3rd FLR Hand Calculation3
3rd FLR Hand Calculation3
lx x
½ Column strip
Middle strip
ly
½ Column strip
½ Column strip Middle strip ½ Column strip
194 mm
220 mm
200 mm
Section at middle strip along X axis
Slab definition
Slab thickness; h = 220 mm
Span along x – dir; lx = 7800 mm
Span along y – dir; ly = 8050 mm
Long span to short span ratio less than 2, hence two-way slab
Clear cover to positive reinforcement; cc = 20 mm
Clear cover to negative reinforcement; c’c = 20 mm
Effective flanged beam section
Flange width; bf = 300 mm
Beam depth; hb = 600 mm
Beam width; bw = 300 mm
Materials
Specified compressive strength of concrete; f’c = 25 MPa
Specified yield strength of reinforcement; fy = 400 MPa
Modulus of elasticity; ESACI = 199948MPa
Concrete type; Normal weight
Project Job Ref.
3RD FLR HAND CALCULATION3
Section Sheet no./rev.
2
Calc. by Date Chk'd by Date App'd by Date
M 8/16/2019
Loads
Total factored ultimate load on slab; wu = 13.40 kN/m2
Check for the depth of slab provided
Clear span x – dir – cl. 13.6.2.5; lnx = max(0.65 lx, (lx - bw / 2 - bw / 2)) = 7500 mm
Clear span y – dir – cl. 13.6.2.5; lny = max(0.65 ly, (ly - bw / 2 - bw / 2)) = 7750 mm
Ratio; = max(lnx, lny) / min(lnx, lny) = 1.033
Moment of inertia of beam; Ib = 5400000000 mm4
Moment of inertia of slab along x – axis; Isx = 7143033333 mm4
Moment of inertia of slab along y – axis; Isy = 6921200000 mm4
Flexural stiffness ratio along x – axis; fx = Ib / Isx = 0.756
Flexural stiffness ratio along y – axis; fy = Ib / Isy = 0.780
Average flexural stiffness ratio; fm = (fx × 2 + fy × 2) / 4 = 0.768
Minimum depth required – cl. 9.5.3; hmin = 217 mm
PASS - slab thickness provided is sufficient for deflection
Moment computation (x – direction)
Width of column strip (half) – cl. 13.2.1; lcol_stp = min(0.25 × lx, 0.25 × ly) = 1950 mm
Width of middle strip – cl. 13.2.2; lmid_stp_x = ly - 2 × lcol_stp = 4150 mm
Factored moment - eqn. 13-4; Mox = wu × ly × lnx2 / 8 = 758.46 kNm
Moment distribution for interior panel – cl. 13.6.3.2; M’ux = 0.65 × Mox = 493.00 kNm
Mux = 0.35 × Mox = 265.46 kNm
Moment distribution in column and middle strips
ly / lx = 1.03
fx × ly / lx = 0.78
Moment distribution factors; fx_neg = 0.74
fx_pos = 0.71
Total column strip design moments; M’x_col_stp = fx_neg × M’ux = 366.05 kNm
Mx_col_stp = fx_pos × Mux = 188.35 kNm
Column strip beam moments; M’x_beam = 242.76 kNm
Mx_beam = 124.91 kNm
Column strip slab moments; M’x_slab = M’x_col_stp - M’x_beam = 123.29 kNm
Mx_slab = Mx_col_stp - Mx_beam = 63.44 kNm
Total middle strip design moments; M’x_mid_stp = (1 - fx_neg) × M’ux = 126.95 kNm
Mx_mid_stp = (1 - fx_pos) × Mux = 77.11 kNm
Required flexural nominal strength in column strip per 1 m width of slab
M’nx_col = M’x_slab / (0.9 × (2 × lcol_stp - bf)) = 38.05 kNm/m
Mnx_col = Mx_slab / (0.9 × (2 × lcol_stp - bf)) = 19.58 kNm/m
Required flexural nominal strength in middle strip per 1 m width of slab
M’nx_mid = M’x_mid_stp / (0.9 × lmid_stp_x) = 33.99 kNm/m
Mnx_mid = Mx_mid_stp / (0.9 × lmid_stp_x) = 20.64 kNm/m
Moment computation (y – direction)
Width of column strip (half) – cl. 13.2.1; lcol_stp = min(0.25 × lx, 0.25 × ly) = 1950 mm
Width of middle strip – cl. 13.2.2; lmid_stp_y = lx - 2 × lcol_stp = 3900 mm
Factored moment - eqn. 13-4; Moy = wu × lx × lny2 / 8 = 784.72 kNm
Project Job Ref.
