable liquids, or any other reference to a liquid that will burn. An ignitable liquid
must have a fire point.
Kst: The dust explosibility constant, defined as the maximum rate of pressure rise of a dust explosion in a
1 cubic meter vessel. The units are bar meter per second (bar m/s). The test method used to obtain this
constant is standardized worldwide. This value (Kst) is used in all modern dust explosion vent sizing to
characterize the reactivity (i.e., explosibility) of a particular dust. Only metric units are used for this constant.
MEC: Minimum explosible concentration, the lowest concentration of dust that can support a self-propagating
explosion. (The terms LEL [lower explosible limit] or LFL [lower flammable limit] mean the same, but are
not often used in the context of dust explosions.)
Media type collector: A device (enclosure) that separates dry, solid material from air by passing the air through
a dry filtering medium. Examples are enclosures with bag-type filters, cartridge-type filters (normally a pleated
filter arranged in a cylindrical shape, similar to automobile air filters), rotary drum filters, and panel filters.
(See Data Sheet 1-45, Air Conditioning and Ventilating Systems, and Data Sheet 7-73, Dust Collectors and
Collection Systems, for information on filter types.)
MIE (minimum ignition energy): The minimum amount of thermal energy released at a point in a combustible
mixture to cause indefinite flame propagation under specified test conditions. The lowest value of MIE, known
as LMIE, is found at a certain optimum mixture. It is this value that is usually reported as the MIE.
Phlegmatization: The process of mixing inert dusts with combustible dusts to reduce or eliminate the explosion
hazard.
Pblast, : The localized pressure as a result of the fireball and pressure from a vented explosion.
max
Pmax: The maximum pressure developed in the 20-liter sphere when testing dust for explosibility
characteristics by ASTM E1226 method. It is factor used to help size explosion vents.
Pred: Highest explosion pressure in a vessel protected with explosion vents; usual units are barg or psig.
Pstat: Explosion vent relief pressure; usual units are barg or psig.
Psia: Pounds per square inch, absolute (unit of pressure).
Psig: Pounds per square inch, gauge (unit of pressure).
Strong ignition source: A strong ignition can provide more than approximately 100 Joules of energy.
a) Examples of a strong ignition source include open flame, welding arc, gas or dust explosion, and electric
arc/short.
b) Conversely, examples that would not be considered a strong ignition source include frictional sparks,
mechanical impact sparks, static sparks, cigarettes, hot surfaces, overheated electrical components.
Strong vessel: A vessel that can withstand explosion pressures in excess of 0.2 barg (3 psig) without being
damaged or destroyed. This includes most process vessels constructed or used in Europe.
Tube sheet: The mounting plate for cartridge-type filters or bag-type filter tubes and cages.
Ultimate strength: Pressure at which an enclosure will be torn open (i.e., ruptured).
Weak vessel or enclosure: A structure that cannot withstand explosion pressures in excess of 0.2 barg
(3 psig) without being damaged or destroyed. This includes most rooms, buildings, and many North American
process vessels.
Yield strength: Pressure at which an enclosure will be deformed without rupturing.
This data sheet includes many new recommendations which were not in the 1976 edition but many locations
will require less protection than the previous version required. The following exceptions have been made
to the general explosion protection requirements:
• Explosion venting is not needed for cyclones handling dusts with a Kst less than 80 (weakly explosible)
and having an open gas outlet on top whose diameter equals or exceeds 45% of the cyclone diameter.
• Systems operating at a pressure below 0.1 bara (1.5 psia) require no protection.
• Spray dryers require a reduced amount of explosion venting compared to other equipment with the same
volume. Note: the explosion venting area for spray dryers and for other equipment is now calculated using
the FM Global Research DustCalc software.
APPENDIX D BIBLIOGRAPHY
1. Bartknecht, W. Dust Explosions: Course, Prevention, Protection. Springer-Verlag, New York, NY, 1989.
2. Alfert, F., and K. Fuhre. Flame and Dust Free Venting of Dust Explosions by Means of a Quenching Pipe.
CMI-Report No. 89-25820-1. Chr. Michelsen Institute (Norway), 1989.
3. Eckoff, R. K. Dust Explosions in the Process Industries. Butterworth-Heinemann, Oxford, 1991.
4. van Wingerden, K. “Prediction of pressure and flame effects in the direct surroundings of installations
protected by dust explosion venting.” Journal of Loss Prevention in the Process Industries (Vol. 6, No. 4,
1993): 241–249.
5. WirknerBott, I., et. al. ’’Dust Explosion Venting: Investigation of the Secondary Explosion.‘‘ Paper presented
at the Seventh International Symposium on Loss Prevention and Safety Promotion in the Process Industries,
Taormina, Italy, 1992.
6. Lunn, G. A. Dust Explosion Prevention and Protection Part 3 — Venting of Weak Explosions and the Effect
of Vent Ducts. Rugby: Institute of Chemical Engineers, 1988.
7. Cooper, M. G., et. al. ’’On the Mechanisms of Pressure Generation in Vented Explosions.‘‘ Combustion
and Flame (1986) 65: 1–14.
8. Cubbage, P. A., and W. A. Simmonds. ’’An Investigation of Explosion Reliefs for Industrial Drying Ovens.
I-Top Reliefs in Box Ovens.‘‘ Transactions of the Institute of Gas Engineers (1955) 105: 470-526.
9. Siwek, R., and O. Skov. ’’Modellberechnung zur Dimensionierung von Explosionsklappen auf der Basis
von praxisnahen Explosionsversuchen.‘‘ VDI Berichte (1988) 701: 569-616.
10. Pineau, J. P. ’’Protection Against Fire and Explosion in Milk Powder Plants.‘‘ Europex First International
Symposium, Antwerp, Belgium, April 16–19, 1984.
11.Hurlimann, H. ’’Results from Real Scale Explosion Tests.‘‘ Third International Symposium on Loss
Prevention and Safety Promotion in the Process Industries, Basel, Switzerland, 1980.
12. van Wingerden, C. J. M., and H. J. Pasman. ’’Explosion Venting of Partially Filled Enclosures.‘‘ Conference
on Flammable Dust Explosions, St. Louis, Missouri, USA, November 2–4, 1988.
13. Zeeuwen, J. P., and G. G. M. van Laar. ’’Explosion Venting of Enclosures Partially Filled with Flammable
DustAir Mixtures.‘‘ International Symposium on Control of Risks in Handling and Storage of Granular Foods,
Paris, France, April 2426, 1985.
14. Siwek, R. ’’New Knowledge About Rotary Air Locks in Preventing Dust Ignition Breakthrough.‘‘ Plant
Operations Progress (July 1989) Vol. 8, No. 3: 165-176.
15. Green, D. W., and R. H. Perry. Perry’s Chemical Engineers’ Handbook, Eighth Edition (Chemical
Engineers Handbook). New York: McGraw-Hill, 2007.
16. DeGood, R. ’’Isolation: Another Way to Take the Bang out of Explosions.‘‘ CPI Equipment Reporter
(Jan-Feb 1988).
17. Siwek, R. ’’A Review of Explosion Isolating Techniques.‘‘ Europex International Seminar, March 1996.