Tedds Calculation Version 2.1.02

This document summarizes the wind load calculations for a monoslope roof building according to ASCE7-10 standards. It provides details on the building dimensions and wind conditions, and calculates the net wind forces on the roof for two load cases - wind from the front and wind from the side. The results show net vertical forces of -106.32 kN for the front wind case and -73.82 kN for the side wind case. It also confirms the minimum design wind loading is satisfied.

Uploaded by

mondaldgp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views

Tedds Calculation Version 2.1.02

This document summarizes the wind load calculations for a monoslope roof building according to ASCE7-10 standards. It provides details on the building dimensions and wind conditions, and calculates the net wind forces on the roof for two load cases - wind from the front and wind from the side. The results show net vertical forces of -106.32 kN for the front wind case and -73.82 kN for the side wind case. It also confirms the minimum design wind loading is satisfied.

Uploaded by

mondaldgp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

WIND LOADING

In accordance with ASCE7-10

Using the directional design method


Tedds calculation version 2.1.02

Building data
Type of roof Monoslope free
Length of building b = 13724 mm
Width of building d = 8131 mm
Height to eaves H = 2000 mm
Pitch of roof 0 = 0.0 deg
Mean height h = 2000 mm
Wind flow Clear

General wind load requirements


Basic wind speed V = 59.0 m/s
Risk category II
Velocity pressure exponent coef (Table 26.6-1) Kd = 0.85
Exposure category (cl 26.7.3) D
Enclosure classification (cl.26.10) Open buildings
Internal pressure coef +ve (Table 26.11-1) GC pi_p = 0.00
Internal pressure coef –ve (Table 26.11-1) GC pi_n = 0.00
Gust effect factor Gf = 0.85

Topography
Topography factor not significant Kzt = 1.0

Velocity pressure
Velocity pressure coefficient (T.27.3-1) Kz = 1.03
Velocity pressure qh = 0.6131N/m2  Kz  Kzt  Kd  V2 / (1m/s)2 = 1.9
kN/m2

Peak velocity pressure for internal pressure


Peak velocity pressure – internal (as roof press.) qi = 1.868 kN/m2
Pressures and forces
Net pressure p = q h  G  CN
Net force Fw = p  A ref
Minimum design wind loading (cl.27.4.7) pmin_r = 0.77 kN/m2

Roof load case 1 - Wind 0, Loadcase B

Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cN pressure qh p Aref Fw
(m) (kN/m2) (kN/m2) (m2) (kN)
1 (+ve) 2.00 -1.10 1.87 -1.75 55.79 -97.46
2 (+ve) 2.00 -0.10 1.87 -0.16 55.79 -8.86
Total vertical net force Fw,v = -106.32 kN
Total horizontal net force Fw,h = 0.00 kN

Minimum loading
Projected vertical area of roof Avert_r_0 = b  d  tan(0) = 0.00 m2
Minimum overall horizontal loading Fw,total_min = pmin_r  A vert_r_0 = 0.0 kN

Roof load case 2 - Wind 90, Loadcase A

Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cN pressure qh p Aref Fw
(m) (kN/m2) (kN/m2) (m2) (kN)
1 (+ve) 2.00 -0.80 1.87 -1.27 16.26 -20.66
2 (+ve) 2.00 -0.60 1.87 -0.95 16.26 -15.49
3 (+ve) 2.00 -0.30 1.87 -0.48 79.06 -37.67
Total vertical net force Fw,v = -73.82 kN
Total horizontal net force Fw,h = 0.00 kN

Minimum loading
Projected vertical area of roof Avert_r_90 = 0.00 m2
Minimum overall horizontal loading Fw,total_min = pmin_r  A vert_r_90 = 0.0 kN