3RD FLR HAND CALCULATION3
Section Sheet no./rev.
3
Calc. by Date Chk'd by Date App'd by Date
M 8/16/2019
Moment distribution for interior panel – cl. 13.6.3.2; M’uy = 0.65 × Moy = 510.07 kNm
Muy = 0.35 × Moy = 274.65 kNm
Moment distribution in column and middle strips
lx / ly = 0.97
fy × lx / ly = 0.76
Moment distribution factors; fy_neg = 0.76
fy_pos = 0.72
Total column strip design moments; M’y_col_stp = fy_neg × M’uy = 386.14 kNm
My_col_stp = fy_pos × Muy = 197.87 kNm
Column strip beam moments; M’y_beam = 248.13 kNm
My_beam = 127.15 kNm
Column strip slab moments; M’y_slab = M’y_col_stp - M’y_beam = 138.01 kNm
My_slab = My_col_stp - My_beam = 70.72 kNm
Total middle strip design moments; M’y_mid_stp = (1 - fy_neg) × M’uy = 123.92 kNm
My_mid_stp = (1 - fy_pos) × Muy = 76.78 kNm
Required flexural nominal strength in column strip per 1 m width of slab
M’ny_col = M’y_slab / (0.9 × (2 × lcol_stp - bf)) = 42.60 kNm/m
Mny_col = My_slab / (0.9 × (2 × lcol_stp - bf)) = 21.83 kNm/m
Required flexural nominal strength in middle strip per 1 m width of slab
M’ny_mid = M’y_mid_stp / (0.9 × lmid_stp_y) = 35.31 kNm/m
Mny_mid = My_mid_stp / (0.9 × lmid_stp_y) = 21.87 kNm/m
Reinforcement calculations
Stress block depth factor; 1 = 0.85
Reinforcement percentage at strain of 0.004; b = 0.85 1 f’c / fy (0.003 / (0.003 + 0.004)) = 0.019
Maximum reinforcement percentage; max = b = 0.019
Minimum reinforcement percentage – cl. 7.12.2.1; min = If(fy < 415 MPa,0.0020,max(0.0014, 0.0018 415 MPa / fy)) = 0.0020
Minimum area of steel required; Amin = min h = 440 mm2/m
Maximum allowable spacing – cl. 13.3.2; smax = min (2 × h, 450 mm) = 440 mm
Column strip (x – direction)
Negative Reinforcement
Depth to negative steel; d’x_col = h - c’c - D’col_x / 2 = 194 mm
Flexural resistance factor; R’ux_col = M’nx_col / d’x_col2 = 1.01 MPa
Reinforcement required; ’reqx_col =0.85f’c/fy×[1-(abs(1-2×R’ux_col /(0.85×f’c)))] = 0.00259
Outer compression steel not required
Area of tension steel required; A’sx_req_col = ’reqx_col × d’x_col = 503 mm2/m
Maximum area of tension steel; A’sx_max_col = max × d’x_col = 3754 mm2/m
Reinforcement provided (negative), 12 mm @ 150 mm centers
Area of tension steel provided; A’sx_col = 754 mm2/m
PASS - area of steel provided is OK
Actual tensile bar spacing provided; s’x_col = 150 mm
PASS - spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dx_col = h - cc - Dcol_x / 2 = 194 mm
Flexural resistance factor; Rux_col = Mnx_col / dx_col2 = 0.52 MPa
Project Job Ref.
3RD FLR HAND CALCULATION3
Section Sheet no./rev.
4
Calc. by Date Chk'd by Date App'd by Date
M 8/16/2019
lx x
½ Column strip
A'sy_col
Asx_col A'sx_col
Asy_mid
Middle strip
ly
Asx_mid A'sx_mid
Asy_col
½ Column strip
A'sy_mid